2.4 DRAFT 

 
Your  E.P.A  Drolet 

stove’s  performance  will  be  optimised  if  it  is  installed  with  a 

chimney (flue) system that provides an adequate draft.  The draft is the force that 
moves  air  from  the  appliance  up  through  the  chimney  and  is  predominantly 
affected  by  the  height  and  diameter  of  the  chimney,  as  well  as  the  stack 
temperatures  of  the  stove.  If  you  test  the  draft  using  a  pressure  gauge,  the 
reading should be between .05 - .07 inches of water column (w.c.) at a medium-
high fire. A draft measure of less than .03" w.c. will cause operational difficulties 
while too much draft (greater than .10" w.c.) will result in over-firing of the stove. 
This can result in excessive operating temperatures. In this case, the installation 
of elbows totaling no more than 180° (ex.: 2 x 30° elbows, 2 x 45° elbows or 2 x 
90°  elbows)  can  be  installed  to  help  reduce  excessive  draft.  If  the  addition  of 
elbows  is  not  sufficient,  a  manual  damper  can  be  installed  in  the  vertical  flue 
pipe. 
 

2.5 OUTSIDE COMBUSTION AIR 

 
It is recommended to install 3’’ (76mm) outside air intake in the room where the stove is 
located or nearby. 
 
The following are signs that a fresh air kit may be required: 
 

  Your stove does not draw steadily, smoke rollouts occur, wood burns poorly, or 

back-draft occurs whether or not there is combustion present. 

 

  Existing  fuel-fired  equipment  in  the  house,  such  as  fireplaces  or  other  heating 

appliances,  smell,  do  not  operate  properly,  suffer  smoke  rollouts  when  opened, 
or back-draft occurs whether or not there is combustion present. 

 

  Opening a window slightly on a calm (windless) day  alleviates any of the above 

symptoms. 

 

  The house is equipped with a well-sealed vapour barrier and tight fitting windows 

and/or has any powered devices that exhaust house air. 

 

  There is excessive condensation on windows in the winter. 

 

  A ventilation system is installed in the house. 

 

Summary of Contents for 45521A

Page 1: ...ATIONAL INC 250 de Copenhague Saint Augustin de Desmaures Quebec Canada G3A 2H3 Tel 418 878 3040 Fax 418 878 3001 This manual is available for free download on the manufacturer s web site It is a copy...

Page 2: ...perty damage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installation requirements in your area and the need to obtain a permit KEEP...

Page 3: ...4 DRAFT 28 2 5 OUTSIDE COMBUSTION AIR 28 2 6 THE ADVANTAGE OF INSTALLING A BLOWER FAN 29 SECTION 3 0 OPERATION 30 3 1 SAFETY INFORMATION 30 3 2 FUEL 32 3 2 1 The use of manufactured logs 33 3 2 2 Simp...

Page 4: ...and or local building codes fire officials or other authorities having jurisdiction should be contacted to determine what restrictions and installation requirements might apply locally 1 1 GENERAL IN...

Page 5: ...s facilitated by the installation of a blower 1 3 CLEARANCES TO COMBUSTIBLES AND FLOOR PROTECTOR To install your appliance correctly it is extremely important to respect all clearances to any combusti...

Page 6: ...6 FIGURE 1 3 Clearances to combustible materials and floor protection...

Page 7: ...Only required under the horizontal section of the connector Must exceed each side of the connector by at least 2 inches 51 mm Reduced clearances using shielding You may decrease the clearances by inst...

Page 8: ...least 1 25 mm by non combustible spacers see graphic 3 50 33 Ceramic tiles or an equivalent non combustible material on fire proof supports with a minimum of 0 024 0 61 mm sheet metal backing spaced...

Page 9: ...d combustible ceiling B 20 in 500 mm minimum C 1 in 25 mm minimum D Between 1 in and 3 in 25 mm and 75 mm E 3 in 75 mm minimum F 18 in 457 mm minimum 1 Shielding 2 Non combustible spacers 3 Ceiling pr...

Page 10: ...3 A 1 in 25 mm minimum 1 Combustible wall 2 Non combustible spacers 3 Non combustible support 4 Ceramic tile or non combustible material Graphic 4 A 1 in 25 mm minimum 1 Combustible wall 2 Non combust...

Page 11: ...Graphic 5 A 1 in 25 mm minimum 1 Combustible wall 2 Non combustible spacers 3 Brick Graphique 6 A 1 in 25 mm minimum 1 Combustible wall 2 Non combustible spacers 3 0 024 0 61 mm thick sheet metal 4 Br...

Page 12: ...BUILT CHIMNEY WITH INSULATION OR ANY OTHER MATERIAL INSULATION PLACED IN THIS AREA COULD CAUSE ADJACENT COMBUSTIBLES TO OVERHEAT DO NOT USE MAKESHIFT COMPROMISES DURING INSTALLATION AS THEY MAY BE SA...

Page 13: ...0 6 m See Figure 2 2 The minimum overall height of the chimney system measured from the stove top to the exterior termination cap of the chimney should be at least 12 3 66m A chimney which is too sho...

Page 14: ...Wall support system If your chimney must rise along an outside wall you need to connect it to your stove through an adjacent wall In Canada the CSA B365 and the CSA C22 1 installation codes are to be...

Page 15: ...rial You will then be able to determine where the chimney will pass through the wall You will probably have to adjust the stove position slightly to ensure that your chimney will run between the studs...

Page 16: ...ons through concrete walls 3 You must first secure the wall thimble into the exterior wall surface Then do the same inside and fasten the trim plate 4 Then from outside the building slide a short chim...

Page 17: ...using wall bands Wall bands wrap around the chimney and then attach to the wall Install the first one 3 feet above the wall support Then you will need another band for each 8 feet of chimney Note if y...

Page 18: ...l called CHIMNEY CONNECTOR Ceiling support system If your chimney must rise inside the house and go through the ceiling you need to connect it to your stove at the ceiling level For this type of insta...

Page 19: ...en the joists You can use a stud finder to locate the joists You also need to take into account the minimum clearances to combustible materials After you have determined where the chimney will go thro...

Page 20: ...plate is flush with the underside of the ceiling and assembly is level secure it with screws 4 Once the support is secure you can begin to assemble the chimney by lowering the first section into the...

Page 21: ...s passes through a living space Elbows 15o or 30o are used when you need to offset your chimney to clear an obstruction or to avoid having to cut joists 7 Once you have cut through your roof and frame...

Page 22: ...ain cap and you can head back inside If the chimney extends more than 5 feet above the roof deck roof guys with telescoping legs and draw bands are required 9 You are now ready to connect your chimney...

Page 23: ...built thimble on construct your own brick thimble If you are using a masonry chimney it is important that it be built in compliance with the specifications of the Building Code in your region It must...

Page 24: ...24 FIGURE 2 2 2 B Factory Built Thimble...

Page 25: ...25 FIGURE 2 2 2 C Brick Thimble...

Page 26: ...per foot with the upper end of the section toward the chimney See Figure 2 3 Detail B To insure a good draft the total horizontal length of the connector should never exceed 8 to 10 2 4 to 3 04 m In...

Page 27: ...tween the stove and chimney See figure 2 4 A The use of two 45 degree elbows See figure 2 4 C is often preferable to a single 90 degree elbow See figure 2 4 B because less turbulence is created in the...

Page 28: ...ed to help reduce excessive draft If the addition of elbows is not sufficient a manual damper can be installed in the vertical flue pipe 2 5 OUTSIDE COMBUSTION AIR It is recommended to install 3 76mm...

Page 29: ...nt the blower enables you to extend the radiation power of your stove You can purchase this option through your DROLET dealer Make sure to specify this part number AC02050 You can also install a therm...

Page 30: ...TOVE CAUTIONS THIS APPLIANCE SHOULD BE MAINTAINED AND OPERATED AT ALL TIMES IN ACCORDANCE WITH THESE INSTRUCTIONS THE USE OF SOME TYPES OF PRESERVATIVE TREATED WOOD AS A FUEL CAN BE HAZARDOUS 3 1 SAFE...

Page 31: ...mperature does not exceed 900o F 482o C If you are using a magnetic thermometer make sure that the temperature does not exceed 475o F 246o C If the door handle of the stove becomes excessively hot to...

Page 32: ...eal Dry seasoned cord wood can be distinguished from green wood by the cracks at each end of the logs Wet or green wood will tend to cause the fire to smoulder producing large amounts of creosote Creo...

Page 33: ...gs into your stove like you would with regular cord wood Start with one log and gradually increase the load to 2 or 3 logs and see how your stove reacts Use a chimney flue thermometer and make sure th...

Page 34: ...until the fire is well established Once the firebox is hot the air control can be partially closed After 30 minutes to one hour you can close the air control completely In order to have the best indic...

Page 35: ...bustion efficiency and to reduce the amount of creosote build up The best performance will be obtained by adding relatively small amounts of fuel to a well established ember bed and then operating wit...

Page 36: ...year in order to insure good control over the combustion maximum efficiency and security To change the door gasket simply remove the damaged one Carefully clean the gasket groove apply a high tempera...

Page 37: ...risk of a chimney fire Call a professional chimney sweep or go to your local E P A Drolet dealer purchase a chimney brush and have the chimney cleaned The chimney and chimney connector must be in good...

Page 38: ...ull load of seasoned cordwood inserted inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of woo...

Page 39: ...39 BRICK LAYOUT ITEM PART DESCRIPTION QTY 1 29010 4 X 9 BRICK 12 2 29010 CUT 4 1 2 X 9 BRICK CUT 2 3 29015 4 X 9 BRICK 2 4 29015 CUT 3 X 9 X 1 1 4 BRICK 2...

Page 40: ...lacement part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after ins...

Reviews: