DSC PC1510 Installation Manual Download Page 35

WARNING 

Please Read Carefully

N o t e   t o   I n s t a l l e r s

This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users
of this system.

S y s t e m   Fa i l u r e s

This system has been carefully designed to be as effective as possible. There are circumstances, however, involving f ire, burglary, or other types of emergencies where it may not
provide protection. Any alarm system of any type may be compromised deliberately or may fail to operate as expected for a variety of reasons. Some but not all of these reasons may
be:

  I n a d e q u a t e   I n s t a l l a t i o n

A security system must be installed properly in order to provide adequate protection. Every installation should be evaluated by a security professional to ensure that all access points and areas
are covered. Locks and latches on windows and doors must be secure and operate as intended. Windows, doors, walls, ceilings and other building materials must be of sufficient strength and
construction to provide the level of protection expected. A reevaluation must be done during and after any construction activity. An evaluation by the fire and/or police department is highly
recommended if this service is available.

  C r i m i n a l   K n o w l e d g e

This system contains security features which were known to be effective at the time of manufacture. It is possible for persons with criminal intent to develop techniques which reduce the
effectiveness of these features. It is important that a security system be reviewed periodically to ensure that its features remain effective and that it be updated or replaced if it is found that it
does not provide the protection expected.

  A c c e s s   b y   I n t r u d e r s

Intruders may enter through an unprotected access point, circumvent a sensing device, evade detection by moving through an area of insufficient coverage, disconnect a warning
device, or interfere with or prevent the proper operation of the system.

  P o w e r   Fa i l u r e

Control units, intrusion detectors, smoke detectors and many other security devices require an adequate power supply for proper operation. If a device operates from batteries, it is possible for
the batteries to fail. Even if the batteries have not failed, they must be charged, in good condition and installed correctly. If a device operates only by AC power, any interruption, however brief, will
render that device inoperative while it does not have power. Power interruptions of any length are often accompanied by voltage fluctuations which may damage electronic equipment such as a
security system. After a power interruption has occurred, immediately conduct a complete system test to ensure that the system operates as intended.

  F a i l u r e   o f   R e p l a c e a b l e   B a t t e r i e s

This system’s wireless transmitters have been designed to provide several years of battery life under normal conditions. The expected battery life is a function of the device environment, usage
and type. Ambient conditions such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the expected battery life. While each transmitting device has a low
battery monitor which identifies when the batteries need to be replaced, this monitor may fail to operate as expected. Regular testing and maintenance will keep the system in good operating
condition.

  C o m p r o m i s e   o f   R a d i o   F r e q u e n c y   ( W i r e l e s s )   D e v i c e s

Signals may not reach the receiver under all circumstances which could include metal objects placed on or near the radio path or deliberate jamming or other inadvertent radio signal
interference.

  S y s t e m   U s e r s

A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary physical disability, inability to reach the device in time, or unfamiliarity with
the correct operation. It is important that all system users be trained in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm.

  S m o ke   D e t e c t o r s

Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of reasons, some of which follow. The smoke detectors may have been improperly
installed or positioned. Smoke may not be able to reach the smoke detectors, such as when the fire is in a chimney, walls or roofs, or on the other side of closed doors. Smoke detectors may
not detect smoke from fires on another level of the residence or building.
Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot sense all types of fires equally well. Smoke detectors may not provide timely
warning of fires caused by carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits,
children playing with matches or arson.
Even if the smoke detector operates as intended, there may be circumstances when there is insufficient warning to allow all occupants to escape in time to avoid injury or death.

  M o t i o n   D e t e c t o r s

Motion detectors can only detect motion within the designated areas as shown in their respective installation instructions. They cannot discriminate between intruders and intended
occupants. Motion detectors do not provide volumetric area protection. They have multiple beams of detection and motion can only be detected in unobstructed areas covered by these
beams. They cannot detect motion which occurs behind walls, ceilings, floor, closed doors, glass partitions, glass doors or windows. Any type of tampering whether intentional or
unintentional such as masking, painting, or spraying of any material on the lenses, mirrors, windows or any other part of the detection system will impair its proper operation.
Passive infrared motion detectors operate by sensing changes in temperature. However their effectiveness can be reduced when the ambient temperature rises near or above body
temperature or if there are intentional or unintentional sources of heat in or near the detection area. Some of these heat sources could be heaters, radiators, stoves, barbeques,
fireplaces, sunlight, steam vents, lighting and so on.

  Wa r n i n g   D e v i c e s

Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if there is an intervening wall or door. If warning devices are located on a different level of the residence
or premise, then it is less likely that the occupants will be alerted or awakened. Audible warning devices may be interfered with by other noise sources such as stereos, radios, televisions, air conditioners or
other appliances, or passing traffic. Audible warning devices, however loud, may not be heard by a hearing-impaired person.

  Te l e p h o n e   L i n e s

If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time. Also an intruder may cut the telephone line or defeat its operation by more
sophisticated means which may be difficult to detect.

  I n s u f f i c i e n t   Ti m e

There may be circumstances when the system will operate as intended, yet the occupants will not be protected from the emergency due to their inability to respond to the warnings in a
timely manner. If the system is monitored, the response may not occur in time to protect the occupants or their belongings.

  C o m p o n e n t   F a i l u r e

Although every effort has been made to make this system as reliable as possible, the system may fail to function as intended due to the failure of a component.

  I n a d e q u a t e   Te s t i n g

Most problems that would prevent an alarm system from operating as intended can be found by regular testing and maintenance. The complete system should be tested weekly and
immediately after a break-in, an attempted break-in, a fire, a storm, an earthquake, an accident, or any kind of construction activity inside or outside the premises. The testing should
include all sensing devices, keypads, consoles, alarm indicating devices and any other operational devices that are part of the system.

  S e c u r i t y   a n d   I n s u r a n c e

Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm system also is not a substitute for property owners, renters, or other occupants to
act prudently to prevent or minimize the harmful effects of an emergency situation.

Summary of Contents for PC1510

Page 1: ...N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read Software Version 4 1 DLS 1 V6 5 and up ...

Page 2: ...his unit is 2 AVIS L étiquette de l Industrie Canada identifie le matériel homologué Cette étiquette certifie que le matériel est conforme à certaines normes de protection d exploitation et de sécurité des réseaux de télécommunications Industrie Canada n assure toutefois pas que le matériel fonctionnera à la satisfaction de l utilisateur Avant d installer ce matériel l utilisateur doit s assurer q...

Page 3: ...ditions 7 Alarm Memory 7 Downloading Callup Command 7 User Programming Commands 7 EEPROM Reset 8 User Function Commands 8 Setting the Clock 6 Master Code 1 8 Set Auto Arm Time 6 Master Code 2 8 Quick Arm ON OFF 6 Master Code 4 8 Auto Arm ON OFF 6 Master Code 5 8 Door Chime ON OFF 6 Master Code 6 8 Bell Test 6 Master Code 8 9 Installer s Test ON OFF 6 Master Code 0 9 Utility Output Command 7 or 7 A...

Page 4: ... Option Code 14 14 3rd System Option Code 14 15 Communication Variables 14 16 Zone Bypass Mask 14 17 System Times 14 18 Auxiliary Delay Loop Entry Exit Times 15 19 System Clock Times 15 20 New Installer s Code 15 21 New Master Code 15 22 2nd Master Code 15 23 Communication Formats 15 24 Programmable Output Options PGM Terminal 16 25 Communicator Call Directions 17 26 Downloading Telephone Number 1...

Page 5: ...delay Six access codes Master key code All zones programmable as fire zones Temporal fire bell pattern Programmable test transmission Zone bypass from the keypad Six zones Bell Siren zone Programmable output Four programmable options Three dedicated keys Fire Emergency Panic Backlit aesthetically pleasing keypad PC1510 Control Panel Six fully programmable zones EOL resistor 30 EOL supervised optio...

Page 6: ...all wiring to the control panel before applying AC power or connecting the battery Mounting the Keypad Keypads should be located close to the designated Entry Exit door s and mounted at a height convenient for all users NOTE Complete all wiring to the control panel before applying AC power or connecting the battery Auxiliary Power Connection The auxiliary power supply can be used to power keypads ...

Page 7: ...hart Z1 COM Z2 NC NO NC NC 5600Ω 0 5W END OF LINE RESISTOR 5600Ω 0 5W END OF LINE RESISTOR EOL RESISTOR LOOPS USING NO NC DEVICES EOL RESISTOR LOOPS USING NC DEVICES ONLY Zone Wiring Chart Figures based on maximum loop resistance of 100 ohms Wire Gauge Max Run Length to AWG End of Lineresistor 24 1900 579m 22 3000 914m 20 4900 1493m 19 6200 1889m 18 7800 2377m Thewiringtablegivesthewirerunlengthfr...

Page 8: ...from the alarm panel communicator RED BATTERY CHARGE CURRENT IS 360 mA MAX 12 VOLT 4 Ah GEL CELL BATTERY CAPACITY FOR EMERGENCY STANDBY IS AT LEAST 4 HOURS IF THE TOTAL LOAD BELL AUX OUTPUTS IS 800 mA OR LESS BLK Battery Connection If the battery is reverse connected the 5 A fuse will blow The battery charging voltage is factory set and normally needs no adjustment Ifthebatterychargingvoltageisout...

Page 9: ...iving unit living unit Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke from a fire generally rises to the ceiling spreads out from a fire generally rises to the ceiling spreads out from a fire generally ...

Page 10: ...ed when the panel is disarmed KEYPAD FUNCTIONS Introduction The PC1500RK remote keypad provides complete information and control of the PC1510 control panel The panel can be fully programmed from the keypad The 6 zone lights provide alarm and status indication for the alarm circuits Each zone can be programmed to be a burglary zone or a fire zone The five function lights guide the user in operatin...

Page 11: ...it from the trouble view mode 5 Fire Alarm Circuit Trouble An open circuit on the zone programmed as a fire loop will initiate a trouble See Zone Definitions section 11 for fire loop zone assignment 6 Loss of Time on System Clock When the PC1510 is powered up or reset the internal time of day clock needs to be reset to the correct time The trouble is cleared after entering the trouble view mode th...

Page 12: ...fter use This function will turn off automatically on arming Items 4 5 6 and 0 turn ON and OFF various features When the item key is pressed and the feature is being turned ON the keypad sounder will beep 3 times If the feature is being turned OFF the sounder will give one long beep Pressing item 8 gives a 2 second Bell Siren and Keypad Light and Buzzer test Setting the Clock 6 Master Code 1 The S...

Page 13: ...passed Note that the 1 command will not remove bypasses from zones that have been manually bypassed Quick Exit Command 0 when Armed Entering 0 when the system is armed will allow the user to exit the premises through any delay zone without altering the status of the system if the Quick Exit feature is enabled The Quick Exit feature can be enabled by turning on option 4 in programmingsection 32 For...

Page 14: ...ter 2 digits for the section you wish to program The sections for the PC1510 panel range from 01 to 36 and each section can be programmed independently Section 00 is reserved for binary programming which is normally done on instruction from factory technical personnel Once the 2 digits for the section you wish to program are entered the Armed light will go OFF the Ready light will go ON steadily a...

Page 15: ...factory technicalpersonnelforspecializedprogrammingnotcovered by the standard programming instructions 01 1st Phone Number This is the first telephone number the Communicator will dial See Section 25 Communicator Call Direction After entering section 01 for programming enter the telephone number the same way you would dial it on a touch tone phone Press after the last digit to complete the telepho...

Page 16: ...e F A and P keys will only take place if the appropriate sections in 09 are programmed with a reporting code 10 Maintenance Alarms and Restorals These reporting codes are used by the communicator to transmit the following list of alarms and restorals See section 05 as a guide to programming Low battery alarm AC failure alarm Fuse failure alarm Low battery restore AC failure restore Fuse failure re...

Page 17: ...municator is delayed 30 seconds If the alarm is acknowledged before the 30 second delay has expired pressing the key will silence the alarm and abort the transmission If the alarm is NOT acknowledged within the 30 second period transmission will proceed and cannot be aborted If the alarm has been silenced and all smoke detectors are not restored to normal the alarm will re sound after 90 seconds 3...

Page 18: ...ng data The first 2 digit number defines the number of attempts alarm and restoral pairs perzonethatthecommunicatorwillmakebeforeitshuts downforthatzone swingershutdown Thenumberofattempts is for the period as defined in the 1st System Option Code Section zone light 2 The number of attempts may be programmedfrom 00 to 99 where 00 meansthecommunicator will never shut down The fire zone cannot be sh...

Page 19: ... 0 through 9 as numbers in the code do not press the or keys If an error is made entering the code complete entry of the 4 digits then enter the section number again to enter the correct code Do not press or while entering the code 22 2nd Master Code Once the section number has been entered 20 21 or 22 enter a new 4 digit code Only use digits 0 through 9 as code numbers Do not press the or keys If...

Page 20: ... option is selected the PGM output is normally low That is it is just the reverse of all other options which are normally high and go low when activated This option is normally used as the negative return for power to 4 wire smoke detectors positive comes from the AUX terminal To activate this output to reset smoke detectors enter the 7 command The PGM terminal will go high open circuit and thus r...

Page 21: ...ng machine connected to the same phone line 30 Reset to Factory Default Software Entering 30 will perform a software reset to the factory default values Once this command is entered the keypad buzzer will beep several times The Trouble LED will be ON during the reset sequence Hardware Iftheinstaller scodeisforgottenandasoftwareresetcannotbe performed thepanelcanberesettothefactorydefaultvalues wit...

Page 22: ... the keypad will sound a constant tone during the Entry Delay During the last 10 seconds of the Entry Delay the keypad will sound a pulsing tone to warn that the delay is about to expire When the urgency option is selected for the audibile Exit Delay the keypad will sound a pulsing tone during the Exit Delay During the last 10 seconds of the Exit Delay the keypad will sound a faster pulsing tone t...

Page 23: ..._________________________________ ZONES Zone Type Protected Area 1 _____________________________ __________________________________________________________________ 2 _____________________________ __________________________________________________________________ 3 _____________________________ __________________________________________________________________ 4 _____________________________ ______...

Page 24: ...the digit 0 in the account code For a 3 digit code enter 0 for the 4th digit 03 2nd Phone Number Page 11 04 2nd Account Code Page 11 05 Zone Alarm Reporting Codes Page 11 For single digit reporting codes enter 0 as the second digit Enter 1 HEX A to transmit a zero Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 4 Alarm Zone 5 Alarm Zone 6 Alarm 06 Zone Restoral Reporting Codes Page 11 For single digit...

Page 25: ...g if an alarm occured during the previous armed period Access Code 1 Access Code 2 Access Code 3 Access Code 4 Access Code 5 Access Code 6 After Alarm Code 09 Priority Alarms and Restorals Page 12 Actuation of the F A or P keys will immediately transmit both an alarm and restoral code There is no delay on the restoral code transmission Fire Loop Trouble Keypad P anic Alarm Keypad F ire Alarm Keypa...

Page 26: ... 0 2 Zone 4 0 2 Zone 5 0 8 Zone 6 First Digit Second Digit 0 Slow Audible 0 Standard Delay 1 Slow Silent 1 Instant 2 Fast Audible 2 Interior 3 Fast Silent 3 Interior Home Away 4 24 Hour Bell 5 24 Hour Bell Buzzer 6 24 Hour Buzzer 7 Aux Delay Uses Auxiliary Entry Exit Times 8 Fire Any one zone may be set as a FIRE zone 12 1st System Option Code Page 13 Default Zone Light ON Zone Light OFF OFF Zone ...

Page 27: ...e Light OFF OFF Zone Light 1 User code required for bypass Code not required OFF Zone Light 2 4 Enabled 4 Disabled OFF Zone Light 3 Periodic downloading Periodic test transmit OFF Zone Light 4 4 access code required 4 no code required ON Zone Light 5 P anic audible buzzer P anic silent buzzer OFF Zone Light 6 Partial closing identified Not identified 15 Communication Variables Page 14 Default 0 3 ...

Page 28: ...smission delay minutes 0 5 0 Slow loop response time x 10 ms 0 3 0 Test transmission cycle or auto download cycle time days Valid entries are 001 to 255 Do not enter 000 Do not enter 000 Do not enter 000 Do not enter 000 Do not enter 000 18 Auxiliary Delay Loop Entry Exit Times Page 15 Default 0 4 5 Entry Time seconds 1 2 0 Exit Time seconds Valid entries are 001 to 255 19 System Clock Times Page ...

Page 29: ...hake 3 1 4 1 and 4 2 non extended formats 1 SESCOA FRANKLIN DCI VERTEX 20 BPS 2300 Hz handshake 3 1 4 1 and 4 2 non extended formats 2 SILENT KNIGHT FAST 20 BPS 1400 Hz handshake 3 1 4 1 and 4 2 non extended formats 3 RADIONICS 2300 1400 Hz handshake 3 1 4 2 non extended formats 4 RADIONICS 2300 1400 Hz handshake 3 1 4 2 non extended with parity format 5 DO NOT USE 6 DO NOT USE 7 DO NOT USE 8 SILE...

Page 30: ...e Alarms and Restorals 0 No transmissions for this group 1 Access Code Openings and Closings 1 Call 1st number and backup to 2nd number 1 Priority Alarms and Restorals 2 Call 2nd phone number only 1 Maintenance Alarms and Restorals 3 Always call both phone numbers Section 13 Light 1 OFF and 2nd phone number must be programmed 26 Downloading Telephone Number Page 17 This telephone number is used by...

Page 31: ... Hz AC 60 Hz OFF Zone Light 6 Restore on bell time out Restore as follower If zone light 4 is ON bypass status will always be shown If zone light 4 is OFF bypass status is shown only when the panel is disarmed 32 5th System Option Code Page 18 Default Zone Light ON Zone Light OFF OFF Zone Light 1 AC excluded from trouble AC included OFF Zone Light 2 No bell during auto arm Bell during auto arm ON ...

Page 32: ...uawk during Entry Delay No Bell Squawk during Entry Delay OFF Zone Light 6 F Key disabled F Key enabled 35 For Future Use Page 18 36 Keypad Lockout Control Page 18 Default 0 0 Number of Invalid Codes before lockout 0 0 Lockout Duration minutes Enter 2 2 digit numbers in the range of 00 to 99 Program the Number of Invalid Codes as 00 to disable the lockout feature 90 Installer s Lockout Enable Page...

Page 33: ...EPHONE PLUG WHT Battery capacity for emergency standby is at least 4 hours if the total load BELL AUX O P is 800mA or less Recommended battery is Yuasa MNP4 12 Do not connect transformer to a receptacle controlled by a switch Temperature Range 0 C 47 C 32 F 120 F Maximum Humidity 85 R H BATT 5A BELL 5A AUX 1A WARNING For continued protection against the risk of fire replace only with the same type...

Page 34: ... of attempts will be limited to a replacement of the product as the exclusive remedy for breach of warranty Under no circumstances shall Digital Security Controls Ltd be liable for any special incidental or consequential damages based upon breach of warranty breach of contract negligence strict liability or any other legal theory Such damages include but are not limited to loss of profits loss of ...

Page 35: ...m may not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke detectors such as when the fire is in a chimney walls or roofs or on the other side of closed doors Smoke detectors may not detect smoke from fires on another level of the residence or building Every ...

Page 36: ... 1999 Digital Security Controls Ltd Toronto Canada www dscgrp com Printed in Canada 29004757 R001 ...

Reviews: