Turn the unit on
Press the “on” button on the control panel.
How to use the control panel
The display panel uses an LCD liquid crystal display
featuring a blue backlight. The display provides a variety
of information about the unit and the operating
environment, including dehumidification mode, defrost
cycle, water full indicator, fan operation indicator, relative
humidity, total run time, and error codes.
1. Control Panel Buttons
When any button is pressed, the backlight turns on. The
backlight goes off after 30 seconds.
1.1 ON/OFF
key:
Each time the ON/OFF key is
pressed, the controller will cycle “on-off-on”. When the
unit is first plugged in, the unit will complete an
automatic self-test before the ON/OFF are available for
use.
1.2 Up
▲key:
Increase humidistat setting. Each press
increases the setting in 1% RH increments to a
maximum of 90% RH. Holding the key will increase the
setting in 5% RH increments each second. Release the
key to accept the desired RH setting.
1.3 Down
▼key:
Decrease humidistat setting. Each
press decreases the setting in 1% RH increments to a
minimum of 30% RH. Holding the key will decrease the
setting in 5% RH increments each second. Release the
key to accept the desired RH setting.
1.4 Purge
key:
Use this button to pump out the
condensate tank. The pump operates for approximately
30 seconds.
2. Functional mode description
2.1. Humidistat operation
1) Press ▲and ▼ to adjust the
dehumidification level.
The available range is 30%–90% RH. The default
humidity setting is 60% RH.
NOTE: To operate the unit in continuous
dehumidification mode
, press
the ▼key
until the
30% RH setting is displayed, and then press the
▼key
again. The panel will display "CO" indicating
the unit has entered continuous dehumidification
mode. When setting the humidity, the set humidity
display flashes. If no keys are pressed for 5
seconds, the the screen will show ambient humidity.
2) T Environment humidity -
T set humidity ≥3, the
compressor and fan on.
3) T Environment humidity-T set humidity
≤
-3, the
compressor stops and the fan runs. The compressor
restart needs to meet: T Environment humidity-T set
humidity
≥3 and 3 minutes delay
3. Operation control description
Any time the unit is turned off or power is interrupted, the
system initiates a 3-minute delay before the unit can be
turned on again.
3.1 Defrost Function
If the system detects the build-up of ice on the coil, the
unit will go into defrost mode and the defrost icon will
display. When the defrost cycle is complete, the defrost
icon will turn off and the unit will automatically resume
normal operation.
3.2 Condensate Tank Full
When the condensate tank is, the pumpout icon on the
panel will display and the pump will operate for
approximately 20 seconds until it detects no more water
in the tank. If the system continues to detect water after
40 seconds, the pump will stop and the system will
display the error code E4 and beep twice every 5
minutes. Check the drain hose for kinks and clogs.
3.3 Memory function:
When shut off normally, the unit will retain humidistat
values set by the user. If power is interrupted, the unit
will default to 60% RH.
4. Sensor Errors
If the humidity sensor fails, the humidity cannot be set, it
automatically switches to continuous dehumidification.
The display shows the humidity sensor fault with code
E3. If the coil probe fails, the unit will not operate, and
the display will show E5. See "Error Codes" table below.
5. Accumulated working time
When the power button is on, the timer starts to count by
minute. After powering off and restarting, the timer count
resumes. The memory of accumulated time is
permanent and cannot be reset. Time data is written into
the memory every 10 minutes, and the accumulated
maximum time is 99999 hours and 59 minutes.
6. Dehumidification icon
In the dehumidification mode, the dehumidification icon
displays while the compressor is operating. The
dehumidification icon flashes when the compressor is
not working, such as during defrost mode.