Dungs AA-A1-0 Series Installation Instructions Download Page 3

3 … 5

MC • Karl Dungs

, Inc.

 • AA...A1 • Edition 2016.03 • P/N 261392

Operation

Setpoint tolerance

Upper switching

pressure

Falling

Rising

Adjustment as  pr

essur

e rises

Pressure

at meter

Switching h

yster

esis Δp

Lower switching

pressure

AA...A1 Mounting Procedure

•  Use suitable hoses for the medium.

•  Use a maximum 5/32” ID hose

•  Secure the hoses with a cable tie or 

a cable clip.

Pressure Connection

Definition of switching 

hysteresis ∆p

The  pressure  difference  between  the 

upper and lower switching pressures.

Connection p2 (–)  = lower pressure

Connection p1 (+)  = higher pressure

Application & Connection Examples

System vacuum monitor

AA...A1 is connected to the air duct with 

the p2 (-) connection. p1 (+) is not con-

nected with the air duct.

Do not seal the p1 (+) connection; it must 

be open to the atmosphere.

Filter monitoring

To monitor a filter, the AA...A1 can be 

connected as shown above.

Blower monitoring

For blower monitoring, connect con-

nection p1 (+) to the air duct on the 

downstream side of the blower and con-

nection p2 (-) to the air duct upstream 

of the blower.

Connection p1

must remain open

Connection p2 Connection p1

Connection p2 Connection p2

Connection p1

Prevent dirt from entering 

into the device through con-

nection p1(+)

Summary of Contents for AA-A1-0 Series

Page 1: ...essure switch perform a leak age and function test Please read the instruction be foreinstallingoroperating Keep theinstructioninasafeplace You find the instruction also at www dungs com If these instructions are not heeded the result may be personal injury or damage to property Theinstallationandmaintenance of this product must be done under the supervision of an ex periencedandtrainedspecialist ...

Page 2: ...essure switch operates without any auxiliary power Contact Rating 5 A resistive 3 A inductive 120 VAC 1 A 12 48 VDC Electrical Connection 1 4 x 1 32 6 3 x 0 8 mm flat male terminals Enclosure NEMA Type 1 NEMA Type 12 with appropriate cover Models Designations Ranges Type Version Description Order No Factory setting range in W C Switching hysteresis in W C AA A1 0 AA A1 0 2 AA A1 0 3 AA A1 0 4 No c...

Page 3: ... Connection p2 lower pressure Connection p1 higher pressure Application Connection Examples System vacuum monitor AA A1 is connected to the air duct with the p2 connection p1 is not con nected with the air duct Donotsealthep1 connection itmust be open to the atmosphere Filter monitoring To monitor a filter the AA A1 can be connected as shown above Blower monitoring For blower monitoring connect co...

Page 4: ...iring must comply with local electrical codes ordi nances and regulations Do not exceed the switch ratings given in the specifi cations and on the switch Standard installation position is vertical upright diaphragm When installed horizontally the pressure switch switches at a pressure higher by approx 0 2 in W C When installed upside down the pressure switch switches at a pressure lower by approx ...

Page 5: ...d that the NO contact makes The NC contact will make automatically when pressure falls below the set point pressure 4 Connect a meter capable or reading 0 1 ohms to the NO and COM contacts 5 Measure the resistance across the NO and COM contacts If the resistance is more than 1 0 ohm the switch switch should be replaced since this indicates that the switch contacts are starting to either corrode or...

Reviews: