The Sensor Status is shown at the bottom of the screen.
Status Icon:
Green
: No alarm
Yellow
: Alarm is active and it has been acknowledged
Red
: Alarm is active and it has not been acknowledged
Use the
Edit
button to make changes to the sensor configuration.
The
Delete
button will erase the sensor configuration from the system.
7.3 Wireless
Select the Wireless icon to configure RF sensors in your system.
1. Enter the
id number
of the sensor (e.g. 1,2,3 etc)
2. Enter a
Name
for the sensor (up to 30 characters).
3. Enter the
Serial number
of the sensor as shown on the sensor body.
4. Use the
Has Water Float
slide button to identify a sensor with a water float.
5. Select the
Location
of the sensor (select the tank, manhole or sump).
6. Enter the
Product offset
.
7. Select a
Relay
to start when a
high product
alarm is sensed.
8. Enter the
Water offset.
This will be available only when the
“Has water float”
slide button is toggled
to the on position.
9. Select a
Relay
to start when a
high water
alarm is sensed.
M2051-EU Rev.: 1 Dover Fueling Solutions