![Duco DucoBox Silent Installation Manual Download Page 29](http://html1.mh-extra.com/html/duco/ducobox-silent/ducobox-silent_installation-manual_2537927029.webp)
28
29
ENGLISH
L0001779-L
18.09.2018 Installation manual for DucoBox Silent
06.G
Tips
• Removing all components from the network (e.g. in the event of problems): Activate ‘Installer mode’ and
long-press ‘INST’
until the LED starts flashing red� The DucoBox will reboot (around 15 seconds) and the LED will stop flashing�
• Restore factory settings for the DucoBox and all paired components (AS FROM DucoBox version
18xxxx)
: Long-press
‘INST’
and ‘ENTER’
if not in ‘Installer mode’� The network remains in place�
• Use the Duco Network Tool to read out information from components�
07
Configuring air volume
The system needs to be configured for it to work correctly� This will ensure its operation is as quiet as possible and energy-efficient�
See under the Tools heading at www�duco�eu for info about determining ventilation flow rates�
07.A
Configuration procedure for DucoBox Silent
The configuration procedure must be carried out on a calm day (no more than wind force 2: leaves rustling, feeling
the wind in one’s face)�
Configuring DucoBox Silent
1
Set all exhaust vents so they match the desired flow rate in accord-
ance with the table below� Proper pre-setting makes for rapid and
correct configuration�
Flow
rate
DucoVent
Design
DucoVent Basic
and other vents
75 m3/h
100% open
50 m3/h
50% open
25 m3/h
25% open
When using DucoVent Design exhaust vents, always leave the outer
ring in place for acoustic effect�
Example
Toilet
Kitchen
Bathroom
Storeroom
2
Before activating configuration mode:
• Close all windows and doors�
• Ensure that all duct openings in the DucoBox are fully closed and that the
DucoBox cover is closed!
• Avoid air leaks in ventilation ducts�
• Set all window ventilators to the open position
open