-55-
P7.04
Running state display 2
0000~FFFF
0
☆
If a parameter needs to be displayed at running, set the corresponding bit to 1, and set P7.04 to the
hexadecimal equivalent of the binary number.
These two parameters are used to set the parameters that can be viewed when the inverter is in the
running state. You can view a maximum of 32 running state parameters that are displayed starting
from the lowest bit of P7.03.
P7.05
Stop state display
0000~FFFF
33
☆
If a parameter needs to be displayed at running, set the corresponding bit to 1, and set P7.04 to the
hexadecimal equivalent of the binary number.
P7.06
Load speed display
coefficient
0.0001~6.5000
1.0000
☆
This parameter is used to adjust the relationship between the output frequency of the inverter and the
load speed. For details, see the description of P7.12.
P7.07
Heatsink temperature of
inverting module
0.0
℃
~100.0
℃
12
℃
●
It is used to display the insulated gate bipolar transistor (IGBT) temperature of the inverter, and the
IGBT overheat protection value of the inverter module depends on the model.
P7.08
Rectification module
temperature
0.0
℃
~100.0
℃
0
℃
●
P7.09
Accumulative running time
0h~65535h
0h
●
It is used to display the accumulative running time of the inverter. After the accumulative running
time reaches the value set in P8.17, the terminal with the digital output function 12 becomes ON.
P7.10
Product number
Inverter product number
-
●
P7.11
Software version
Software version of control board
-
●
15
14
13
12
11
10
9
8
Linear speed
Communication
Encoder speed
Power-on time
(Hour)
Running time
(Min)
Input pulse frequency
(Hz)
X
Y
7
6
5
4
3
2
1
0
PID
feedback
Remaining running time
PLC
phase
Input pulse frequency
(kHz)
Running frequency
2 (Hz)
AI1
voltage
before correction
(V)
AI2
voltage
before correction
(V)
AI3
voltage
before correction
(V)
7
6
5
4
3
2
1
0
DI
status
set
frequency
(Hz)
bus
voltage
(V)
DO
status
AI1
voltage
AI2
voltage
AI3
voltage
counter
15
14
13
12
11
10
9
8
Length
reserved
reserved
reserved
PLC
phase
Load speed
PID
setting
Input pulse frequency
(Hz)
(V)
(V)
(V)