electrical and fragrance planning advice
use this checklist to verify that you have all the information you need from your SeNSORY SKY
ATT
consultations.
The following items are particularly important:
Maximum distance between fragrance modules and ceiling installation enclosure for rain panel: 12 m
Maximum vertical height between fragrance modules and ceiling installation enclosure for rain panel: 4 m
Max. distance between the fragrance modules and the sub-distribution board: 1 m
Max. distance between the ceiling installation enclosure for rain panel and the sub-distribution board: 12 m
The fragrance modules have to installed outside the wet zone in an accessible area. They must not be installed above
the sub-distribution
Space required for frangrance modules: 1000 x 210 x 140 mm (overall dimensions). We recommend installation using
xGrid track art. no. 12 320 970 90
Space required for all components in the sub-distribution board: approx. 500 x 500 mm (internal dimensions)
The ethernet cable from the SENSORY SKY
ATT
is to end up in the sub-distribution board. A network outlet according
to TIA 568A is necessary to connect SENSORY SKY
ATT
to a network. The local network has to be behind a router with
firewall.
The customer must provide ductwork acording to the planning guide
Equipotential bonding 2 x 4 mm² for ceiling installation enclosure for rain panel and concealed rough part eVALVE
(hand shower set) have to be provided by the customer
The total length of all connecting cables (from ceiling installation enclosure for rain panel to concealed rough part eVALVE
to control elements until the control module fragrance in the sub-distribution board) must not be longer than 30 m
Install the terminating resistor on the last element in the loop connected via connecting cables
Hole diameter 56 mm for concealed rough parts for electronic control elements
The installation of the connecting
cable and concealed rough parts for electronic control elements has to occur at the
same time that the pre-wall is closed
Fasten Connecting cables in the pre-wall (via cable ties) Be sure to leave enough cable in front of cable tie for later
connection
The customer must provide the following circuit-breakers and electrical components
- earth leakage circuit breaker (30 mA, 2-pin, type A)
- Safety cutout (6 A, type B),
- 3 x circuit breaker (16A, Type 1S)
- equipotential bonding busbar in subdistribution board
- equipotential bonding (4 mm²) for concealed rough part eVALVe (hand shower set)
electrical installation in accordance with VDe 0100. Please conform to national statutory regulations, where different