14.5 SAV Leakage test
14.6 Recommended maintenance intervals
Max. inlet pressure [bar]
Functional test
Maintenance
> 0.1 to 1
every 4 years
every 8 years
> 1 to 5
every 2 years
every 4 years
> 5
once a year
every 2 years
Go to section "12. Commissioning, decomissioning
and recommissioning for FRM-NOC or SAV" for per-
forming functional and leakage testing of SAV.
1. The maintenance intervals depend on the system-
specific operating and environmental conditions, gas
quality, state of the pipelines, etc.
2. The maintenance intervals have to be set by the sys
-
tem operator according to the system requirements.
3. It is recommended to perform a functional test on a
monthly base and carry out maintenance works every
year including a leakage testing, in order to guarantee
the system availability.
4. It is necessary to comply at least with the maintenance
intervals specified in G 495.