7/03
Keypads - DS7445i/DS7447i/DS7447E
Page 4 of 4
P/N: 49205D
Installation Instructions
© 2003 Bosch Security Systems
130 Perinton Parkway, Fairport, NY 14450-9199 USA
Customer Service: (800) 289-0096; Technical Support: (888) 886-6189
8.0
Commercial Fire Applications
(DS7400Xi Series)
8.1
Single Keypad Use in Commercial Fire
Systems
The keypad must be used on the keypad bus and mounted
to the front of the control enclosure. If the keypad is within
the same room as the control equipment, with the wire run
in conduit (or equally protected against mechanical injury)
within 6 m (20 ft.) of the control equipment.
The keypad must be assigned as Keypad Address 1.
8.2
Multiple Keypad Use in Commercial Fire
Systems
Only one keypad must be used on the panel's option bus
and assigned as Keypad Address 11-14.
The keypad must be mounted to the front of the control
enclosure. If the keypad is within the same room as the
control equipment, with the wire run in conduit (or equally
protected against mechanical injury) within 6 m (20 ft.) of
the control equipment.
9.0
Instruction Label and Slide
Two instruction labels are provided and one must be placed
onto the pull-out slide. The slide may be installed to pull
from the left or the right (slide it into rear of base).
1
2
3
4
5
Figure 8: Instruction Label and Slide Installation
1 - Back of keypad
2 - Pull-out slide
3 - Instruction label (Writing on other side)
4 - Pull-out slide guide track
5 - Alternate location of pull-out slide
•
Use Instruction Label (P/N: 28815) if the keypad(s) you
are installing are for use with the DS7060, DS7080i
Series and DS7400Xi Series Control Panels.
•
Use Instruction Label (P/N: 49646) if the keypad(s) you
are installing are for use with the DS7200 Series
Control Panels.
Keypad Notification
Possible Causes
DS7445i Continuous
Sounder.
The yellow and green wires
have been disconnected
The control panel has
malfunctioned. Replace the
control panel.
DS7447i/DS7447E
Continu
ous Sounder and
System Fault
d
isplay.
The yellow and green wires
have been disconnected
The control panel has
malfunctioned. Replace the
control panel.
DS7445I Continuous
Sounder
The keypad has not been
programmed properly at the
control panel.
DS7447i/ DS7447E
Continuous Sounder and
Not Programmed
Display.
The keypad has not been
programmed properly at the
control panel.
DS7445i 3-beep Error Tone
on All Keypads.
Two or more keypads have the
same address.
DS7400 Series Only: DS7430
MUX Module not installed
on main board correctly.
Check pin alignment.
DS7400 Series Only: Keypad
and another device on the
option bus have the same
address.
DS7445i/DS7447i/
DS7447E
3-beep Error Tone on All
Keypads and
Entry
Error. Please Try
Again
Display on
DS7447i/DS7447E Keypad.
Two or more keypads have the
same address.
DS7400 Series Only: DS7430
MUX Module not installed
on main board correctly.
Check pin alignment.
DS7400 Series Only: Keypad
and another device on the
option bus have the same
address.
Table #: One-column Wide
Be careful when installing the label. Place it as
close to the pull-tab as possible.
10.0
Troubleshooting
See Table 5 for troubleshooting tips.