Dunkirk EMPIRE 3EWC0.80 Installation, Operation & Maintenance Manual Download Page 27

27

Annually

Recommend flue passages, combustion 

chamber area (target wall, fire door insulation, 

durablanket), burner adjustment, control operation, and 

boiler seals (fire door gasket or silicone seal, cast iron 

sectional seals, flue collector) be checked once each year 

by trained Service Technician. 

Before The Start Of Each Heating Season

 

(or when 

system has been shut down for extended periods of time) 

recheck whole system for water, oil, and vent piping leaks. 

Replace or patch any leaks or faulty seals.

Vent Pipe:

 Visually inspect entire venting system once a 

month for any signs of leakage, deterioration, or soot build 

up. If vent pipe shows any signs of leaking or deterioration, 

replace it immediately. If it shows any signs of soot 

build up, clean vent pipe and have burner settings and 

combustion checked by trained Service Technician.

Safety Relief Valve:

 Valve should open automatically 

when system pressure exceeds pressure rating (usually 30 

psi) of safety relief valve. Should valve ever fail to open 

under this condition, shut down the system. Drain system 

until system pressure is reduced below safety relief valve 

pressure rating. Contact Service Technician to replace the 

valve and inspect heating system to determine cause, may 

indicate equipment malfunction. Safety relief valve should 

be tested monthly during heating season. Prior to testing, 

make certain discharge pipe is properly connected to valve 

outlet and arranged so as to contain and safely dispose of 

boiler discharge. Hold trip lever fully open for at least five 

seconds in order to flush free any sediment that may lodge 

on valve seat. Permit valve to snap shut. Refer to valve 

manufacturer’s instructions packaged for more details.

 

Conventional Expansion Tank

:

 Tank may become 

water logged or may receive excess air. Frequent automatic 

opening of safety relief valve indicates water logging. High 

boiler temperature accompanied by unusually low radiation 

unit temperature (and “knocking” noises) indicates excess 

air in the tank. To correct either condition, close valve 

between boiler and tank. Drain tank until empty. Check all 

tank plugs and fittings, tighten as necessary. Open valve 

between boiler and tank. Water will rise to normal height in 

tank if system has automatic fill valve, otherwise manually 

refill system. 

Diaphragm Expansion Tank

:

 Tank may become 

water logged. Frequent automatic opening of safety relief 

valve indicates water logging. High boiler temperature 

accompanied by unusually low radiation unit temperature 

(and “knocking” noises) indicates excess air in the tank. To 

correct this condition, replace diaphragm expansion tank.

Water System: 

If system is to remain out of service 

during freezing weather, drain it completely (water left in 

system may freeze and will crack pipes and/or boiler).

Tankless Coil (Or Cover Plate) Gasket:  

Gasket 

should be checked at least twice year for leakage, replace if 

necessary. If gasket is replaced, make sure that when coil 

plate (or cover plate) is reattached, ten nuts are torqued 

in alternating pattern to insure equal force is applied to 

entire gasket creating good seal. Nuts should be torqued so 

gasket does not squeeze out from behind the plate.

Control Well:

 

Remove control well every five years and 

clean any scale or sediment deposits from all parts exposed 

to boiler water.  After cleaning, reinstall well using pipe 

sealing compound. Teflon tape is not recommended.

Never burn garbage or paper in the unit, never leave 

combustible material around it.

MAINTENANCE

 WARNING

Burn, scald hazard.  Some maintenance tasks 

require draining the boiler. Verify boiler is cool and 

at zero pressure before draining.  Verify boiler is 

appropriately drained before removing relief valve, 

control well, tankless coil etc. Failure to follow these 

instructions could result in death or serious injury.

!

  

Oil Burner Maintenance

: Perform following 

preventative maintenance annually, prior to heating 

season.

1. 

Do not oil. 

Oil burner motors are permanently 

lubricated.  

2. 

Fuel Filter  Replace to prevent contaminated fuel from 

reaching nozzle. Partially blocked fuel filter can cause 

premature failure of fuel pump.

3. 

Fuel Pump Unit  Replace pump screen and clean pump 

unit to maintain fuel delivery to nozzle.

4. 

Ignition Electrodes

  Clean and adjust per 

manufacturer’s recommendations, to maintain reliable 

ignition of oil.

5. 

Nozzle  Replace to maintain safe and reliable 

combustion efficiency. Replace with nozzle as required 

in charts located in this manual.

6. 

Fan and Blower Housing

  Must be kept clean, free of 

dirt, lint and oil to maintain proper amount of air fuel 

requires to burn.

7. 

Check Final Burner Adjustments.

If any component parts must be replaced, always use parts 

recommended by burner manufacturer.

 

PN 240013012, Rev. B [12/15/2020]

Summary of Contents for EMPIRE 3EWC0.80

Page 1: ...ON MAINTENANCE MANUAL Maximum Allowable Working Pressure 50 psi Models 3EWC0 80 T 4EWC1 00 T 4EWC1 25 T 5EWC1 55 T Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 54...

Page 2: ...at this heat stays in the structure Net AHRI Rating represents portion of remaining heat that can be applied to heat radiation or terminal units finned tube baseboard cast iron radiators radiant floor...

Page 3: ...British Thermal Unit Heating Capacity based on 13 1 CO2 with a 0 02 w c draft over fire and a 1 smoke or less Testing was done in accordance with the D O E Department of Energy test procedure gph Gal...

Page 4: ...nent injury Children elderly and infirm or physically handicapped persons are more likely to be permanently injured by hot water Never leave them unattended in bathtub or shower Never allow small chil...

Page 5: ...e hindered by overfilling the boiler Recommend initial fill pressure of 10 12 psig For higher fill pressures expansion tank s air charge will need to be increased to match fill pressure Consult manufa...

Page 6: ...uire attention Install boilers at least 6 from combustible material on left side rear and above and at least 24 on right side and front Allow at least 24 accessibility clearance above for servicing 5...

Page 7: ...IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED SAFETY SWITCH 2 FILL PIPE MIN 2 I D...

Page 8: ...y with additional room s of sufficient volume so the combined volume of all spaces meets the criteria for unconfined space Total input of all combustion equipment installed in combined space shall be...

Page 9: ...3 When communicating with outdoors through horizontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of all equipment in the enclosure...

Page 10: ...res 6a and 6b A Install safety relief valve with spindle in vertical position B Do not install shutoff valve between boiler and safety relief valve C Install discharge piping from safety relief valve...

Page 11: ...ally cause damage to boiler and venting system Minimum design return water temperature to prevent this condensation in boiler and venting is 120 F Boiler used in heating system where design water temp...

Page 12: ...NOTE CIRCULATOR CAN ALSO BE INSTALLED ON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 Figure 8 Syst...

Page 13: ...XPANSION TANK PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure 9 System Piping Arrangement Zonin...

Page 14: ...G PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATORS SYSTEM PIPING Figure 10 System P...

Page 15: ...uous flow NOTICE Do not use tankless coil if your water is excessively hard with lime or other deposits which will accumulate inside the coil When using tankless coil the Hydrolevel control is mounted...

Page 16: ...ent installations shall be in accordance with applicable provisions of NFPA 31 Standard for the installation of Oil Burning Equipment latest edition and applicable provisions of local building codes N...

Page 17: ...e boiler Install chimney connector start at boiler with vertical pipe elbow then install draft regulator horizontally When regulator is in place start at chimney and work back to the regulator Join th...

Page 18: ...THAN HIGHEST PART OF PASSAGE THROUGH ROOF MUST BE AT LEAST 2 FT HIGHER THAN ANY NEIGHBORING OBJECT WITHIN 10 FT MUS MUST HAVE AN UNOBSTRUCTED TOP OPENING TYPICAL CHIMNEY CONNECTION Figure 12 Typical...

Page 19: ...lations Connect 120 volt electrical supply to L1 and L2 terminals and two thermostat wires to T and T terminals on Hydrolevel limit control Run separate circuit from separate over current protection d...

Page 20: ...20 ELECTRICAL WIRING Figure 13 Hydrolevel 3250 Control with Beckett or Carlin Burner PN 240013012 Rev B 12 15 2020...

Page 21: ...21 Figure 14 Hydrolevel 3250 Control with Riello Burner ELECTRICAL WIRING PN 240013012 Rev B 12 15 2020...

Page 22: ...e runs air free close isolation valve or zone valve Repeat this procedure for remaining heating zones D Once all zones are filled with water and purged of air close power purging drain valve and fill...

Page 23: ...rner flame will be dark orange and formation of soot will occur in heating unit In buildings of conventional frame brick or stone construction that do not have utility rooms basement windows or stair...

Page 24: ...1HP 0 80 2 1 4 0 65 60 W 150 0 60 0 65 50 4EWC1 00 T EZ 1HP 1 00 2 1 4 0 85 60 B 150 0 85 1 00 60 4EWC1 25 T EZ 1HP 1 25 2 1 4 1 00 60 B 155 0 85 1 00 75 5EWC1 55 T EZ 1HP 1 55 2 1 4 1 25 60 B 155 1 1...

Page 25: ...trode Setting Figure 17 Riello Turbulator Setting Figure 18 Carlin Electrode Setting Turbulator Setting A Loosen NUT 1 turn SCREW 2 until INDEX MARKER 3 is aligned with correct index number per Burner...

Page 26: ...chamber is very hot Adjust Thermostat Heat Anticipator or Thermostat Cycle Rate According to Instructions Included With The Thermostat Check Thermostat Operation Follow instructions included with you...

Page 27: ...manually refill system Diaphragm Expansion Tank Tank may become water logged Frequent automatic opening of safety relief valve indicates water logging High boiler temperature accompanied by unusually...

Page 28: ...nd of flue brush off and inserting it into drill When brushing take care to not damage target wall with flue brush 6 Carefully vacuum soot accumulations from combustion chamber area take care to not d...

Page 29: ...ure head location and size if applicable are per manufacturer s recommendations If burner being used has damaged head replace head with same head recommended for use on this boiler 6 Inspect and clean...

Page 30: ...ectric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It may be in close...

Page 31: ...31 PUMP CURVES 15 10 5 0 5 4 3 2 1 m Head 1 2 3 4 5 US GPM 5 10 15 20 m h 3 Head feet Grundfos UP15 42F Pump Curve B G NRF22 Pump Curve PN 240013012 Rev B 12 15 2020...

Page 32: ...decreases This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED U...

Reviews: