Electrical Installation Instructions
1. The reader comes with 16 feet of non-shielded cable. The type of cable used to extend the distance will affect the maximum
distance the reader can be extended.
Switch 2 control board to reader – Maximum cable run = 300 feet (100 m)
2. The micro Reader will be sent out with a RJ45 connector on it. This can be cut off and the cable stripped back ready for wiring.
3. Mount Switch 2 control board into power supply cabinet with stand-offs supplied.
4. Connect reader to control board as shown in Fig. 5. If additional reader is required for in/out operation, wire the reader in
parallel.
5. Reader operates on 12VDC only. Connect reader to power transformer and electric lock as shown in Fig. 6 or Fig. 7.
Note:
Unit requires a filtered and regulated power source for proper operation. See our line of power supplies and transformers for
options to use.
Fig. 3
Fig. 4
Micro Reader surface mounted onto wall using back plate.
The plastic end cap is placed over the exposed end of the reader.
Micro Reader surface mounted onto a hollow wall using the back
plate. The plastic end cap is placed over the base plate.
Fig. 5
Proximity Micro Reader Wiring Diagram
Proximity Slimline Reader Wiring Diagram
Note:
All installations must conform to local fire, National Building, and Life Safety Codes.