74
13 - TROUBLE SHOOTING
Troubleshooting Chart 2
Turn Off All Heat Calls
Inspect Burner through sight
glass. Is flame present?
NO
YES
Replace Flame
Sense
Adjust Gas Mixture See
Section 9. Re-check.
E-16 still present?
NO
YES
Replace Gas
Valve
Condition
Corrected
E16 - False Flame Signal
Initiate heat call. Check CO
2
at high fire is 9.1-9.5%
Out of Range
In Range
Replace Flame
Sense
PN 240011664, Rev. L [11/01/2020]