FUEL CONSUMPTION

NG

 L.P. VAPOR

1000 BTU/CU FT

2520 BTU/CUFT

MODEL     CF/HR BTU/HR

#/HR* GAL/HR CF/HR BTU/HR*

PSS15B2W 260

260,000

2.7

2.96

108

272,160

*Based on full load operation

L.P. TANK SIZING

Required L.P. Tank size for L.P. Vapor withdrawal

operating at various outside temperatures given in
degrees Fahrenheit (Celsius)

      TANK TEMPERATURE

MODEL

60 f(16 c) 32 f(0 c)

0 f(-18 c) -20 f(-29 c)

PSS15B2W 150 Gal.

250 Gal.

500 Gal. 1000 Gal.

ENGINE SPECIFICATIONS:

  Refer to engine operating and maintenance instructions.

** NOTICE **

Regarding Engines - This manual covers the generator
portion of these units.  See the separate engine instruc-
tion manual for engine-related problems, detailed engine
information and engine warranty.

**  CAUTION  **

Be sure to check the engine oil level frequently, as
specified in the engine manual.

The engine manufacturer has established an excellent

worldwide engine service organization; engine service is
available from a nearby authorized dealer or distributor;
check the yellow pages of the telephone directory under
“engines,” or ask the dealer from whom you purchased
the power plant.

The rated power of each engine-generator is limited by

the temperature, altitude and all other ambient conditions
specified by the engine manufacturer.  Engine power will
decrease 3-1/2% for each 1000 ft. above sea level, and
will decrease an additional 1% for each 10 degrees
Fahrenheit above 60 degrees Fahrenheit.

UNPACKING INSTRUCTIONS

** NOTICE **

When unpacking the generator set, be sure to inspect it
carefully for freight loss or damage.  If loss or damage is
noted at the time of delivery, require that the person
making the delivery make note of the loss or damage on
the freight bill, or affix his signature under the consignor’s
memo of the loss or damage.  Contact the carrier for
claim procedures.

When loss or damage is noted after delivery, segregate

the damaged material, and contact the carrier for claim
procedures. Be sure to retain the packaging material for
carrier inspection.

“Concealed Damage” is understood to mean damage to

the contents of a package which is not evident at the time
of delivery by the carrier, but which is discovered later.
The carrier or carriers are responsible for merchandise
lost or damaged in transit.  The title to goods rests with
the consignee when generators are shipped F.O.B.
factory, and only the consignee can legally file a claim.
Please note, most carriers have a time limit for filing
concealed damage claims.

****  CAUTION  ****

These units are shipped without oil.  Be sure to check oil
levels before operating.  See engine manufacturer’s
instruction manual for recommended oil requirements
before initial starting.

UNPACKING:

1.

Carefully remove the carton.

2.

After inspecting the engine-generator and transfer

switch for external physical damage, check for the
following items packed inside the carton.

a. Owner’s manual, wiring diagram and parts list.
b. Engine manufacturer’s instruction manual.

3.

Remove main frame hold down bolts, (4).

4.

Unit can now be lifted from shipping pallet.

INSTALLATION

General Information

  *************
*****  WARNING  ****
    *************

Before proceeding with the installation, be sure the
operation selector switch is in the stop position.

These engine/generator sets are designed to be

mounted on a concrete pad outdoors only.  The
transfer switch is mounted next to your electrical entrance
or distribution panel inside the building.  Consult a
qualified, licensed electrician or contractor  to install and
wire the transfer switch.  The installation must comply with
all national, state and local codes.

Before beginning the installation process recheck the

rating of the generator set and its transfer switch rating.
Be certain they can handle the intended load and are
compatible with the entrance voltage, phase and current
ratings.  Plans for installation should be prepared with
proper attention to mechanical and electrical engineering
detail to assure a satisfactory system installation.  The
information in this manual is offered only as a guide to
finalizing your installation plans.

Summary of Contents for WINCO PSS15B2W/A

Page 1: ...PACKAGED STANDBY SYSTEM PSS15B2W A INSTALLATION AND OPERATORS MANUAL Engine Generator Set...

Page 2: ...rication 6 Battery Installation 6 Connecting Battery Charger 6 TRANSFER SWITCH INSTALLATION 6 AC Electrical Connections 7 DC Electrical Connections 8 INITIAL START UP 8 TROUBLESHOOTING INFORMATION 9 W...

Page 3: ...ut of reach of children c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropri...

Page 4: ...UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR PSS15B2W A 100AMPS 60 AMPS UL Automatic Transfer Switch Sizes UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR PSS15B2W A 100 AMPS 100 AMPS 200 AMPS...

Page 5: ...rrier for claim procedures Be sure to retain the packaging material for carrier inspection Concealed Damage is understood to mean damage to the contents of a package which is not evident at the time o...

Page 6: ...stays clean WARNING FIRE HAZARD DO NOT OVERTIGHTEN THE FUEL LINE THIS IS A TAPERED FITTING OVERTIGHTENING WILL CAUSE THE FITTING TO CRACK AND LEAK FUEL For all vapor fuel systems the delivery pressure...

Page 7: ...n inches of water column The second is with a pressure gauge calibrated in ounces per square inch Reference numbers 1 through 3 in the block diagrams above are system parts supplied by customer Refere...

Page 8: ...battery terminal is connected to the negative cable ground from the engine generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure...

Page 9: ...ion panel should contain your only neutral to ground bond All power leads from the generator to the A T S must be sized to handle rated generator output amperage at a minimum the type of wire you use...

Page 10: ...anded wire should be used These wires will be labeled Bat and Start The control wires will be connected as follows in the generator control terminal box ATS Panel Generator Control Panel Start 1 to Wi...

Page 11: ...s you will have to fail the incoming line power to the A T S panel All the loads connected to the A T S should now be dead The engine generator set will go into a 3 to 10 second start delay At the end...

Page 12: ...be 3600 RPM 9 AC short on output leads PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and the Automatic Tra...

Page 13: ...PAGE 11 4190 00 60706 169 AC AND DC GENERATOR WIRING DIAGRAM...

Page 14: ...PAGE 12 60706 169 4190 00 AC AND DC GENERATOR SCHEMATIC...

Page 15: ...PAGE 13 4190 00 60706 169 GENERATOR LAYOUT...

Page 16: ...ility and fitness for a particular purpose are limited to 12 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation o...