4 TERMINAL DESCRIPTION
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
1
DC Plant Supply Input
(-ve)
1.0mm
Connected to plant battery negative
2
DC Plant Supply Input
(+ve)
1.0mm
Connected to plant battery positive
(Recommended Fuse 2A)
3
Fuel relay Output
1.0mm
Used to operate the fuel relay.
4
Start relay Output
1.0mm
Used to operate the cranking relay.
5
Auxiliary Output relay 1
1.0mm
Configurable output.
6
Auxiliary Output relay 2
1.0mm
Configurable output.
7
Charge Fail Input/ Excitation
Output
1.0mm
Must NOT be connected to plant supply
negative if not used.
8
Low Oil Pressure Input
0.5mm
Switch to negative.
9
High Engine Temp Input
0.5mm
Switch to negative.
10
Auxiliary Input 1
0.5mm
Switch to negative.
11
Auxiliary Input 2
0.5mm
Switch to negative.
12
Remote Start Input
0.5mm
Switch to negative.
13
Mains loading Relay
Normally Open contact
1.0mm
Used to close the mains
contactor / breaker
14
Generator loading Relay
Normally Open contact
1.0mm
Used to close the generator
contactor / breaker
15
Functional Earth
1.0mm
Connect to a good clean earth point
16
Mains L1
Voltage Monitoring Input
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
17
Mains L2
Voltage Monitoring Input
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
18
Mains L3
Voltage Monitoring Input
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
19
Mains N
Voltage Monitoring Input
1.0mm
Connect to Mains N supply (AC)
20
Alternator Input L1
1.0mm
Do not connect if not used. (2A Fuse)
21
Alternator Input N
1.0mm
Do not connect if not used.
NOTE:-
For single phase mains monitoring the neutral should be connected to terminal
19, L1 should be connected to terminals 16,17 and 18.
NOTE:-
For two phase mains monitoring the L2 should be connected to terminal 19, L1
should be connected to terminals 16,17 and 18. The voltage between the two phases must
not exceed 305 Volts.
NOTE:- All the outputs are solid state, rated at 1.2 Amps 8 Volts to 35 Volts DC, and
switch to battery negative when active.