Power 24VAC
WNG-2133-
BacNet to Douglas Gateway
White
Blue
xx
NE
T A
Ea
rth
NE
T B
RS
-485 B
System
Selector
MC6000 System
W2000 System
RS
-485 A
LonWorks FTT-10
Data Signal
Service
Wink
This device links external BacNet based system to a
Douglas W-2000 LonWorks based Lighting Control System
or to a Douglas MC-6000 System. The WNG-2133 permits
the external system to switch relay groups, obtain status of
relay groups, switch individual relays and obtain status of
individual relays. The programming of relay groups is done
within the Douglas system using the Douglas user
interface. For detailed information regarding setup and
installation of this device, refer to the WNG-2133
Application Manual.
Self Configured System
WRS-2224: Nodes 24 to 13
WNS-2308: Nodes 8 to 1
Groups: All inherent to the
WRS-2224 and WNS-2308 devices
ü
WNS-2150 Configured System
WRS-2224: Nodes 1-10
Groups: ALL
WRS-2224: Nodes 11-30
Groups: None
WRS-2224: Nodes 31-50
Groups: None
WRS-2224: Nodes 51-70
Groups: None
Parts
BACnet Gateway: Directions & Applications
page 2
lighting controls
side view
Selector Switch,
Douglas System
·
Toggle to select type of
Douglas system that is to
be connected to the
BACnet system.
·
Pressing left side selects
the MC-6000 System,
pressing right side selects
the W-2000 System.
Data Signal, Douglas
MC-6000 System
·
RS-485 data signal from
the Douglas MC-6000
System, if used.
·
Socket plugs into a MC-
6210 Panel Control Card
that has a BACnet encoder.
Service Pin & LED,
Douglas W-2000
System
·
The Service LED flashes
as a diagnostic aid.
·
Pressing the Service Pin
transmits WNG-2133
data to a W-2000
network, if connected.
Douglas System
Identification Label
·
Generally supplied at the
factory.
·
Other label, as shown below,
can be supplied for a MC-
6000 System.
Power Connections
·
24VAC
BACnet Data Signal
Connection
·
IP from the external BACnet
system.
·
Data signal cable, which plugs
into socket on side, is CAT-5e.
Wink Pin & LED,
Douglas W-2000
System
·
The Wink LEd flashes,
when prompted by the
W-2000 network, to
identify unit.
·
Pressing the WInk Pin
disables the WInk LED.
Data Signal Connection,
Douglas W-2000
System
·
FTT-10 (78kbs) data signal
from the the Douglas W-
2000 LonWorks lighting
control system, if used.
·
Wiring type is twisted pair,
unshielded, #16 AWG
Belden.
MC-6000 Configured System
Relay Group Assignments
MC-6000
Group #s
Individual Relay Assignments
BacNet
Variables
BacNet
Variables
MC-6000
Node# Relays