Adjusting the Set Point

•  Do NOT attempt to adjust the factory setting of the switch. 

Breaking the seal affects the switches ability to act as a 

differential switch.

Automatic Reset

• The NC contact of the AA...A1 breaks when pressure rises 

above the set point. It makes automatically when pressure 

falls below set point.

Annually check the switch for proper operation 

Set Point Calibration

1. Connect a meter capable of r/- 0.1 ohms to the NC 

and COM contacts.

2. Measure the resistance across the NC and COM contacts. 

If the resistance is more than 1.0 ohm, the switch switch 

should be replaced, since this indicates that the switch 

contacts are starting to either corrode or carbonizing.

Operation & Adjustment

Maintenance & Testing

3. Apply pressure to the + air pressure connection, and 

confirm that the NC contact breaks when pressure rises 

above the set point and that the NO contact makes. The 

NC contact will make automatically when pressure falls 

below the set point pressure.

4. Connect a meter capable or r/- 0.1 ohms to the NO 

and COM contacts.

5. Measure the resistance across the NO and COM contacts. 

If the resistance is more than 1.0 ohm, the switch switch 

should be replaced, since this indicates that the switch 

contacts are starting to either corrode or carbonizing.

Accessories & Replacement

Accessory for pressure switch

Order No.

Mounting plate (flat plastic)

230301

NEMA Type 1 Cover (1pcs)

230216

NEMA Type 1 Cover (77 pcs)

231432

NEMA Type 2 Cover (1pcs)

230280

NEMA Type 2 Cover (200 pcs)

250107

NEMA Type 12 cover with 1/2 NPT conduit connection

225816

Karl Dungs GmbH & Co. KG

P.O. Box 12 29

D-73602 Schorndorf, Germany

Phone  +49 (0)7181-804-0

Fax  +49 (0)7181-804-166

e-mail [email protected]

Internet http://www.dungs.com

Karl Dungs, Inc.

3890 Pheasant Ridge Drive NE

Suite 150

Blaine, MN 55449, U.S.A.

Phone 763 582-1700

Fax  763 582-1799

e-mail [email protected]

Internet http://www.dungs.com/usa/

We reserve the right to make modifications in the course of technical development.

Summary of Contents for AA-A1-0 Series

Page 1: ...essure switch perform a leak age and function test Please read the instruction be foreinstallingoroperating Keep theinstructioninasafeplace You find the instruction also at www dungs com If these instructions are not heeded the result may be personal injury or damage to property Theinstallationandmaintenance of this product must be done under the supervision of an ex periencedandtrainedspecialist ...

Page 2: ...essure switch operates without any auxiliary power Contact Rating 5 A resistive 3 A inductive 120 VAC 1 A 12 48 VDC Electrical Connection 1 4 x 1 32 6 3 x 0 8 mm flat male terminals Enclosure NEMA Type 1 NEMA Type 12 with appropriate cover Models Designations Ranges Type Version Description Order No Factory setting range in W C Switching hysteresis in W C AA A1 0 AA A1 0 2 AA A1 0 3 AA A1 0 4 No c...

Page 3: ... Connection p2 lower pressure Connection p1 higher pressure Application Connection Examples System vacuum monitor AA A1 is connected to the air duct with the p2 connection p1 is not con nected with the air duct Donotsealthep1 connection itmust be open to the atmosphere Filter monitoring To monitor a filter the AA A1 can be connected as shown above Blower monitoring For blower monitoring connect co...

Page 4: ...iring must comply with local electrical codes ordi nances and regulations Do not exceed the switch ratings given in the specifi cations and on the switch Standard installation position is vertical upright diaphragm When installed horizontally the pressure switch switches at a pressure higher by approx 0 2 in W C When installed upside down the pressure switch switches at a pressure lower by approx ...

Page 5: ...d that the NO contact makes The NC contact will make automatically when pressure falls below the set point pressure 4 Connect a meter capable or reading 0 1 ohms to the NO and COM contacts 5 Measure the resistance across the NO and COM contacts If the resistance is more than 1 0 ohm the switch switch should be replaced since this indicates that the switch contacts are starting to either corrode or...

Reviews: