69
14.5.2 DNP V3.0 Implementation Table
The following table identifies which object variations, function codes, and qualifiers the NetGuardian SUI
supports in both request messages and in response messages. For static (non-change-event) objects,
request send with qualifiers 00, 01, 06, 07, or 08 will be responded with qualifiers 00 or 01.
OBJECT
REQUEST
(Library w ill parse)
RESPONSE
(Library w ill respond w ith)
Object
Num ber
Variation
Num ber
Description
Function Codes
(dec)
Qualifiers Codes
(hex)
Function
Codes (dec)
Qualifiers
Codes (hex)
1
1
Binary Input
1
(read)
00, 01
(start-stop)
06
(no range, or all)
129
(response)
00, 01
(start-stop)
10
2
Binary Output Status
1
(read)
00, 01
(start-stop)
06
(no range, or all)
129
(response)
00, 01
(start-stop)
12
1
Control Relay Output
Block
5
(direct op)
6
(dir. op, noack)
17, 28
(index)
129
(response)
echo of request
30
3
32-Bit Analog Input
Without Flag
1
(read)
00, 01
(start-stop)
06
(no range, or all)
129
(response)
00, 01
(start-stop)
50
1
Time and Date
1
(read)
07
(limited qty = 1)
129
(response)
07
(limited qty = 1)
2
(write)
07
(limited qty = 1)
60
1
Class 0 Data
1
(read)
06
(no range, or all)
60
2
Class 1 Data
1
(read)
06
(no range, or all)
60
3
Class 2 Data
1
(read)
06
(no range, or all)
60
4
Class 3 Data
1
(read)
06
(no range, or all)
Summary of Contents for D-PK-NGSUI