CMN

Minimum collector tempera-
ture adjustment range  

 

-10 ... 90 °C 
Factory setting 10 °C

CMX: 

 

Maximum collector temp. 
Adjustment range  
100 ... 190 °C 
Factory setting120 °C

4.1.10 System cooling 

If the selected maximum store temperature is reached, the 
solar system switches off. If then the collector temperatu-
re rises to the selected maximum collector temperature 
(

CMX

), the solar pump remains activated until the collector 

temperature falls below the temperature limit value. The 
store temperature might continue to rise (up to the maxi-
mum store temperature), but only until 95 °C (emergency 
shutdown of the store). If the store temperature is higher 
than the maximum store temperature (

S MX

) and the col-

lector temperature is lower by at least 5 K than the store 
temperature, the solar system remains activated until the 
store is again cooled down by the collector and the pipes 
to the selected maximum temperature (

S MX

). 

In case of active system cooling   is shown on the display 
(flashing). Thanks to the cooling function the solar system 
can be kept running for longer periods on hot summer days 
and cooling of the collector and the heat transfer medium 
is ensured as well.

OCX

:  

Option system cooling 
Adjustment OFF ... ON 
Factory setting OFF

4.1.11   Option minimum collector limit

OCN: 

 

Minimum collector limit 
Adjustment range OFF / ON 
Factory setting OFF

The minimum collector temperature is a minimum switching 
temperature, which must be exceeded to allow the solar 
pump  (R1/R2)  to  switch  on. The  minimum  temperature 
will prevent overswitching of the solar pump (or solid fuel 
boiler charging pumps) at low collector temperatures. If the 
minimum temperature is underrun, 

 (flashing) is shown 

on the display.

CFR

Antifreeze temperature 
Adjustment range  

 

-10 ... 10 °C 
Factory setting 4,0 °C

4.1.12   Option antifreeze function

OCF: 

 

Antifreeze function 
Adjustment range  

 

OFF / ON 
Factory setting OFF

The antifreeze function activates the loading circuit between 
collector and store if the selected antifreeze function is 
underrun in order to protect the medium from freezing or 
thickening. If the selected antifreeze temperature is excee-
ded by 1 °C, the loading circuit will be deactivated.
Please note:
As there is only a limited heat quantity of the store available 
for  this  function,  the  antifreeze  function  should  only  be 
used in regions with few days of temperatures around the 
freezing point.

4.1.9 Collector temperature limit  

Collector emergency shutdown

If the selected collector limit temperature (

EM

) is exceeded, 

the solar pump (R1/R2) is deactivated to avoid overheating 
of the solar components (collector emergency shutdown). 
The limit temperature is set to 140 °C but it can be changed 
within the adjustment range of 110 ... 200 °C. In the display  

 (flashing) is shown.

EM

Collector temperature limit 
Adjustment range 

 

110 ... 200 °C, 
Factory setting 140 °C

Summary of Contents for SHR 521 20

Page 1: ...uying a Drayton product Please read this manual carefully to get the best perfomance from this unit Drayton SHR 521 20 Installation Commissioning Operation Fault nding Examples SHR 521 20 manual B 490...

Page 2: ...e following security advice in order to avoid danger and damage to people and property Instructions Attention should be paid to the statutory provisions for prevention of industrial accidents to the s...

Page 3: ...tus and operating control lamp Operation by 3 pushbuttons on the front of the housing Functions Temperature differential controller with optional system func tions System monitoring according to BAW g...

Page 4: ...521 20 Drayton 06334 SHR 521 20 monen indd 4 Examples SHR 521 20 Please nd detailed con nection diagramms for these systems in chap ter 1 Standard solar systems Solar systems with dual mode DHW cylin...

Page 5: ...before opening the housing 1 2 Electrical wiring The power supply to the controller must only be made by an external mains switch last step of installation and the mains voltage must be 220 240Volt 50...

Page 6: ...nder with 1 store 3 sensors and backup heating The sensor S4 TRF can optionally be used for heat quantity balancing Arr 2 1 2 2 Allocation of terminals for system 2 Symbol Speci cation S1 collector se...

Page 7: ...rd key 1 is used for scrolling forward through the menu or to increase the adjustment values The backwards key 2 is accordingly used for the reverse function To con rm the current mode hold down butto...

Page 8: ...rs with collector sensor Pump 3 way valves The ow direction or the current breaking capacity are always shown Heating circuit Store 1 and 2 with heat exchanger Back upheat with burner symbol Temperatu...

Page 9: ...pply must be activated The controller passes an initialisation phase in which the operating control lamp ashes red and green When the initialisation is complete the controller is in automatic operatio...

Page 10: ...return ow 11 S4 Temperature sensor 4 11 h P x Operating hours relay 1 11 h P1 x Operating hours relay 1 11 h P2 x Operating hours relay 2 11 kWh Heat quantity kWh 12 MWh Heat quantity MWh 12 Arr 1 2 S...

Page 11: ...mperatures display range 40 250 C 4 1 4 Indication of other temperatures Shows the current temperature of the sensor TRF temperature return ow TRF other measured temperatures display mode 40 250 C 4 1...

Page 12: ...eze Adjustment range 0 3 Factory setting 1 MED Concentration of antifreeze in Vol MED is blinded out by MEDT 0 and 3 Adjustment range 20 70 Factory setting 45 The heat quantity transferred is calculat...

Page 13: ...exceeded a further loading of the store is stopped so that a damaging overheating can be avoided If the maximum store temperature is exceeded is shown on the display Please note The controller is equi...

Page 14: ...ctor limit Adjustment range OFF ON Factory setting OFF The minimum collector temperature is a minimum switching temperature which must be exceeded to allow the solar pump R1 R2 to switch on The minimu...

Page 15: ...actory setting OFF 4 1 13 Recooling function If the selected maximum store temperature S MX is reached the solar pump remains activated to avoid overheating the collector The store temperature might c...

Page 16: ...g adjustments can be made 4 1 16 Operating mode HAND HND1 HND2 Operating mode OFF relay off ashing AUTO relay in automatic operation ON relay on ashing HAND HND1 HND2 Operating mode Adjustment range O...

Page 17: ...f the control lamp goes out o k no The can fuse of the controller is defective It can be replaced after removal of the front cover spare fuse is enclosed in the accessory bag Operating control lamp as...

Page 18: ...calci ed yes Control replace Decali cation no Heat exchanger blocked yes no Cleaning Heat exchanger too small yes New calculation of the dimension no Check collector special function Change Ton and To...

Page 19: ...mp start up in manual operation yes There is no current check fuses replace them and check power supply The selected temperature difference for starting the pump is too high choose suitable setting no...

Page 20: ...tning Sensors Our product range includes high precision platinum tem perature sensors atscrew sensors ambient temperature sensors indoor temperature sensors cylindrical clip on sensors and irradiation...

Reviews: