Page 1: ...200 series reverse osmosis systems Installation Operation and Maintenance Manual WATER TREATMENT READ AND SAVE THESE INSTRUCTIONS...

Page 2: ...instructions could produce the hazardous situations described resulting in property damage personal injury or death Failure to follow the instructions in this manual can cause moisture to accumulate...

Page 3: ...nd other hazardous conditions These hazardous conditions could cause property damage personal injury or death Contact with energized circuits can cause property damage severe personal injury or death...

Page 4: ...N 10 System operation 10 Initial system start up 10 System flush 10 Normal operations 10 Shutdown 10 Start up checklist 11 Start up 12 Start up procedure 12 Test operation 12 Initial system start up 1...

Page 5: ...al which was shipped with your RO system is a comprehensive operation manual Refer to it for information about using the keypad display and Web interface and for troubleshooting information Download D...

Page 6: ...a premature fouling of the membrane with a loss of permeate flow and permeate quality 5 Recommended minimum clearances if 24 or greater 610 mm above 6 152 mm left right and rear and 24 610 mm front le...

Page 7: ...2 Gallons minute 0 0 5 0 0 5 0 0 5 System pressure psi pump pressure through membranes 100 150 100 150 100 150 F C 50 10 50 10 50 10 Pre filters Sediment cartridge 5 micron 1 1 1 Carbon cartridge 10 m...

Page 8: ...system provides menus for all RO system functions with a Web interface for Ethernet access see Figure 4 1 The Vapor logic Installation and Operation Manual ships with the RO system Refer to it for in...

Page 9: ...REQUIREMENTS Supply water quality is an important component of DriSteem reverse osmosis system reliability and maintenance Water hardness can increase the reverse osmosis system maintenance requireme...

Page 10: ...6 DRISTEEM RO 200 SYSTEM WATER TREATMENT SYSTEMS INSTALLATION OPERATION AND MAINTENANCE MANUAL Flow schematic OVERVIEW FIGURE 6 1 FLOW SCHEMATIC RO200 PIPING...

Page 11: ...7 DRISTEEM RO 200 SYSTEM WATER TREATMENT SYSTEMS INSTALLATION OPERATION AND MAINTENANCE MANUAL Flow schematic OVERVIEW FIGURE 7 1 FLOW SCHEMATIC RO200 PIPING 1...

Page 12: ...let pressure is lower than 8 psi adjustable 7 High pressure pump and motor Rotary pump and motor to pressurize the incoming water 8 Membrane modules RO membrane elements housed in stainless steel pres...

Page 13: ...TEEM RO 200 SYSTEM WATER TREATMENT SYSTEMS INSTALLATION OPERATION AND MAINTENANCE MANUAL INSTALLATION Piping and instrumentation arrangement FIGURE 9 1 FLOW SCHEMATIC WITH A CARTRIDGE DECHLORINATOR OM...

Page 14: ...proper flushing of system 7 After the flush time is over press the power button OFF 8 Redirect the permeate line to the desired location NORMAL OPERATIONS 1 Turn the power back ON After the pump star...

Page 15: ...enu is displayed on the keypad display The display may take several seconds to appear as the controller powers up Confirm in the Main Menu that the mode is Auto and that status is Idle When Idle appea...

Page 16: ...falls below 30 psi 210 kPa INITIAL SYSTEM START UP 1 Close the manual valves to both the RO holding tank and all downstream equipment Open the manual valve leading to the drain 2 Open the feed water s...

Page 17: ...mation using the system operation data log on page 26 The values recorded at startup will be important for determining system performance at a later date OPERATING DO S AND DON T S DO 1 Change the car...

Page 18: ...y screen Press Up or Down arrow to move through menus and screens Press Enter to select or confirm Alarm label flashes when there is a system alarm Typical Home screen Status Tank pressure status Mess...

Page 19: ...n Filling System is supplying high pressure water to meet demand Full Storage tank is full system not running TEST OUTPUTS When completing an installation or repair cycle all outputs to verify operati...

Page 20: ...nit operation is suspended and the RO Flush valve remains open until the model specific RO flush time is met the unit is taken out of RO flush mode or the RO tank is drained See the Diagnostics sectio...

Page 21: ...ault Water temperature TDS sensor reading is out of range Yes Low inlet pressure Water pressure at RO inlet is less than 10 psi Yes High storage pressure Tank storage pressure has exceeded 60 psi Yes...

Page 22: ...4 Manual drain 5 Test outputs 6 Test run 1 to 4 1 to 4 Read HR 1 MSV 01 nvoRunMode Mode of the unit or system The defined options are 1 Auto 2 Local standby 3 System standby 4 Manual drain 5 Test out...

Page 23: ...07 nvoAlmOutPress See Table 17 2 Alarm menu Alarm_floor_water_ sensor_activated RW DV 08 BV 08 nvoAlmFloorWet See Table 17 2 Alarm menu Alarm_pressure_sensor_ out_of_range RW DV 09 BV 09 nvoAlmPrSens...

Page 24: ...e reaches 12 psi it is time to replace the sediment and carbon cartridges CHANGING CARTRIDGE FILTERS 1 Put the system into Standby mode and shut down the RO system 2 Close inlet supply valve 3 Un asse...

Page 25: ...1 5 per F This is normal and does not indicate membrane fouling A malfunction in the pretreatment pressure control or pump can cause a drop in feed water delivery pressure feed water flow product wate...

Page 26: ...tridge is installed 3 Remove the sediment filter from the pre filter housing 4 Replace the sediment filter with the cleaning cartridge and assemble into the filter housing 5 Turn the system ON and put...

Page 27: ...RO system OPTIONAL Instead of time use one of the following criteria a Run the system until the pH of the concentrate is almost the same as the cleaning solution pH 10 12 b Permeate rate for the syst...

Page 28: ...ridge with the preservative cartridge and assemble into the filter housing 5 Turn the system ON After 30 40 seconds shut down the system 6 Drain the system of the permeate solution as much as possible...

Page 29: ...ssure Cartridge filters plugged Change filters Solenoid valve malfunction Replace solenoid valve and or coil Permeate flow low Low water temperature Adjust water temperature Low system pressure Adjust...

Page 30: ...______ _________________________________________________________________________________________________________________________________ _______________________________________________________________...

Page 31: ...ee chlorine ppm Total hardness Total alkalinity pH Week 1 _________ Week 3 _________ Week 5 _________ Week 7 _________ Week 9 _________ Week 11 _________ MAINTENANCE Water quality test strips 0 25 50...

Page 32: ...ATMENT SYSTEMS INSTALLATION OPERATION AND MAINTENANCE MANUAL RO system Models 201 202 and 203 REPLACEMENT PARTS FIGURE 28 1 RO 200 SYSTEM REPLACEMENT PARTS Exploded view of the each unique replacement...

Page 33: ...04 400 4 METER 2GPM FLOW W NEEDLE VALVE 1 4 FNPT 2 501907 402 5 METER 2GPM FLOW 1 4 FNPT 1 501907 302 6 SEDIMENT FILTER 2 5 X 10 5 MICRON 1 550030 002 7 CARBON FILTER 2 5 X 10 10 MICRON 2 550030 003 8...

Page 34: ...408995 008 11 Contactor 35A SIEMENS 1 407010 001 4 Bushing 7 8 shutter HEYCO 1 407129 12 Display VL w o back Vapor logic 1 408495 002 5 Lug medium 1 409250 027 13 Case rear display Vapor logic 1 40849...

Page 35: ...31 DRISTEEM RO 200 SYSTEM WATER TREATMENT SYSTEMS INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes...

Page 36: ...strict liability in tort or any other legal theory even if DriSteem has notice of the possibility of such damages By purchasing DriSteem s products the purchaser agrees to the terms and conditions of...