Dovre 525MF Installation Instructions And Operating Manual Download Page 5

A draught/vacuum of 15 - 20 Pa during normal
operation is ideal.

Starting from the flue spigot, the flue must run as
vertically as possible. Changes in direction and
horizontal pieces disrupt the outward flow of
combustion gases and may cause soot deposits.

To prevent combustion gases from cooling down
too much, which reduces the draught, ensure that
the interior diameter is not too big.

The flue or chimney should ideally have the same
diameter as the connection collar.

For the nominal diameter: see the appendix
"Technical data". If the smoke channel is well
insulated, the diameter may be slightly bigger
(up to 2x the section of the connection collar).

The section (area ) of the smoke channel must be
constant. Wider segments and (in particular)
narrower segments disrupt the outward flow of
combustion gases.

When using a cover plate or exhaust hood : make
sure that the cover does not restrict the flue outlet
and that the cap does not impede the outward flow
of combustion gases.

The flue must end in a zone that is not affected by
surrounding buildings, trees or other obstacles.

The flue outside the house must be insulated.

The chimney must be at least 4 metres high.

As a rule of thumb: 60 cm above the ridge of the
roof.

If the ridge of the roof is more than 3 metres away
from the flue: stick to the measurements in the
following figure. A = the highest point of the roof
within a distance of 3 metres.

Ventilation of the area

For good combustion, the stove needs air (oxygen).
This air is supplied via adjustable air inlets from the
area in which the stove is installed.

The combustion will be incomplete in case of
insufficient ventilation, which results in toxic
gases being produced and spread through the
area.

As a rule of thumb, the air supply should be 5,
5 cm²/kW. Extra ventilation is needed when:

The stove is in an area that is well-insulated.

There is mechanical ventilation, for example a
central extraction system or an extraction hood in
an open kitchen.

You can provide extra ventilation by having a
ventilation louvre fitted on the outside wall.

Make sure that other air consuming appliances (such
as tumble-driers, other heating appliances or a
bathroom fan) have their own supply of outside air, or
are switched off when you use the appliance.

You can also connect the appliance to an
outside air supply. A connection kit is supplied
for this purpose. This makes additional
ventilation unnecessary.

Floors and walls

The floor on which the appliance is placed must have
sufficient bearing capacity. For the weight of the
appliance, see the appendix "Technical data".

Protect flammable flooring from heat radiation
by means of a fireproof protective plate. See
the appendix "Distance from combustible
material".

Remove combustible material such as
linoleum, carpets/rugs and similar materials
below the fireproof protective plate.

Keep sufficient distance between the
appliance and combustible materials such as
wooden walls and furniture.

The connecting tube also radiates heat. Ensure
that there is sufficient distance or a shield
between the connecting tube and combustible

Subject to change because of technical improvements

5

Summary of Contents for 525MF

Page 1: ...HOUTKACHEL INSTALLATION INSTRUCTIONS AND OPERATING MANUAL WOOD STOVE INSTALLATION ET MODE D EMPLOI POELE A BOIS EINBAUANLEITUNG UND GEBRAUCHSANWEISUNG HOLZ FEUERST TTE INSTRUCCIONES DE INSTALACI N Y...

Page 2: ...9 Fuel 9 Lighting 9 Burning wood 10 Burning brown coal briquettes 11 Burning anthracite coal 11 Controlling combustion air 11 Extinguishing the fire 12 Removing ashes 12 Fog and mist 13 Solving proble...

Page 3: ...RE cannot be held liable for any problems or damage resulting from incorrect installation Observe the following safety regulations when installing and using the appliance In this manual you can read h...

Page 4: ...ance is installed If ventilation is insufficient combustion will be incomplete resulting in toxic gases being produced and spread through the room See the chapter Installation requirements for more in...

Page 5: ...oxygen This air is supplied via adjustable air inlets from the area in which the stove is installed The combustion will be incomplete in case of insufficient ventilation which results in toxic gases...

Page 6: ...becomes warm during use a glove has been supplied which you may use to protect your hand The appliance is suitable for connection to outside air supply The appliance comes standard with a connection...

Page 7: ...hamber improving combustion and they can withstand burning anthracite coals Cast iron inner plates protect the combustion chamber and dissipate heat to the surroundings 5 1 1 6 4 7 3 4 2 09 20020 041...

Page 8: ...0008 007 1 2 3 4 5 Preparing the outside air connection If the appliance is installed in a room without sufficient ventilation you can install the connecting kit on the appliance for the supply of out...

Page 9: ...t least 2 years Saw the wood to size and split it while it is still fresh Fresh wood is easier to split and split wood dries more easily Store the wood under a roof where the wind has free access Do n...

Page 10: ...y air inlet of the appliance see the following figure 5 Allow the fire develop into a good blaze until there is glowing bed of charcoal You can then add fuel and adjust the appliance see the chapter S...

Page 11: ...l briquettes on the charcoal bed 4 Close the door 5 Regularly remove ashes from the stove base riddling the grate Use the cold handle to operate the riddling rod Burning anthracite coal Always close t...

Page 12: ...pen the primary air inlet for the time being if the air supply by the secondary air inlet is inadequate or if you want to fan the fire It is better to add a small amount of logs regularly than to add...

Page 13: ...e your chimney checked and maintained At the beginning of the heating season have the chimney swept by an expert During the heating season and after the chimney has not been used for a long time have...

Page 14: ...ass in the appliance is broken or cracked it must be replaced before you can use the appliance again Make sure that no stove window cleaner runs between the glass and the cast iron door Lubrication Al...

Page 15: ...g s 3 9 g s Flue gas temperature measured in the measurement section 288 C 298 C 299 C Temperature measured at the appliance outlet 396 C 385 C 402 C Minimum draught 12 Pa 12 Pa 12 Pa CO emission 13...

Page 16: ...Appendix 2 Measurements 525MF 09 20020 108 16 Subject to change because of technical improvements...

Page 17: ...ible material 2 Incombustible material thickness 100 mm Please note To guarantee the flow of combustion air when no outside air connection is provided the distance from the outside air connection coll...

Page 18: ...reproof protective plate A B B 09 20002 004 Minimal dimensions of fireproof protective plate A mm B mm Din 18891 500 300 Germany 500 300 Finland 400 100 Norway 300 100 18 Subject to change because of...

Page 19: ...osit hermetically tight no chinks Chimney stack incorrect Sufficiently high above the roof no obstacles in the vicinity Air inlets set incorrectly Open the air inlets completely Stove connected to the...

Page 20: ...ction diameter 15 connection to 8 height 5 sweep 13 Chinks in appliance 14 Clean glass 14 Cleaning appliance 13 Coal ash content 9 Combustible material distance from 17 Connection measurements 16 Conn...

Page 21: ...cast iron 7 chamotte 7 Inner plates fire resistant remove 7 Installation measurements 16 K Kindled fire 9 Kindling 19 L Lighting 9 Lubricant 14 Lubricate 14 M Maintenance chimney 13 clean glass 14 cle...

Page 22: ...supply of outside air 8 rule of thumb 5 Ventilation louvre 5 Vermiculite inner plates 7 W Walls fire safety 5 Warning chimney fire 4 9 12 combustible materials 4 fireproof inner plates 9 glass broken...

Reviews: