DRISTEEM RO 200 SYSTEM WATER TREATMENT SYSTEMS INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
OPERATION
Start-up checklist
If an item in the Start-up checklist below does not apply to your system, skip to the next item and continue the process.
☐
Read this manual and all other information that was provided with your system.
☐
Verify that all fi eld wiring is done according to the instructions in this manual and in the unit wiring diagram.
☐
Confi rm that proper grounding and an approved earth ground are provided.
☐
Confi rm that the keypad/display is mounted with its modular cable routed away from high-voltage circuits and
connected to the Display connector on the Vapor-logic board.
☐
Install cartridge fi lter and check for leaks.
☐
Precharge pressurized RO storage tank to 28 psi (195 kPa).
Note:
This precharge pressure is for pressurized RO storage tank cut-in and cut-out switch points at 30 and 50 psi
(210 and 345 kPa) respectively.
☐
Turn on the water supply, and confi rm there are no leaks.
☐
Turn on power to the unit, and confi rm the Main menu is displayed on the keypad/display. The display may take
several seconds to appear as the controller powers up.
☐
Confi rm in the Main Menu that the mode is “Auto” and that status is “Idle.”
☐
When “Idle” appears in main menu, confi rm that the inlet pressure is at least 40 psi (276 kPa) on the display.
☐
With suffi cient water available, the system in Auto mode, and the storage tank pressure less than 30 psi (210 kPa),
verify that the pump is activated.
☐
Set perm fl ow and recirc fl ow meter to desired setting.
☐
If you experience diffi culties, have the keypad/display information available along with the serial number and unit
Model, and call DriSteem Technical Support at 800-328-4447.
Note:
Instructions on how to properly care for the freeze protect chemical that is shipped with the system is available
on the SDS sheet at www.dristeem.com.
☐
Inspect to insure that no fl exible plumbing lines have been kinked or damaged during installation.
WARNING
Tipping hazard
Before installing the 200 series
reverse-osmosis system, use
supplied leg brackets or lag points
to permanently fi x the system to
the fl oor and/or adjacent building
structure. Failure to install according
to instructions can result in serious
injury or death. See page 10 for
instructions.