55
RTS HUMIDIFIER RX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Inspection and maintenance
MAINTENANCE
OFF-SEASON SHUT-DOWN PROCEDURE
1. Switch off electrical power.
2. Remove the enclosure panels.
3. Shut off the water supply to the makeup valve.
4. Drain the evaporating chamber, and clean if necessary following the
instructions in this manual.
5. Replace the enclosure panels.
• Leave the evaporating chamber dry, the power off, and the water
shut-off valve closed until the next humidification season.
REMOVING THE TANK HEATER PLATE
1. Remove all but 2 heater plate nuts.
2. Loosen remaining two and use 1/4-20 bolts at weld nut locations to pry
cover from tank.
OM-8103
FIGURE 55-1: HEATER PLATE REMOVAL
Loosened
Loosened
Remove
Alternate tightening to break gasket seal
Alternate tightening
to break gasket
seal