background image

26

LOCKOUT AND RESET SECTIONS

[90] Installer Lockout Enable

When this feature is enabled, performing a hardware or software reset to restore the system’s factory
programming will not reset the Installer’s Code or the Downloading Access Code.

To enable this feature, enter Section [90].  After entering Section [90], enter [Installer’s Code][90] to confirm
activation of this feature.  If the Installer’s Code and the Section number are not entered correctly, the keypad will
sound a single long tone to indicate the error and the feature will not be enabled.

A panel that has this feature enabled will provide an audible indication upon power-up by clicking the telephone
line relay 10 times.  Ensure that the new Installer’s Code has been entered correctly before enabling this feature
as there is no way of re-entering the Programming Mode without the new Installer’s Code.

[91] Installer Lockout Disable

Entering Section [91] while in the installer’s Programming Mode will disable the Installer Lockout feature
described in Section [90].

To enable this feature, enter Section [91].  After entering Section [91], enter [Installer’s Code][91] to confirm
activation of this feature.  If the Installer’s Code and the Section number are not entered correctly, the keypad will
sound a single long tone to indicate the error and the feature will not be enabled.

NOTE:

 Panels returned to DSC with the Installer Lockout feature enabled and no other apparent problems will be

subject to an additional service charge.

[99] Factory Default

Enter this section to reset the system’s programming to the factory default settings.

To enable this feature, enter Section [99].  After entering Section [99], enter [Installer’s Code][99] to confirm
activation of this feature.  If the Installer’s Code and the Section number are not entered correctly, the keypad will
sound a single long tone to indicate the error and the feature will not be enabled.

Hardware Reset of System Programming

If the Installer’s Code is lost or forgotten, the system’s memory must be restored to the factory default settings
before programming may be performed.  Note that if the Installer Lockout feature has been enabled, the
Hardware Reset will not restore the default Installer’s Code.

To restore the factory default programming:

1

Remove power from the system by disconnecting the AC and battery

2

Remove any connections to the Zone 1 and PGM terminals

3

Connect the Zone 1 and PGM terminals together

4

With the Zone 1 and PGM terminals connected, apply AC power to the system

5

Wait for 20 seconds after applying power and then remove the connection between the Zone 1 and PGM terminals

6

The system’s factory default programming has now been restored.  Note that if the Installer’s Lockout feature had
been enabled, the Installer’s Code and the Downloading Access Code will not be reset to the default settings.

Summary of Contents for PC2525

Page 1: ...INSTALLATION MANUAL PC2525 Version 1 1 ...

Page 2: ......

Page 3: ...ng 1 6 Trouble Conditions 2 7 Alarm Memory 3 7 Door Chime ON OFF Command 4 7 User Programming Commands 5 Master Code 8 User Function Commands 6 Master Code 8 Setting the Clock 6 Master Code 1 9 Set Auto Arm Time 6 Master Code 2 9 Quick Arm ON OFF 6 Master Code 4 9 Auto Arm ON OFF 6 Master Code 5 9 System Test 6 Master Code 8 9 User Call up 6 Master Code 9 9 Installer s Test ON OFF 6 Master Code 0 ...

Page 4: ...e Restoral Reporting Codes 20 41 LINKS1000 Maintenance Reporting Codes 20 42 Communication Variables 21 43 Test Transmission Time of Day 21 44 Communicator Format Options 21 45 Communicator Call Direction 22 46 First Communicator Option Code 23 47 LINKS1000 Preamble First Telephone Number 24 48 LINKS1000 Preamble Second Telephone Number 24 DOWNLOADING PROGRAMMING SECTIONS 25 70 First Downloading O...

Page 5: ...Programmable auto downloading Swinger shutdown Transmission delay 8 Access Codes Master Code All zones programmable as fire zones Programmable test transmission Zone bypass from the keypad Eight zones Bell Siren zone Programmable output Three dedicated keys Fire Auxiliary Panic Backlit aesthetically pleasing keypad SPECIFICATIONS PC2525 Control Panel Eight fully programmable zones EOL resistor sup...

Page 6: ...llel Do not connect multiple keypads on the same wire run For stand by loading purposes assume a current draw of 35 mA per keypad This estimate represents the panel in the disarmed state with two open zones AC Power Wiring Complete all wiring to the control panel before connecting AC power or the battery Do not plug the transformer into an outlet that is controlled by a switch Battery Connection O...

Page 7: ...or so that if power to the detectors fails a fire zone trouble will be initiated Refer to the Hook Up Diagram for instructions on using 2 wire smoke detectors page 33 If 2 wire smoke detectors are used the Programmable Output Option in Section 06 must be programed as 00 The 2 wire smoke detector circuit will operated in the same manner as a Type 8 Delayed Fire zone refer to Section 01 Zone Definit...

Page 8: ...ns It is recommended that additional smoke detectors beyond those required be installed for increased protection The added areas include basement bedrooms dining rooms furnace room utility room and hallways not protected by the required detectors GUIDELINES FOR LOCATING SMOKE DETECTORS Figure 1 A smoke detector should be located between the sleeping area and the rest of the family unit Figure 2 In...

Page 9: ...ssed intentionally 1 command If the Ready light is not on one or more zones are open The system can only be armed when the Ready light is ON To arm enter a 4 digit Access Code As each digit is entered the keypad sounder will beep When the correct Access Code has been entered the Armed light will come ON and the keypad will beep 6 times If the Access Code has been entered incorrectly the keypad wil...

Page 10: ...on for enabling and disabling the Quick Arm feature Zone Bypassing 1 A bypassed zone will not cause an alarm Use zone bypassing when access is needed to part of a protected area or if damage to contacts or wiring cannot be repaired immediately The panel can be armed with one or more zones bypassed even if the zone s are open The Ready light will be ON and the Bypass light will be ON if a zone is b...

Page 11: ...ll initiate a trouble 8 Loss of Time on System Clock When the PC2525 is powered up or reset the internal time of day clock needs to be reset to the correct time The trouble is cleared after entering the trouble view mode then pressing to exit The trouble will also be cleared on any attempt to set the time of day Refer to 6 User Function Commands for information on setting the clock Press to return...

Page 12: ... will simply replace the old one If you wish to program another code press the number key for the code to be programmed and enter the new 4 digit code Press the key to exit this section Erasing a Code To erase a code enter 5 Master Code Press the key of the code you wish to erase The Zone Light for that code number will flash Enter NOTE The Master Code cannot be erased If the Master Code is forgot...

Page 13: ...ng period the warning will be silenced and Auto Arming will be cancelled Auto Arming will be attempted at the same time the next day Quick Arm ON OFF 6 Master Code 4 Pressing 4 while in the User Function Command mode will Enable 3 beeps or Disable one long beep the Quick Arm feature With this feature enabled the panel can be armed by simply entering 0 Auto Arm ON OFF 6 Master Code 5 Pressing 5 whi...

Page 14: ...ller by entering the Alarm and Restoral Codes in Programming Section 38 F ire Key Pressing the F key and holding it for 2 seconds will initiate a local pulsing alarm and if programmed will transmit the alarm to the monitoring station A Fire alarm may also be generated by pressing the 1 and 3 keys together and holding them down for 2 seconds The keypad will sound a series of short beeps once the pa...

Page 15: ...it in the next number When all required data for a section is entered the keypad will beep several times and the Armed light will come ON Enter the number of the next Section to be programmed It is not necessary to program all 2 or 3 digit numbers in any given section A section can be entered and programmed by going only to the digit or digits to be changed and then pressing to return to the Progr...

Page 16: ...n exit delay and an entry delay provided that a Delay zone has been tripped first If the protected area is entered without coming through the normal Delay entrance and an Interior zone is tripped an immediate alarm will be generated 3 Interior Home Away If the system is armed and the Delay Zone is NOT tripped during the exit delay time the type 3 zone will be bypassed 4 24 Hour Bell is active at a...

Page 17: ...ay an indication when this type of zone is activated 02 System Times Six system times are programmed in this section each entry requires a 3 digit number Do not press the key during data entry 1 Entry Delay Time 001 to 255 seconds This value determines the standard entry delay time The factory default entry time is 30 seconds 2 Exit Delay Time 001 to 255 seconds This value determines the standard ...

Page 18: ...the keypad buzzer is active The PGM output will also be activated for the duration of the Exit Delay if an Audible Exit Delay is selected in Section 11 Zone Light 5 06 Courtesy Pulse Follow Entry and Exit Delays This option provides an output which follows the entry and exit times It can be used to turn on a courtesy light near the exit door for the duration of the entry exit times 07 Entry Delay ...

Page 19: ...t open When the system is armed the Auxiliary Delay Zones will be bypassed When the zones are secured they will be added to the system and will be armed Once armed activity on an Auxiliary Delay Zone will initiate the Auxiliary Entry Delay OFF No Force Arming If an Auxiliary Delay Zone is left open when the system is armed the Auxiliary Entry Delay will begin as soon as the Exit Delay expires If t...

Page 20: ...tivate Utility Output After entering the 7 Utility Output Command an Access Code must be entered before the Utility Output will be activated OFF Access Code Not Required to Activate Utility Output Enter the 7 Utility Output Command to activate the Utility Output Zone Light 6 Alarm Display Options ON Alarms Displayed while Armed Alarm conditions will be displayed on system keypads whether the syste...

Page 21: ...vated for zones that have exceeded the limit of alarms set in the Swinger Shutdown counter OFF Bell Shutdown Disabled The BELL output will be activated for all alarms on all zones even after the Swinger Shutdown counter has been exceeded The BELL output will continue to be activated for all alarms even though the alarms will not be reported once the Swinger Shutdown counter has been exceeded Zone ...

Page 22: ... Urgency Applied to Entry Delay The Keypad will sound a steady tone during the Entry Delay During the last 10 seconds of the Entry Delay the keypad will sound a pulsing tone to warn that the Entry Delay is about to expire OFF Standard Entry Delay The Keypad will sound a steady tone throughout the Entry Delay time Zone Light 7 Telephone Line Monitor Disabled Enabled ON Telephone Line Monitor Disabl...

Page 23: ... second account code is always transmitted to the Second telephone number Refer to Section 31 for programming instructions 34 Alarm Reporting Codes Zones 1 8 Enter 8 2 digit numbers for the Alarm Reporting Codes for zones 1 to 8 These codes are used by the communicator to report alarms on zones 1 to 8 Listed below are several programming examples and the resulting transmission using different form...

Page 24: ...ed If the After Alarm Code is programmed that code will be transmitted to the monitoring station on opening if an alarm occurred during previous armed period This feature is useful for installations where openings and closings are not reported normally but it is desired to have a report to the monitoring station on opening if an alarm did occur during the previous armed period This feature allows ...

Page 25: ... the list below Valid entries are from 00 to 11 do not enter any other values The selection for each phone number is determined by the type of receiver being called Enter the format number for the First telephone number first It is necessary to program both telephone format numbers even if the first phone number is the only one being used 00 Silent Knight Ademco Slow 10 BPS 1400 Hz handshake 01 Se...

Page 26: ...osing Section 36 C1 Low Battery Section 39 E1 Battery Restorals Section 40 E1 AC Failure Section 39 E1 AC Restoral Section 40 E1 Bell Trouble Section 39 F1 Bell Restoral Section 40 F1 Troubles Sections 39 40 AA Misc Alarms Section 38 A1 to 99 Test Code Section 39 1C or DC System Test Code Section 39 CC After Alarm Code Section 37 B1 Auto Arm Cancel Code Section 36 C8 TLM Restoral Code Section 40 E...

Page 27: ...ight attempts to communicate to the First Telephone Number fail up to eight attempts will be made to communicate to the Second Telephone Number If all eight attempts to communicate to the Second Telephone Number fail a Failure to Communicate Trouble will be generated Zone Light 5 Partial Closing Identification Options ON Partial Closings Identified The alarm codes for all manually bypassed zones w...

Page 28: ...Escort Voice Assisted Security Control module is being used Closing Confirmation must only be used if the system is programmed to report openings and closings OFF Closing Confirmation Disabled The Exit Delay time will commence once an Access Code is entered to arm the system Factory default setting 47 LINKS1000 Preamble First Telephone Number LINKS1000 Preamble Codes are 4 digit codes used with lo...

Page 29: ...Enabled The system will automatically place a call to the downloading computer at the time programmed in the System Clock Times and at the interval in days programmed in the System Times A downloading telephone number must be programmed in the Downloading Computer Telephone Number section OFF Periodic Downloading Disabled The system will not perform automatic downloading functions Zone Lights 6 8 ...

Page 30: ...t be enabled NOTE Panels returned to DSC with the Installer Lockout feature enabled and no other apparent problems will be subject to an additional service charge 99 Factory Default Enter this section to reset the system s programming to the factory default settings To enable this feature enter Section 99 After entering Section 99 enter Installer s Code 99 to confirm activation of this feature If ...

Page 31: ..._______________ Entry Time ________________________________________ Exit Time _________________________________ Bell Cutoff ________________________________________ KEYPAD ZONES F Key ON OFF Quick Arm ON OFF A Key ON OFF Quick Exit ON OFF P Key ON OFF Installers Lockout ON OFF Installer s Name ______________________________________________ NOTES ____________________________________________________...

Page 32: ... entries are 001 to 255 Do not enter 000 NOTE Auxiliary Delay Times must be longer than Standard Delay times Loop Response Times must be in the range of 010 to 255 do not program times less than 010 I _ _ _ _ _ _ I _ _ _ _ _ _ I I _ _ _ _ _ _ _ I _ _ _ _ _ _ _ I I _ _ _ _ _ _ I _ _ _ _ _ _ I I _ _ _ _ _ _ _ I _ _ _ _ _ _ _ I I _ _ _ _ _ _ I _ _ _ _ _ _ I I _ _ _ _ _ _ _ I _ _ _ _ _ _ _ I I _ _ _ _...

Page 33: ...Bell Squawk disabled ON Zone Light 7 No bell during Auto Arm Bell during Auto Arm OFF Zone Light 8 Exit Delay Termination Enabled Exit Delay Termination Disabled 11 Fourth System Option Code Page 18 Default Zone Light ON Zone Light OFF OFF Zone Light 1 Bell pulses always Bell pulses on Fire Alarm only OFF Zone Light 2 Bell Squawk on Exit Delay No Bell Squawk OFF Zone Light 3 Bell Squawk on Entry D...

Page 34: ...I Zone 8 Alarm PC2525 v1 1 NOTE If a Zone Light is ON that zone may be bypassed using the 1 command NOTE If a Zone Light is ON that Access Code may be used to bypass zones If an Access Code is not required to bypass zones programming in this Section will not affect system operation NOTE For single digit reporting codes enter 0 as the second digit Enter 1 hexadecimal A to transmit a 0 zero I _ _ _ ...

Page 35: ...I Access Code 8 I______I______I Partial Closing Code I______I______I Auto Arm Cancellation Code 37 Opening Disarming Reporting Codes for Access Codes 1 8 Page 20 I______I______I Access Code 1 I______I______I Access Code 2 I______I______I Access Code 3 I______I______I Access Code 4 I______I______I Access Code 5 I______I______I Access Code 6 I______I______I Access Code 7 I______I______I Access Code ...

Page 36: ...to 11 do not enter any other values Default 0 1 First Telephone Number 0 1 Second Telephone Number 00 Silent Knight Ademco Slow 10 BPS 1400 Hz handshake 01 Sescoa Franklin DCI Vertex 20 BPS 2300 Hz handshake 02 Silent Knight Fast 20 BPS 1400 Hz handshake 03 Radionics 40 BPS 2300 1400 Hz handshake 04 Radionics 40 BPS 2300 1400Hz handshake with parity 05 Sescoa Super Speed 06 Silent Knight Ademco Sl...

Page 37: ...FF Zone Light 6 For Future Use OFF Zone Light 7 For Future Use OFF Zone Light 8 For Future Use 71 Downloading Computer s Telephone Number Page 25 Enter 0 for the digit 0 zero in the telephone number Be sure to enter to complete the entry of the telephone number 72 Downloading Access Code Page 25 Default 2 5 2 5 Enter 4 digits using 0 through 9 do not enter or 73 Panel Identification Code Page 25 D...

Page 38: ... Number Page 25 I______I______I______I______I Program all unused digits with hexadecimal F 90 Installer Lockout Enable Page 26 Enter 90 Installer s Code 90 91 Installer Lockout Disable Page 26 Enter 91 Installer s Code 91 99 Factory Default Page 26 Enter 99 Installer s Code 99 I _ _ _ _ _ _ I _ _ _ _ _ _ I I _ _ _ _ _ _ _ I _ _ _ _ _ _ _ I I _ _ _ _ _ _ I _ _ _ _ _ _ I_ _ _ _ _ _ I I _ _ _ _ _ _ _...

Page 39: ...ntifier PFA1 Type Zone Standard Loop Style Class B Style B Maximum Line Resistance 100Ω total End of Line Device EOLR 1 1000Ω 0 5W Maximum Detectors 20 Compatible Detector Models Falcon Detection Technologies Model 525 and 525T HOOK UP DIAGRAM ...

Page 40: ...her warranties whether expressed or implied and of all other obligations or liabilities on the part of Digital Security Controls Ltd This warranty contains the entire warranty Digital Security Controls Ltd neither assumes nor authorizes any other person purporting to act on its behalf to modify or to change this warranty nor to assume for it any other warranty or liability concerning this product ...

Page 41: ...37 ...

Page 42: ... 1995 Digital Security Controls Ltd 1645 Flint Road Downsview Ontario Canada M3J 2J6 Printed in Canada 29001634 R0 ...

Reviews: