Dovre 2000CBBS Installation Instructions & Operating Manual Download Page 7

2000CB

                                                             7                                                 

03.27997.000

 

3.2.       Preparation 

Please inspect the fireplace for damage caused during transport immediately after 
delivery and notify your distributor in case there are any defects. Do not put the ap-
pliance into operation in the meantime. 
In order to avoid damaging the fireplace during installation and to make its handling 
easier, it is recommended to remove previously all loose parts (fire-resistant bricks, 
grille, ashtray, ...) from the stove. Note the location of those parts while removing 
them, so that you have no difficulties in re-assembling the parts later on.   
The stove will be supplied with the following parts: 

A set of legs 

A smoke dome with fixing material 

A flue collar with fixing material 

A “cold handle” to open the door 

An ashtray (option) 

3.2.1.    Assembly of the legs 

Carefully tilt the appliance onto its backside .  
Fix the leg holders on the bottom plate with nut M8 
and collar Ø8xØ17. 

 

Adjust the height of the leg on the holder with bolt 
M8x50, nut M8 and both collars Ø8xØ25. 
Fix the adjustment bolts under the legs. These will 
allow to adjust the fireplace level.  

3.1.4.    Combustible material round the fireplace 

Within the radiation area of the fireplace 

Assure a distance of at least 80 cm between the opening of the fireplace and com-
bustible material. That distance may be reduced to 40 cm if the combustible mate-
rial is sufficiently shielded and well ventilated.   

Outside the radiation area of the fireplace 

Assure a distance of at least 5 cm between the mantle built 
around the fireplace and combustible material. A small sur-
face contact between combustible material and the mantle 
(e.g. wall cladding) is allowed if the mantle of the fireplace 
is sufficiently insulated.  
A wooden ornamental rafter must not be installed within 
the radiation area of the fire. Outside the radiation area, 
there must always be a ventilation gap of 1 cm all around 
to prevent heat from building up (see picture). 
No combustible material must be present within 50 cm from the convection outlet 
areas.  

min 1 cm 

min 1 cm 

Summary of Contents for 2000CBBS

Page 1: ...INSTALLATIEVOORSCHRIFTEN EN GEBRUIKSAANWIJZING INSTALLATION ET MODE D EMPLOI INSTALLATION INSTRUCTIONS AND OPERATING MANUAL EINBAUANLEITUNG UND GEBRAUCHSANWEISUNG INBOUWHAARD FOYER FIREPLACE KAMINEINS...

Page 2: ...moval 38 4 6 Extinguishing the fire 38 4 7 Weather conditions 39 5 Maintenance 39 Annex 1 Technical data sheet 52 Annex 2 Dimensions 53 Inhalt pag Vorwort 40 1 Einleitung 40 2 Sicherheit 40 3 Montagev...

Page 3: ...ke the long term and trouble free functioning of your heater for granted Please consult an expert when installing and connecting the heater The manufac turer cannot be held liable for problems caused...

Page 4: ...ught is caused by environmental phenomena such as wind It is prohibited to connect several heaters to one chimney for instance the central heating boiler unless local or national regulations allow thi...

Page 5: ...pt the combustion process and cause the smoke flow through the chimney to be interrupted which may lead to smoke emissions into the room Mainly in case of a fireplace together with the combustion gase...

Page 6: ...e and the walls around it must not contain electric wires The appliance shall be installed on floors with an adequate load bearing capacity Under the appliance Under the appliance any combustible mate...

Page 7: ...t the height of the leg on the holder with bolt M8x50 nut M8 and both collars 8x 25 Fix the adjustment bolts under the legs These will allow to adjust the fireplace level 3 1 4 Combustible material ro...

Page 8: ...either horizon tally or vertically Fix the flue collar on the smoke dome with 2 bolts M6x30 2 nuts M6 and 4 collars 6x 12 Assure proper sealing with kit or paste 3 2 3 Installation of the ashtray if...

Page 9: ...pening is 250 cm The grids may be installed on all sides It is important that air flows freely into the convection chamber If you use an air vent to convey outside air into the convection chamber reme...

Page 10: ...other auxiliary material such as steel it will not function as a heat bridge The picture on the next page shows an example of fireplace installation within com bustible material 3 4 Finishing When the...

Page 11: ...e wall Convection area Fresh air inlet Fireproof floor Combustible floor Convection air inlet Insulation if necessary Convection Air outlet Opening against eventual pressu re buildup Stainless steel p...

Page 12: ...than twenty pe r cent moisture Wet logs are unsuitable for burning as they do not produce enough heat and all of the energy is lost in the process of evaporation Moreover the burning of wet wood cause...

Page 13: ...cause tar and creosote to deposit in the chimney after a long pe riod of time Tar and creosote are highly combustible substances Thicker layers of these substances might catch fire when the t emperatu...

Page 14: ...glass can be cleaned with a number of glass cleaning products available on the market Your installer can also supply you with appropriate products However never use abrasive or corrosive cleaning pro...

Page 15: ...e Hout Bois Wood Holz Maximale lengte houtblokken Longueur maximale des b ches Maximal length of logs Maximal L nge der Holzblocken 40 cm Schoorsteenaansluiting diameter Raccordemant chemin e diam tre...

Page 16: ...2000CB 16 03 27997 000 Bijlage 2 afmetingen Annexe 2 dimensions 2000CB GL 2000CB BS Annex 2 dimensions Anlage 2 Abmessungen...

Page 17: ...2000CB 17 03 27997 000...

Page 18: ...ntinuous product improvement specifications of the delivered product may differ from the con tent of this booklet without further notice Im Rahmen kontinuerlicher Produktverbesserung k nnen Specifikat...

Page 19: ......

Page 20: ...E O E...

Reviews: