DTI WINCO PSS15B2W/A Installation And Operator'S Manual Download Page 7

PAGE 5

4190-00

60706-169

    *************
*****  WARNING  ****
    *************
PERSONAL DANGER - Do not use galvanized pipe in
fuel line runs.  The galvanized coating can become
eroded and flake off, causing possible obstructions in the
regulator or fuel valve.  The results could range from
inoperative engine start to hazardous fuel leaks.

NATURAL GAS  or LP VAPOR

Size of pipe normally required for generators operating

on NATURAL GAS  or LP VAPOR

up to 25 feet*

25 - 100 feet* over 100 feet*

      use a two

PSS15B2W 3/4” pipe

1” pipe

 regulator system

*Allow an additional 3 feet for each standard elbow.  Do not use
‘street ells’ (restrictive)*

****  CAUTION  ****
Be careful when sealing gas joints.  Excessive sealing
compound can be drawn into the solenoid, regulator or
carburetor causing an engine malfunction.

FUEL PRESSURE

L.P. &  N.G. VAPOR FUEL

Correct fuel pressure cannot be stressed enough.  The

most common cause for inoperative systems is an
inadequate or incorrect fuel pressure.  Performance of the
engine is in direct relation to the correctness of the fuel
system.  Shown below is a  block diagram of a typical L.P.
or N.G.  vapor fuel installation.

Notice the following tables give two (2) different units of

measuring fuel pressure. The first and most accurate is
the use of a simple water manometer.  A manometer is
calibrated in inches of water column. The second is with a
pressure gauge calibrated in ounces per square inch.

Reference numbers 1 through 3 in the block diagrams

above are system parts supplied by customer.

Reference number 4 is the engine generator set.

Below is a table of the fuel pressure reading at each

reference in the system.

Fuel Pressure Table

Single Regulator (L.P. Vapor only)

       1

     3               4

UNIT OFF

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

Two (2) Regulator System (L.P. Vapor only)

       1

      2

       3

  4

UNIT OFF

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

Natural Gas

1

    3

    4

UNIT OFF

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

LP/NG FUEL CONVERSION

The PSS15B2W/A generator systems have been

tested on NATURAL GAS prior to shipment.  If you are
going to use them on LP vapor, follow the procedures
outlined below to change the fuel type.

1.  Connect  your LP supply to the unit, making sure
that you have the correct fuel pressure.

2.  Locate the vapor fuel adapter mounted between
the air filter and the carburetor body.

Summary of Contents for WINCO PSS15B2W/A

Page 1: ...PACKAGED STANDBY SYSTEM PSS15B2W A INSTALLATION AND OPERATORS MANUAL Engine Generator Set...

Page 2: ...rication 6 Battery Installation 6 Connecting Battery Charger 6 TRANSFER SWITCH INSTALLATION 6 AC Electrical Connections 7 DC Electrical Connections 8 INITIAL START UP 8 TROUBLESHOOTING INFORMATION 9 W...

Page 3: ...ut of reach of children c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropri...

Page 4: ...UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR PSS15B2W A 100AMPS 60 AMPS UL Automatic Transfer Switch Sizes UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR PSS15B2W A 100 AMPS 100 AMPS 200 AMPS...

Page 5: ...rrier for claim procedures Be sure to retain the packaging material for carrier inspection Concealed Damage is understood to mean damage to the contents of a package which is not evident at the time o...

Page 6: ...stays clean WARNING FIRE HAZARD DO NOT OVERTIGHTEN THE FUEL LINE THIS IS A TAPERED FITTING OVERTIGHTENING WILL CAUSE THE FITTING TO CRACK AND LEAK FUEL For all vapor fuel systems the delivery pressure...

Page 7: ...n inches of water column The second is with a pressure gauge calibrated in ounces per square inch Reference numbers 1 through 3 in the block diagrams above are system parts supplied by customer Refere...

Page 8: ...battery terminal is connected to the negative cable ground from the engine generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure...

Page 9: ...ion panel should contain your only neutral to ground bond All power leads from the generator to the A T S must be sized to handle rated generator output amperage at a minimum the type of wire you use...

Page 10: ...anded wire should be used These wires will be labeled Bat and Start The control wires will be connected as follows in the generator control terminal box ATS Panel Generator Control Panel Start 1 to Wi...

Page 11: ...s you will have to fail the incoming line power to the A T S panel All the loads connected to the A T S should now be dead The engine generator set will go into a 3 to 10 second start delay At the end...

Page 12: ...be 3600 RPM 9 AC short on output leads PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and the Automatic Tra...

Page 13: ...PAGE 11 4190 00 60706 169 AC AND DC GENERATOR WIRING DIAGRAM...

Page 14: ...PAGE 12 60706 169 4190 00 AC AND DC GENERATOR SCHEMATIC...

Page 15: ...PAGE 13 4190 00 60706 169 GENERATOR LAYOUT...

Page 16: ...ility and fitness for a particular purpose are limited to 12 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation o...

Reviews: