Device rejoin in at the second uplink packet.
Issue describe as below:
Cause for this issue:
The fuse on LSE01 is not large enough, some of the soil probe require large current up to 5v
800mA, in a short pulse. When this happen, it cause the device reboot so user see rejoin.
Solution:
All new shipped LSE01 after 2020-May-30 will have this to fix. For the customer who see this
issue, please bypass the fuse as below: