FTT-10 (78kbs) data signal
from the Douglas W-2000
LonWorks lighting control
system, if used.
·
Wiring type is twisted pair,
unshielded, #16 AWG Belden
.
24VAC Transformer
Connections
WNG-2133 Bacnet to Douglas System Gateway
Introduction
BACnet Gateway: Directions & Applications
lighting controls
·
Wink LED flashes, when
prompted by network, to
identify unit.
·
Pressing the Wink pin disables
the Wink LED.
page 1
BACnet Data Signal
Connection
·
IP from the external BACnet
system.
·
BACnet data signal cable is
CAT-5e and plugs into the
socket on the right side:
side view
Data Signal Connection,
Douglas W-2000 System
Wink LED & Pin
Douglas W-2000 System
·
Service LED flashes as
diagnostic aid.
·
Pressing the Service pin
transmits WNG-2133 data to
the W-2000 network.
Service LED & Pin
Douglas W-2000 System
Selector Switch, Douglas
System
·
Toggle to select type of Douglas
System to be connected to
BACnet network.
·
Pushing switch to left selects
MC-6000 system, pushing
switch to right selects W-2000
system.
·
RS-485 data signal from the
Douglas W-2000 LonWorks
lighting control system, if used.
·
Socket plugs into a MC-6000
GTW Panel Control Card, which
is equipped with a BACnet
encoder.
Data Signal Connection,
Douglas MC-6000 System