Page 49
Installation and operation manual – Chic-Choc woodburning cookstove
ENGLISH
8.2 Floor Protection
This stove is designed to prevent the floor from overheating. However, it must be placed on a
non-flammable surface to protect the floor from hot embers that may fall during loading.
Any type of tile will require a continuous non combustible sheet beneath to prevent the possibility
of embers falling through to the combustible floor if cracks or separation should occur in the
finished surface. Check local codes for approved alternatives. No protection is required if the
unit is installed on a non-combustible floor (ex: concrete).
FLOOR PROTECTION
Canada
USA
G
6
8" (203 mm)
N/A
H
8" (203 mm)
N/A
I
18" (457 mm)
From door
opening
16" (406 mm)
From door
opening
J
N/A
8" (203 mm)
K
63-
1
⁄
8
" (1603 mm)
54-
5
⁄
8
" (1387 mm)
N
7
N/A
See note 9
S
53" (1346 mm)
43" (1092 mm)
T
37-
1
⁄
2
" (953 mm)
30-
1
⁄
2
" (775 mm)
U
63-
1
⁄
8
" (1603 mm)
54-
5
⁄
8
" (1387 mm)
V
84-
1
⁄
2
" (2146 mm)
70-
3
⁄
8
" (1788 mm)
G
H
J
S
I
K
Figure 18: Floor protection
U
T
V
FLUSH
30''
D
A
B
E
US
36''
92cm
CAN
48''
122cm
Ve
Ho
N
80''
203cm
Figure 19: Clearances
Figure 20: Clearances
6
The floor protection at the back of the stove is limited to the stove’s required clearance if such clearance is smaller than 8 inches (203 mm).
7
Only required under the horizontal section (Ho) of the connector. Must exceed each side of the connector by at least 2 inches (51 mm).