INSTALLATION
• Install the controller on an easily accessible interior
wall, approximately 1.5 m above the floor in an area
of average temperature.
• Avoid direct sunlight or other heat sources (e.g. above
radiators and heat emitting equipment).
• Avoid locations behind doors, outside walls,and below
or above air discharge grills and diffusers.
• Location of mounting is less critical if external sensors
are used.
• Ensure adequate air circulation to dissipate heat
generated during operation.
• Observe local regulations.
• Do not mount in a wet or condensation prone
environment.
INSTALLATION INSTRUCTIONS
1. Connect the wires to be connected to the terminals of
the power case according to wiring diagram.
2. Install the mounting plate to the flush mounting box.
Notes:
• Make sure the nipple with the front holding screw is
facing to the ground (TCI models only).
• Make sure the mounting screw heads do not stand out
more than 0.2" (5 mm) off the surface of the mounting
plate.
3. Ensure the jumpers are set correctly (TCI models only).
4. Slide the two latches located on the top of the front
part into the hooks at the upper side of the mounting
plate.
5. Carefully lower the front part until the interconnector
reaches the mounting-plate. Continue pressing in a
gentle way until the front part is fully connected. While
inserting the connectors, a slight resistance can be felt.
This is normal. Do not use excessive force.
6. With a Phillips-type screw driver of size #2, carefully
tighten the front holding screw to secure the front part
to the mounting plate. This screw is located on the
front lower side of the unit. There is no need to tighten
the screw too much (TCI models only).
JUMPER CONFIGURATION (TCI MODELS ONLY)
Jumpers are mounted vertically only.
1. A0 - Selection of output signal type
• Left position: voltage output (0 - 10 V) factory
default.
• Right position: current output (0 - 20 mA)
2. UI - Selection of input signal type
• Left position: voltage input (0 - 10 V) factory
default.
• Middle position: current input (0 - 20 mA)
• Right position: RT or dry-contact input
FIGURE 10-1: CONNECTION (TCI MODELS ONLY)
Table 10-1:
TCI Terminal connections
TCI-W11-U-H
(Room)
TCI-W11-U
(Duct)
G0 Ground
1
1
G
24VAC/21VDC
2
2
Y1
Control output
6
6
X1
Duct sensor Input
—
7
INSTALLATION
Installation instructions
OM-8134
10
DRISTEEM TCI AND TRI2 HUMIDISTAT INSTALLATION, OPERATION, AND MAINTENANCE MANUAL