Dunkirk EMPIRE 3EWC0.80 Installation, Operation & Maintenance Manual Download Page 23

23

Draft Regulators:

 Barometric draft regulator is required 

for controlling draft through boiler. Mount barometric draft 

regulator in chimney connector. Refer back to section on 

“Chimney And Chimney Connections”. Once draft regulator 

is installed, use draft gauge to adjust to proper opening: 

A. 

Combustion chamber over fire draft shall be -0.01” 

WC to  -0.02” WC.

B. 

Stack draft will be approximately -0.02” WC. to 

-0.04” WC. 

C. 

Larger installation, greater draft will be required in 

stack to obtain desired over fire draft.

Start:

 Fill entire system with water. Vent all air from 

system following section for Filling The Boiler.

Fuel Units And Oil Lines:

 

• 

Install oil line(s) to oil burner.

• 

Recommend using heavy wall copper tubing and 

flared fittings, not compression fittings. 

• 

All connections and joints must be absolutely airtight. 

Use an appropriate non-hardening thread sealing 

compound on the threaded connections, not Teflon 

tape. 

• 

See fuel unit data sheet furnished with the burner for 

sizing, lift, and length of tubing recommendations.

Oil burner is equipped with single stage fuel unit for single 

pipe installation. Satisfactory where fuel supply is on same 

level as or above burner permitting gravity flow of oil. Per 

NFPA 31 requirements, never exceed 3 psig pressure to 

inlet side of fuel unit. 

When necessary to lift oil to burner, two pipe installation 

is required. Run return line between fuel unit and oil 

supply. Refer to fuel unit instructions furnished with burner 

for specific instructions on two pipe installations. Do not 

exceed fuel unit manufacturer’s recommendations for 

running vacuum. 

NOTICE

If lift exceeds 14 feet for Beckett or Carlin burners 

or 11 feet for Riello burners, two stage fuel unit is 

required with return line.

Install oil filter of adequate size inside building between 

tank shutoff valve and oil burner. For ease of servicing, 

locate shutoff valve and filter near oil burner.

Air Supply For Combustion:

 

• 

Do not install boiler in rooms with insufficient air, unless 

corrective steps are taken. 

• 

It may be necessary to install windows or cut holes in 

a door to rooms used for supply air to obtain sufficient 

combustion air and prevent less than atmospheric air 

pressure in that room. 

• 

If there is a lack of combustion air, burner flame will be 

dark orange and formation of soot will occur in heating 

unit. 

• 

In buildings of conventional frame, brick, or stone 

construction that do not have utility rooms, basement 

windows, or stair doors, air infiltration is normally 

adequate to provide enough air for combustion and for 

operation of barometric draft control. 

• 

Room used for supplying combustion air should be 

isolated from any area served by exhaust fans. 

• 

Refer to the section "

Fresh Air For Combustion

" for 

additional sizing guidelines.

OPERATING THE BOILER  

Nozzles And Electrodes

:

 Use proper size, spray angle, 

and spray pattern nozzle. 
To install nozzle, remove nozzle line electrode assembly, 

if necessary remove retention ring assembly, and install 

and tighten nozzle. Take care not to damage electrode 

insulators or bend electrode tips. 

After installing nozzle, reassemble nozzle line electrode 

assembly and set electrode tip spacing. 
Depending on burner type, electrode tip spacing may 

need to be set prior to reassembling nozzle line electrode 

assembly. 

Refer to following pages for setting electrode tip spacing.

Final Burner Adjustments:

 

Final burner adjustments 

must be made using combustion test instruments. Refer 

to preliminary burner settings charts for initial startup. Set 

burner accordingly. 

• 

Check draft over fire to verify it is between -0.01” WC 

and -0.02” WC, adjust draft as necessary. 

• 

After operating 10 minutes to warm up boiler, use 

combustion test equipment to take smoke reading in 

flue pipe between boiler and draft regulator. 

• 

Smoke reading should be zero to trace (Shell Bacharach 

Scale). 

• 

A new boiler requires more than 10 minutes to burn 

clean due to oil film on new heat exchanger. 

• 

If smoke reading is zero, gradually close burner’s air 

adjustment to obtain smoke reading showing trace 

smoke reading. Once smoke reading is trace, measure 

CO

2

 and as insurance margin increase air to sufficiently 

reduce CO

2

 by ½% to 1%.

If clean fire cannot be obtained, it is necessary to verify 

burner head and electrode alignment. Proper electrode 

alignment figures are presented on following pages. If 

fire continues to be smoky, replace nozzle with correct 

replacement.

Once burner is completely adjusted, start and stop burner 

several times to assure good operation with no fluttering 

or rumbling. Verify there are no oil leaks. Record nozzle 

size, oil pressure, combustion readings, and air settings on 

tag or label attached to burner or, boiler.

 

PN 240013012, Rev. B [12/15/2020]

Summary of Contents for EMPIRE 3EWC0.80

Page 1: ...ON MAINTENANCE MANUAL Maximum Allowable Working Pressure 50 psi Models 3EWC0 80 T 4EWC1 00 T 4EWC1 25 T 5EWC1 55 T Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 54...

Page 2: ...at this heat stays in the structure Net AHRI Rating represents portion of remaining heat that can be applied to heat radiation or terminal units finned tube baseboard cast iron radiators radiant floor...

Page 3: ...British Thermal Unit Heating Capacity based on 13 1 CO2 with a 0 02 w c draft over fire and a 1 smoke or less Testing was done in accordance with the D O E Department of Energy test procedure gph Gal...

Page 4: ...nent injury Children elderly and infirm or physically handicapped persons are more likely to be permanently injured by hot water Never leave them unattended in bathtub or shower Never allow small chil...

Page 5: ...e hindered by overfilling the boiler Recommend initial fill pressure of 10 12 psig For higher fill pressures expansion tank s air charge will need to be increased to match fill pressure Consult manufa...

Page 6: ...uire attention Install boilers at least 6 from combustible material on left side rear and above and at least 24 on right side and front Allow at least 24 accessibility clearance above for servicing 5...

Page 7: ...IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED SAFETY SWITCH 2 FILL PIPE MIN 2 I D...

Page 8: ...y with additional room s of sufficient volume so the combined volume of all spaces meets the criteria for unconfined space Total input of all combustion equipment installed in combined space shall be...

Page 9: ...3 When communicating with outdoors through horizontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of all equipment in the enclosure...

Page 10: ...res 6a and 6b A Install safety relief valve with spindle in vertical position B Do not install shutoff valve between boiler and safety relief valve C Install discharge piping from safety relief valve...

Page 11: ...ally cause damage to boiler and venting system Minimum design return water temperature to prevent this condensation in boiler and venting is 120 F Boiler used in heating system where design water temp...

Page 12: ...NOTE CIRCULATOR CAN ALSO BE INSTALLED ON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 Figure 8 Syst...

Page 13: ...XPANSION TANK PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure 9 System Piping Arrangement Zonin...

Page 14: ...G PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATORS SYSTEM PIPING Figure 10 System P...

Page 15: ...uous flow NOTICE Do not use tankless coil if your water is excessively hard with lime or other deposits which will accumulate inside the coil When using tankless coil the Hydrolevel control is mounted...

Page 16: ...ent installations shall be in accordance with applicable provisions of NFPA 31 Standard for the installation of Oil Burning Equipment latest edition and applicable provisions of local building codes N...

Page 17: ...e boiler Install chimney connector start at boiler with vertical pipe elbow then install draft regulator horizontally When regulator is in place start at chimney and work back to the regulator Join th...

Page 18: ...THAN HIGHEST PART OF PASSAGE THROUGH ROOF MUST BE AT LEAST 2 FT HIGHER THAN ANY NEIGHBORING OBJECT WITHIN 10 FT MUS MUST HAVE AN UNOBSTRUCTED TOP OPENING TYPICAL CHIMNEY CONNECTION Figure 12 Typical...

Page 19: ...lations Connect 120 volt electrical supply to L1 and L2 terminals and two thermostat wires to T and T terminals on Hydrolevel limit control Run separate circuit from separate over current protection d...

Page 20: ...20 ELECTRICAL WIRING Figure 13 Hydrolevel 3250 Control with Beckett or Carlin Burner PN 240013012 Rev B 12 15 2020...

Page 21: ...21 Figure 14 Hydrolevel 3250 Control with Riello Burner ELECTRICAL WIRING PN 240013012 Rev B 12 15 2020...

Page 22: ...e runs air free close isolation valve or zone valve Repeat this procedure for remaining heating zones D Once all zones are filled with water and purged of air close power purging drain valve and fill...

Page 23: ...rner flame will be dark orange and formation of soot will occur in heating unit In buildings of conventional frame brick or stone construction that do not have utility rooms basement windows or stair...

Page 24: ...1HP 0 80 2 1 4 0 65 60 W 150 0 60 0 65 50 4EWC1 00 T EZ 1HP 1 00 2 1 4 0 85 60 B 150 0 85 1 00 60 4EWC1 25 T EZ 1HP 1 25 2 1 4 1 00 60 B 155 0 85 1 00 75 5EWC1 55 T EZ 1HP 1 55 2 1 4 1 25 60 B 155 1 1...

Page 25: ...trode Setting Figure 17 Riello Turbulator Setting Figure 18 Carlin Electrode Setting Turbulator Setting A Loosen NUT 1 turn SCREW 2 until INDEX MARKER 3 is aligned with correct index number per Burner...

Page 26: ...chamber is very hot Adjust Thermostat Heat Anticipator or Thermostat Cycle Rate According to Instructions Included With The Thermostat Check Thermostat Operation Follow instructions included with you...

Page 27: ...manually refill system Diaphragm Expansion Tank Tank may become water logged Frequent automatic opening of safety relief valve indicates water logging High boiler temperature accompanied by unusually...

Page 28: ...nd of flue brush off and inserting it into drill When brushing take care to not damage target wall with flue brush 6 Carefully vacuum soot accumulations from combustion chamber area take care to not d...

Page 29: ...ure head location and size if applicable are per manufacturer s recommendations If burner being used has damaged head replace head with same head recommended for use on this boiler 6 Inspect and clean...

Page 30: ...ectric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It may be in close...

Page 31: ...31 PUMP CURVES 15 10 5 0 5 4 3 2 1 m Head 1 2 3 4 5 US GPM 5 10 15 20 m h 3 Head feet Grundfos UP15 42F Pump Curve B G NRF22 Pump Curve PN 240013012 Rev B 12 15 2020...

Page 32: ...decreases This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED U...

Reviews: