Set Payload version
This is the first byte of the uplink payload. RS485-LN can connect to different sensors. User can set the PAYVER
field to tell server how to decode the current payload.
•
AT Command:
AT+PAYVER:
Set PAYVER field = 1
•
Downlink Payload:
0xAE 01
--> Set PAYVER field = 0x01
0xAE 0F
--> Set PAYVER field = 0x0F
Set RS485 Sampling Commands
AT+COMMANDx or AT+DATACUTx
These three commands are used to configure how the RS485-LN polling data from Modbus device. Detail of usage
•
AT Command:
AT+COMMANDx:
Configure RS485 read command to sensor.
AT+DATACUTx:
Configure how to handle return from RS485 devices.
•
Downlink Payload:
0xAF
downlink command can be used to set AT+COMMANDx or AT+DATACUTx.
Note
: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
Format: AF MM NN LL XX XX XX XX YY
Where:
• MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~ 0F,
• NN: 0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
• LL: The length of AT+COMMAND or AT+DATACUT command
• XX XX XX XX: AT+COMMAND or AT+DATACUT command
• YY: If YY=0, RS485-LN will execute the downlink command without uplink; if YY=1, RS485-LN will execute
an uplink after got this command.
Example:
AF 03 01 06 0A 05 00 04 00 01 00
: Same as AT+COMMAND3=0A 05 00 04 00 01,1
AF 03 02 06
10
01
05 06 09 0A
00
: Same as AT+DATACUT3=
16
,
1
,
5+6+9+10
AF 03 02 06
0B
02
05 07 08 0A
00
: Same as AT+DATACUT3=
11
,
2
,
5~7+8~10