background image

12-2020 

 dormakaba Canada Inc. RAC5 MFC Installation Guide – PK3738 | 12 

 

The tamper alarm switch’s polarity is such that when the door is 
closed, the switch itself is also in a closed state. Ensure that the 
wiring to the premise alarm system is done accordingly to 
prevent false alarms. 

4.

 

Wire relay expansion board outputs. Refer to Annex B for sample wiring diagram. 

The relay expansion board provides 8 relay contacts for wiring and control of relay-enabled elevator. The 
board only provides normally open or normally closed dry contacts, so no power is provided by the board. 
As wiring of relay-controller equipment may vary between products, please refer to the product 
manufacturer’s instruction booklet. 

NOTE: 

Refer to Annex B, Figure 8 for specific relay expansion board bypass switches. 

 

If bypass switches are ON, the relays are bypassed and the green LED associated with that relay 
is turned ON 

 

If bypass switches are OFF, the controller PCB can activate the relays. The associated LEDs turn 
ON during relay activation 

 

When the power of the RAC5 MFC is too low (power failure), the controller PCB stops 
functioning and the relays on the controller PCB or the expansion board will return to their 
normal state. The normal state is defined as relays OFF. Any peripheral connected to the relays 
will then be either in a normally open (NO) or normally closed (NC) state, depending on the 
wiring 

5.

 

Install elevator controller. 

Each Expansion board contains 8 dry relay contacts. Up to 8 expansion boards can be used for total 
control of 64 common areas. The relay outputs are at the wiring input of each three-terminal connector 
(NO, COM, NC) on the expansion PCB as well as being indicated on the label on the inside of the door. 
Several floors can be controlled by one relay (one common area). 

The relays in the RAC5 MFC are UL rated and are capable of a maximum switching of 30 VDC @ 1A. For 
time duration of relay state change, please refer to Annex B, Figure 8. 

6.

 

Connect the power adapter. 

NOTE: 

Dependent on the countries’ electrical power requirements, follow the directions below for the 

power adapter required. Refer to Annex B, Figure 8 for detailed wiring. 

a)

 

International Power Adapter 

i.

 

Attach the appropriate AC outlet prong to the power adapter 

ii.

 

Route the power adaptor wires into the enclosure and secure the wire (recommended 
with tie wraps) 

iii.

 

From the inside of the enclosure, crimp the fork terminals supplied in the hardware bad 
to the end of each wire 

iv.

 

Connect the fork-terminated wires to the power supply input as shown in Annex B, 
Figure 8 

b)

 

North America Power Adapter 

i.

 

From the inside of the enclosure, connect one end of the fork-terminated wires to the 
power supply inputs as shown in Annex B, Figure 8 

IMPORTANT

 

Summary of Contents for RAC5 MFC

Page 1: ...RAC5 MFC Installation Guide RAC Install Guide Covers qxp_Layout 1 2021 01 26 3 47 PM Page 1 ...

Page 2: ... Reader s 7 3 1 5 Power Adapter 8 3 1 6 Installation Hard Bag 8 3 1 7 Tools Required not supplied 8 3 2 Exploded View 9 4 System Installation Overview 9 4 1 Pre installation Procedures 10 4 2 Installation and Wiring Procedures 10 5 Annex A Quick Troubleshooting Guide 15 5 1 Power Troubleshooting 15 5 2 Card Reading Troubleshooting 15 5 3 External Inputs Troubleshooting 16 5 4 Relay Expansion Board...

Page 3: ...12 2020 dormakaba Canada Inc RAC5 MFC Installation Guide PK3738 2 11 Annex G Fire Alarm Panel Wiring 21 12 Annex H Reader Drilling Template 22 ...

Page 4: ...tallation of card readers or other peripherals within elevators must only be done with prior consultation of the elevator manufacturer A technician from the elevator manufacturer should always be present for installation Do not connect to a receptacle controlled by a switch If installing the RAC5 MFC in an elevator cage environment or in proximity to any other equipment that may generate high leve...

Page 5: ...t installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interfer...

Page 6: ...s Card Reader can be mounted directly on the inside of the elevator car typically on the elevator call button panel For surface mount the surface area required for the contactless reader is 5 W x 5 H x 2 D 12 7 x 12 7 x 5cm 2 depth behind panel required The RAC5 MFC is an access control solution that can operate 2 individual card readers provides multiple relays and much more as per the feature li...

Page 7: ...g operation E Power Battery Status LEDs Provides visual indication of the operational status of the RAC5 MFC system Battery status LED is only used on battery back up equipped systems F Cam lock with Key To provide secure locking and to control access to the RAC5 MFC enclosure Optional Components G Relay Expansion Board Interface board providing 8 relay outputs that can be used to control relay eq...

Page 8: ... subject to change without notice For letter designations refer to Figure 4 3 1 1 RAC5 MFC Enclosure NOTE All items below come factory installed A RAC5 MFC enclosure with access door B Power Supply 24 VAC 24 VDC input 12 VDC output C Controller PCB D Tamper switch E 2 panel mounted LEDs green for power and battery status F Cam lock 3 1 2 Relay Expansion Board G 8 Relay expansion PCB boards includi...

Page 9: ...z 3 1 6 Installation Hard Bag L 4x Philips wood screw 8 x 1 1 4 M 4x Nylon anchor 6 10 N 4x Concrete anchor 7 9 O 2x Strain relief connector with locking nut P Ring terminal connector Q 5x Steel flat washer 8 R 2x Crimp fork terminals 18 22 AWG 3 1 7 Tools Required not supplied Additional tools may be required dependent on the peripherals being installed The list below covers the installation of t...

Page 10: ...ordered and materials tools required are available Ensure all cabling is available for the peripherals components being installed All installations and wiring of RAC5 MFC enclosure peripherals must comply with all applicable local building codes and regulations and National Electric Code ANSI NFPA 70 Do not connect power to the enclosure until the end of the installation IMPORTANT CAUTION ...

Page 11: ...ld be installed in an obvious location at an ergonomic height near the access door or elevator being controlled The space to use the contactless reader must be large enough to allow for adequate clearance for the card being presented to the reader 3 Install strain relief Strain reliefs are provided in the hardware bag to secure the wires leading into the enclosure and to help prevent the possibili...

Page 12: ...nected In addition the wire used to connect the peripherals to the controller PCB must be of the proper gauge and type as specified by the manufacturer Every wire must pass through a strain relief as connected in the pre installation procedures dormakaba Canada Inc does not provide technical or field support for third party locking devices Please consult the device manufacturer for support NOTE Th...

Page 13: ...heral connected to the relays will then be either in a normally open NO or normally closed NC state depending on the wiring 5 Install elevator controller Each Expansion board contains 8 dry relay contacts Up to 8 expansion boards can be used for total control of 64 common areas The relay outputs are at the wiring input of each three terminal connector NO COM NC on the expansion PCB as well as bein...

Page 14: ... PK3738 13 ii Route the wires out of the enclosure to the AC power source and secure the wires recommended with tie wraps iii Crimp the fork terminals supplied in the hardware bag to the end of the wires and connect them to the power adapter screw terminals ...

Page 15: ...access door LEDs as indicated below and in Annex B Figure 8 NOTE The wires must be connected with the proper polarity Once the terminals are installed they are designed to have a tight fit so removal may damage the LEDs LED Description Location on Door Terminal Connection Terminal Connection Power Status Top Red Orange Battery Status Bottom Red Yellow Ensure that the proper connections are made e ...

Page 16: ...ed RAC5 MFC enclosure s panel door Power Status LED is OFF Verify that the power supply is powered both AC ON and DC ON LEDs are on Verify the LED wiring to the power supply All RAC5 MFC LEDs are OFF Verify that the DC ON LED on the power supply is on Verify that the AC power is active for the wall mount adapter Verify that the RAC5 MFC controller is connected properly to the power supply as per A...

Page 17: ...n the Relay Expansion Board should be off Verify that the RAC5 MFC is not in Passage Mode Relay Expansion Board relays do not activate Activate the manual bypass switches SW1 and SW3 on the Relay Expansion Board and verify that the relays are activated and the corresponding LEDs turn on De activate the manual bypass Verify that the RAC5 MFC controller is active Heartbeat LED D46 should be blinking...

Page 18: ...E J5 TB 3 RD2 Data J12 pin 2 GREEN J5 TB 4 RD1 Data J12 pin 3 WHITE J5 TB 3 RD1 Data J12 pin 4 GREEN J5 TB 4 Controller Board RAC5 Reader Connections Controller Board Contactless Reader Wire connection to back of contactless card reader TB 1 BLACK TB 2 RED TB 3 WHITE TB 4 GREEN 12V GND Power Supply NO C NC NO C NC LOW BATT AC FAIL DC OUT BAT INPUT XFRM 1 2 3 4 1 2 3 4 1 2 3 4 J17 J3 J7 J8 J12 J1 J...

Page 19: ...gramming shielded cables should be used and connections made as per the diagram below Figure 9 Shielded Cable Wall Pluggable Transformer RAC5 Enclosure RAC5 Main PCB Mounting Screw Ingress Reader Egress Reader Power Supply Electrical Connector Shield Wire of Cable Ground Wire Shield Wire of Cable To Ground 1 Use shielded cables for the readers 2 Connect the shield wire of the reader cables to the ...

Page 20: ...12 2020 dormakaba Canada Inc RAC5 MFC Installation Guide PK3738 19 8 Annex D RAC5 MFC Components Figure 10 RAC5 MFC Components ...

Page 21: ...D GND LOW_BATAC_FAIL 4 3 2 1 O N 1 2 3 4 DELAY0 DELAY1 DEVICES TESTMODE SW2 D46 D37 D48 SW1 Reset 10 Annex F Dual Reader Wiring Figure 12 Dual Reader Wiring RAC5 NFC Wall Reader Red Black White Green RAC5 NFC Wall Reader 1 2 3 4 1 2 3 4 1 2 3 4 J17 J3 J7 J8 J12 J1 J15 J16 J6 J18 J19 RAC5 MFC PCB NO NC CO M GND F IRE GND 12V _LCK 1 GND 1 2V NO NC CO M RE_UNL 2 GND RE_UNL 1 1 2 3 4 1 2 3 4 1 2 3 2 1...

Page 22: ...5 Lite or RAC5 XT are connected to a Fire Alarm Panel it must be connected to a Normally Closed dry contact output 1 2 3 4 1 2 3 4 1 2 3 4 J17 J3 J7 J8 J12 J1 J15 J16 J6 J18 J19 RAC5 MFC PCB NO NC CO M GND F IRE GND 12V _LCK 1 GND 1 2V NO NC CO M RE_UNL 2 GND RE_UNL 1 1 2 3 4 1 2 3 4 1 2 3 2 1 1 2 3 12_LCK 2 GND 1 2 3 4 PWRGND GND PWR RD 1 RD 2 READER 2 READER 1 1 2 3 4 J11 REX2 GND TAMPER GND DOO...

Page 23: ...12 2020 dormakaba Canada Inc RAC5 MFC Installation Guide PK3738 22 12 Annex H Reader Drilling Template Figure 15 Reader Drilling Template not to scale ...

Page 24: ...dormakaba Canada Inc www dormakaba us RAC Install Guide Covers qxp_Layout 1 2021 01 26 3 48 PM Page 4 ...

Reviews: