8.0

Commercial Fire Applications
(DS7400Xi Series)

8.1

Single Keypad Use in Commercial Fire
Systems

The keypad must be used on the keypad bus and mounted
to the front of the control enclosure. If the keypad is within
the same room as the control equipment, with the wire run
in conduit (or equally protected against mechanical injury)
within 6 m (20 ft.) of the control equipment.

The keypad must be assigned as Keypad Address 1.

8.2

Multiple Keypad Use in Commercial Fire
Systems

Only one keypad must be used on the panel's option bus
and assigned as Keypad Address 11-14.

The keypad must be mounted to the front of the control
enclosure. If the keypad is within the same room as the
control equipment, with the wire run in conduit (or equally
protected against mechanical injury) within 6 m (20 ft.) of
the control equipment.

9.0

Instruction Label and Slide

Two instruction labels are provided and one must be placed
onto the pull-out slide. The slide may be installed to pull
from the left or the right (slide it into rear of base).

1

2

3

4

5

Figure 8: Instruction Label and Slide Installation

1 - Back of keypad

2 - Pull-out  slide

3 - Instruction label (Writing on other side)

4 - Pull-out slide guide track

5 - Alternate location of pull-out slide

Use Instruction Label (P/N: 28815) if the keypad(s) you
are installing are for use with the DS7060, DS7080i
Series and DS7400Xi Series Control Panels.

Use Instruction Label (P/N: 49646) if the keypad(s) you
are installing are for use with the DS7200 Series
Control Panels.

Keypad Notification

Possible Causes

DS7445i Continuous
Sounder.

The yellow and green wires
have been disconnected

The control panel has
malfunctioned. Replace the
control panel.

DS7447i/DS7447E
Continu

ous Sounder and

System Fault

 

d

isplay.

The yellow and green wires
have been disconnected

The control panel has
malfunctioned. Replace the
control panel.

DS7445I Continuous
Sounder

The keypad has not been
programmed properly at the
control panel.

DS7447i/ DS7447E
Continuous Sounder and

Not Programmed

 Display.

The keypad has not been
programmed properly at the
control panel.

DS7445i 3-beep Error Tone
on All Keypads.

Two or more keypads have the
same address.

DS7400 Series Only: DS7430
MUX Module not installed
on main board correctly.
Check pin alignment.

DS7400 Series Only: Keypad
and another device on the
option bus have the same
address.

DS7445i/DS7447i/
DS7447E
3-beep Error Tone on All
Keypads and 

Entry

Error. Please Try

Again

 Display on

DS7447i/DS7447E Keypad.

Two or more keypads have the
same address.

DS7400 Series Only: DS7430
MUX Module not installed
on main board correctly.
Check pin alignment.

DS7400 Series Only: Keypad
and another device on the
option bus have the same
address.

Table #: One-column Wide

Be careful when installing the label. Place it as
close to the pull-tab as possible.

10.0

Troubleshooting

See Table 5 for troubleshooting tips.

Summary of Contents for DS7445i

Page 1: ...lace the shorting jumpers over the address pins as shown in Figure 2 Figure 2 shows proper shorting jumper placements Wire Gauge 18 AWG is required for UL Fire Installations Wire Type no shield 4 wire Max Resistance wire resistance should not exceed 33 ohms Table 1 Keypad Wiring Distances Maximum distance between control panel and each keypad should not exceed 305 m 1000 ft 1 Jumper Plug ON covers...

Page 2: ...OFF OFF ON ON 18 OFF ON OFF OFF ON ON 19 ON ON OFF OFF ON ON 20 OFF OFF ON OFF ON ON 21 ON OFF ON OFF ON ON 22 OFF ON ON OFF ON ON 23 ON ON ON OFF ON ON 24 OFF OFF OFF ON ON ON 25 ON OFF OFF ON ON ON 26 OFF ON OFF ON ON ON 27 ON ON OFF ON ON ON 28 OFF OFF ON ON ON ON 29 ON OFF ON ON ON ON 30 OFF ON ON ON ON ON 31 ON ON ON ON ON ON 32 OFF OFF OFF OFF OFF ON Table 4 Keypad Address Selections for Oth...

Page 3: ...base While feeding the excess wiring out of the rear of the base press the cover straight in until it latches 6 0 DS7447i DS7447E Contrast Control Turn the DS7447i DS7447E Keypad s contrast control clockwise to increase contrast Turn it counter clockwise to decrease contrast See Figure 5 for the location of the Contrast Control on the DS7447i DS7447E LCD Keypad 7 0 Special Key Labeling Do not labe...

Page 4: ...on of pull out slide Use Instruction Label P N 28815 if the keypad s you are installing are for use with the DS7060 DS7080i Series and DS7400Xi Series Control Panels Use Instruction Label P N 49646 if the keypad s you are installing are for use with the DS7200 Series Control Panels Keypad Notification Possible Causes DS7445i Continuous Sounder The yellow and green wires have been disconnected The ...

Reviews: