DSE7110 & DSE7120 Operator Manual
14
4.1.4
CAN
PIN No
DESCRIPTION
CABLE
SIZE
NOTES
25
CAN port H
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
26
CAN port L
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
27
CAN port Common
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
NOTE:- Screened 120
Ω
Ω
Ω
Ω
impedance cable specified for use with CAN must be used for the CAN link and
the Multiset comms link.
DSE stock and supply Belden cable 9841 which is a high quality 120
Ω
Ω
Ω
Ω
impedance cable suitable for CAN
use (DSE part number 016-030)
NOTE:- Terminals 28 to 38 are not fitted to the DSE7100 series controllers.
4.1.5
GENERATOR / MAINS LOAD SWITCHING
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
39
Output relay C
1.0mm
AWG 18
Normally configured to control load switching device
(Recommend 10A fuse)
40
Output relay C
1.0mm
AWG 18
Normally configured to control load switching device
41
Output relay D
1.0mm
AWG 18
Normally configured to control load switching device
(Recommend 10A fuse)
42
Output relay D
1.0mm
AWG 18
Normally configured to control load switching device
4.1.6
GENERATOR / MAINS VOLTAGE SENSING
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
43
Generator L1 (U) voltage
monitoring
1.0mm²
AWG 18
Connect to generator L1 (U) output (AC)
(Recommend 2A fuse)
44
Generator L2 (V) voltage
monitoring
1.0mm²
AWG 18
Connect to generator L2 (V) output (AC)
(Recommend 2A fuse)
45
Generator L3 (W) voltage
monitoring
1.0mm²
AWG 18
Connect to generator L3 (W) output (AC)
(Recommend 2A fuse)
46
Generator Neutral (N) input
1.0mm²
AWG 18
Connect to generator Neutral terminal (AC)
47
Mains L1 (R) voltage monitoring
1.0mm²
AWG 18
Connect to Mains L1 (R) output (AC)
(Recommend 2A fuse)
48
Mains L2 (S) voltage monitoring
1.0mm²
AWG 18
Connect to Mains L2 (S) output (AC)
(Recommend 2A fuse)
49
Mains L3 (T) voltage monitoring
1.0mm²
AWG 18
Connect to Mains L3 (T) output (AC)
(Recommend 2A fuse)
50
Mains Neutral (N) input
1.0mm²
AWG 18
Connect to Mains Neutral terminal (AC)
NOTE:- Terminals 47-50 are not fitted to the DSE7110.