DRISTEEM TCI-W11  HUMIDISTAT INSTALLATION MANUAL

INSTALLATION

•  Install the controller on an easily accessible interior 

wall, approximately 1.5 m above the floor in an area 

of average temperature.

•  Avoid direct sunlight or other heat sources (e.g. above 

radiators and heat emitting equipment).

•  Avoid locations behind doors, outside walls,and below 

or above air discharge grills and diffusers.

•  Location of mounting is less critical if external sensors 

are used.

•  Ensure adequate air circulation to dissipate heat 

generated during operation.

•  Observe local regulations.
•  Do not mount in a wet or condensation prone 

environment.

INSTALLATION INSTRUCTIONS

1.  Connect the wires to be connected to the terminals of 

the power case according to wiring diagram.

2.  Install the mounting plate to the flush mounting box.
Notes: 

•  Make sure the nipple with the front holding screw is 

facing to the ground. 

•  Make sure the mounting screw heads do not stand out 

more than 0.2" (5 mm) off the surface of the mounting 

plate.

3.  Ensure the jumpers are set correctly.
4.  Slide the two latches located on the top of the front 

part into the hooks at the upper side of the mounting 
plate.

5.  Carefully lower the front part until the interconnector 

reaches the mounting-plate. Continue pressing in a 
gentle way until the front part is fully connected. While 
inserting the connectors, a slight resistance can be felt. 
This is normal. Do not use excessive force.

6.  With a Phillips-type screw driver of size #2, carefully 

tighten the front holding screw to secure the front part 
to the mounting plate. This screw is located on the 
front lower side of the unit. There is no need to tighten 
the screw too much.

JUMPER CONFIGURATION

Jumpers are mounted vertically only.

1.  A0 - Selection of output signal type

•  Left position: voltage output 0 - 10 V) factory 

default.

•  Right position: current output (0 - 20 mA)

2.  UI - Selection of input signal type

•  Left position: voltage input (0 - 10 V) factory 

default.

•  Middle position: current input (0 - 20 mA)
•  Right position: RT or dry-contact input

FIGURE 5-1: CONNECTION

X

H1

24 V AC/DC

0 V (COM)

2

G

Y

M1

X

U1

G0

G0

7

X1

6

Y1

G0

Table 5-1:
Terminal connections

TCI-W11-U-H 

(Room)

TCI-W11-U  

(Duct)

G0 Ground

1

1

G

24VAC/21VDC

2

2

Y1

Control output

6

6

X1

Duct sensor Input

7

Summary of Contents for TCI-W11-U

Page 1: ...ious injury from electrical shock or damage to product and can void product warranty due to possible product misapplication CAUTION 1 Do not set humidity higher than recommended or moisture can accumulate which can cause bacteria and mold growth or dripping water into building spaces Dripping water can cause property damage bacteria and mold growth can cause illness 2 Do not set humidity up to rec...

Page 2: ...umidity default disabled Set min or max humidity display default 0 and 100 Calibrate sensor Tune the PI control loop Enable security to prevent user from changing parameters WARNING This device is intended to be used for comfort applications Where a device failure endangers human life and or property it is the responsibility of the owner designer and installer to add additional safety devices to p...

Page 3: ... to EN60730 1 Environment Operation To IEC 721 3 3 Climatic conditions class 3K5 Temperature 0 to 50ºC 32 to 122ºF Humidity 95 RH non condensing Transport storage To IEC 721 3 2 and IEC 721 3 1 Climatic conditions class 3K5 and class 1K3 Temperature 25 to 70ºC 13 to 158ºF Humidity 95 RH non condensing Mechanical conditions class 2M2 Standards conformity EMC standard low voltage directive 2014 30 E...

Page 4: ...RE 4 1 USING THE DRISTEEM HUMIDISTAT DISPLAY Down Decrease SET POINT Parameter setting SCROLL menu options and parameters Off Energy hold off Outputs are off inputs monitored for alarms Up Increase SET POINT Parameter setting SCROLL menu options and parameters DISPLAY INPUT VALUES 75 UI1 For TCI W11 Press OPTION 2 s SEL and H C is displayed Press UP key once UI1 and its value are displayed UI1 is ...

Page 5: ... set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance can be felt This is normal Do not use excessive force 6 Wit...

Page 6: ...ts tied to this input will be disabled Verify input connections jumper settings and parameter settings for the input involved Err3 A function refers to a disable input Disable the function or enable the input Err4 Internal failure Product must be replaced Table 6 2 Replacement parts Model Description Part Number TCI W11 U W26 kit 1 Model TCI W11 U W26 1 duct sensor 600968 TCI W11 U W26 PI controll...

Reviews: