13
VENT DAMPER INSTALLATION & INSTRUCTIONS
Figure 11 - Damper Motor Wiring
Figure 12 - Vent Damper Placement
Vent Damper
Vent Outlet
Damper Motor
DAMPER INSTALLATION
Follow Damper installation instructions provided with
damper. See Figure 11
.
1.
Verify only boiler is serviced by Vent Damper. Figure
12.
2.
Clearance of not less than 6 inches (152mm) between
Vent Damper and combustible material must be
maintained. Additional clearance should be allowed for
service of Vent Damper.
3.
Vent Damper must be in the open position when
appliance main burners are operating.
4.
Vent Damper position indicator must be in visible
location following installation.
5.
Thermostat's heat anticipator must be adjusted to
match total current draw of all controls associated with
boiler during heating cycle.