Leading mullion pressure switch (if fitted)
• With the door operating, press the leading mullion
buffer at position A as shown in Fig 4 and verify
that the door stops
• Repeat the test in position B
Automatic operation
• Test the door operation by walking toward the door,
which should begin to rotate of accelerate to normal
operating speed when you reach not less than 1000mm
from the threshold (Fig 5)
• The door should continue to rotate for sufficient time
to allow the user to pass completely through the door
• Repeat for other entrance
Manual operation
• With the door stationary, test by pushing the door in
its direction of rotation (fig 6)
Power Assisted operation
• Test by pushing the door in its direction of rotation (fig 7)
• On removal of hand pressure the door should stop
• Test by pushing the door in its direction of rotation (fig 7)
General tests
• Check there are no hazards due to crushing, shearing,
impact and drawing-in
• Check that the door speed is not likely to increase the
risk of impact
• Check the door area does not present tripping or
slipping hazards
• Check all door panels for broken/cracked glass
• Check all doors have correct warning and
information signs displayed
• Check operation of manual or remote activation
• Check operation of all emergency stop buttons if fitted
• Check for distractions and obstructions in the vicinity of
the doors
Daily checks -
facility operator
Manual revolving door
If you have questions about any of the above items,
please contact dormakaba UK Service. Safety devices
for all doors should be checked by an ADSA qualified
technician at least once a year.
If you have a problem you cannot correct, turn off the
door and call your local dormakaba on 0800 212 3800.
REVOLVING DOOR LOG BOOK