9023744 - 3rd edition - October 2005
Fault – Cause – Remedy
Fault – Cause – Remedy
Should it not be possible to eliminate the malfunctions occurring by employing the remedial measures described, or should
other faults occur:
Transmitter resp. Sensing head SE Ex: check and, if necessary, arrange repair by trained service personnel.
Fault
Cause
Remedy
No Display
Cable faulty
Check cable to central controller.
Transmitter resp. sensing head can no
longer be calibrated
Ex-sensor faulty or poisoned
Replace Ex-sensor, page 22.
Measurement current fluctuates with
approx. 1 Hz between 2.5 mA and 5 mA
Sliding switch set to "1" = cal or "2" =
test
Set sliding switch to "0" = normal.
Measurement current less than 3.0 mA
Sensor connection interrupted or Ex-sen-
sor defective
Replace Ex-sensor, page 22.
Measurement signal extremely negative
Calibrate transmitter resp. sensing head,
page 15 or page 16.