SETUP AND CONFIGURATION
Description of available objects
Table 20-2:
Description of Available Objects
Object
Name (8 Bytes)
Description
Range/Type
R/W
Controller Information
AV 08
#Alarm
Number of alarms
8bit
R
Controller State
BV 00
OpStOo
Operation state On - Off: Inactive / Active
BV
R/W
MV 02
Degree
Operation state Celsius – Fahrenheit: 1 = Celsius, 2 =
Fahrenheit
MV
R/W
BV 04
AccSp
Enable access to set points
BV
R/W
MV 03
OpStOPMS
Operation State Master/Slave mode: “Master” /
“Slave”
MV
R/W
MV 04
OpStWink
Operation State “Wink” function: “WinkON” /
“WinkOFF”
MV
R/W
Universal Inputs
AI 101
UI-01
Universal Input 01, 16 bytes
Room RH
R
AV 101
UI-01-OS
Universal Input 01 Offset (calibration = 01u6), 16 bytes
Room RH
Offset
R/W
AI 106
UI-06
Universal Input 06, 16 bytes
Duct RH
R
AV 106
UI-06-OS
Universal Input 06 Offset, 16 bytes
Duct RH
Offset
R/W
Alarms
MV 601
AL-01
Alarm 1: Not Active, Active, Need confirmation, 16
bytes
Hi/Low Input
R/W
(1)
Control Loops
AV 211
LP-01-SSP
Saved set point, 16 bytes
R/W
AV 212
LP-01-CSP
Calculated set point
R
AV 213
LP-01-PROP
Proportional output
R
Analog Outputs
MV 311
AO-01-ST
Analog Output 1 state
R
AV 311
AO-01-VAL
Analog Output 1 Value, 16 bytes
R
AV 312
AO-01-OV
Analog Output 1 Override Value
R/W
(1) Writable to “not active” only, if state is “not active, need confirmation”.
Note: The DriSteem application of the X2 controller on DriSteem model TRI2 does not use all available BACnet points.
This list includes only the BACnet points as used with DriSteem humidifiers. Some points apply only to duct sensor
applications and others apply only to room wall sensor applications.