dormakaba 9000 Delayed Egress Exit Device Installation 
Instructions

95011817 (1135-88) IDE-20

01-2020

Exit Device

5

Basic wire connection

1.5  Basic wire connection

1

2

3

4

5

6

7

8

9

10

11

12

DORMA ES100

Minimum 18 AWG

wire recommended for

24VDC inputs (red &

black) leads.

 DORMA ES105

(Power transfer)

    "required"

 * For 24VDC inputs only (red & black wires).

Note: Wire run is from supply to device
and back to the supply.

WIRE   18AWG          16AWG     14AWG      12AWG

FEET            25                 50               75              100 

Maximum Wire Length From Power Supply To 

Device & Back To Supply In Feet x Wire Gage/Size 

Monitoring

Outputs

Control Inputs

CAUTION:

TURN OFF 120VAC POWER PRIOR TO MAKING ANY CONNECTIONS TO TERMINALS

WHITE

BLACK

GREEN

(NEUTRAL)

(HOT)

(GROUND)

   120 VAC

POWER LINE

(1.0 AMP MAX.)

   From UPS

Power Source

Green Ground

Screw Located

On Chassis

    dormakaba MODEL ES100

24 VOLT DC POWER SUPPLY

FUSE

PUSH

TO RESET

CIRCUIT

BREAKER

3.0 AMP

24VDC

3/4 AMP
120VAC

REPLACE WITH 3AG 3/4 AMP

SLO-BLOW TYPE FUSE ONLY

        NO

CONNECTION

ZONE 2

ZONE 1

CONTROL

 SWITCH

CONTROL

 SWITCH

   OUTPUT

TERMINALS

24VDC

   OUTPUT

TERMINALS

24VDC

(+)

(+)

(+)

(+)

(-)

(-)

(IN)

(IN)

(AD100 220V Version Optional)

Note: "The fire alarm contact is to be

used as a supplementary feature and

not intended to replace required fire

alarm appliances".

Specific project or custom wiring diagrams available on re-
quest, consult the 

dormakaba

 techinical service department.

“Product intended for indoor use.”

NOTE:  Always disconnect power prior to making any 
connections or service.

It is recommended that the 120VAC power be supplied 
from an Uninterrupted Power Supply (UPS) to ensure
proper operation during a power failure.
Always observe proper static discharge grounding pro-
cedure's when installing or servicing the DE device.
Wires that interconnect (+) 24Vdc, (-) 24Vdc, authorized
egress/auto reset, and all other secondary connections must
be located within the same room as the panic hardware per

UL294

.

For ULC installations:

 Some 

"Authorities Having Juris-

diction"

 also require an illumination level of 100' feet at

the door, to be provided by the emergency power supply
system.

(12) Wire primary connection

bundle 22" in length.

DPS

(See Page 6 for typical
wiring of control inputs
and monitoring outputs.)

BLACK: (-) 24VDC IN
RED: (+) 24VDC IN
WHITE: AUTHORIZED EGRESS/AUTO RESET

ORANGE: BYPASS/RE-ARM
GREY: DPS N/C
VIOLET: ALARM RELAY COMMON
GREEN: RED OUTPUT EMITTER
BROWN: RED OUTPUT COLLECTOR
BLUE: GREEN OUTPUT EMITTER
YELLOW: GREEN OUTPUT COLLECTOR
PINK: ALARM RELAY N/C
TAN: ALARM RELAY N/O

Grey

Black

(6) Wire secondary connection

bundle 22" in length.

BLACK: NOT USED

RED: TIED TOGETHER WITH

BLUE: 24VDC for acc.

GREEN: FIRE ALARM CONTACT

BROWN: 24VDC for acc.

VIOLET: CHECK EXIT

OTHER DOOR ON PAIRS

Summary of Contents for 9000DE Series

Page 1: ...9000DE Series Delayed Egress Exit Device Installation instructions 95011817 01 2020 EN ...

Page 2: ...Basic wire connection 5 1 6 Key switch operation for device 6 1 7 Cover end cap and label 7 1 8 Pair of doors 9100 DE Delayed Egress Exit Devices x YR09LFSC Electric Trim Fair Secure x ES100 Power Supply x ES105 Power Transfer x 3914W Sounder x MC 4 DPS x Card Readers 8 1 9 Single Door 9300 DE Delayed Egress Exit Device x YR09LFSC Electric Trim Fail Secure x ES100 Power Supply x ES105 Power Transf...

Page 3: ...36 door opening withoutcutting Can be cutto fit a 32 minimum door opening 85 Decibel Alarm Standard LED Status Indicator Standard Nuisance Alarm Standard DIP Switch Settable Key Switch Control Standard Remote Authorized Egress Standard DIP Switch Settable Remote Re Arm Standard Remote Bypass Standard Door Position Input Standard DIP Switch Settable Auto Reset or Manual Reset DIP Switch Settable Au...

Page 4: ...hten Re install filler in rail and reconnect the small pigtail connectors Use caution not to pinch or bind wires Note IfDIPswitch settings are required to be changed do it now prior to re installing filler in rail See Section below 6310D Cam S3 S1 S3 S1 Underside of filler OFF ON 1 23 4 DIP switch settings should be completed at time of initial installation check local building code Factory settin...

Page 5: ... Specific project or custom wiring diagrams available on re quest consult the dormakabatechinical service department Product intended for indoor use NOTE Always disconnect power prior to making any connections or service It is recommended that the 120VAC power be supplied from an Uninterrupted Power Supply UPS to ensure proper operation during a power failure Always observe proper static discharge...

Page 6: ...flashes green audible alarm is off Initiated by rotating the key clockwise approximately 180 degrees until switch engages hold key until mode is activated DPS input is disabled Re arm Mode From alarm mode unit goes to the delayed egress mode Initiated by rotating the key clockwise approximately 180 degrees until switch engages hold key until mode is activated From the bypass mode unit goes to the ...

Page 7: ...uired order through Service Parts model number CBCLBL Consult with local code authority s having jurisdiction See CBC Secton 1003 1 10 Paragraph 6 KEEP PUSHING THIS DOOR WILL OPEN IN 15 SECONDS ALARM WILL SOUND LED light codes Solid Green Delayed Egress Mode Slow Flashing Green Bypass Mode Fast Flashing Green Authorized Egress Mode Solid Yellow Delay Mode Solid Red Alarm Mode This product meets or...

Page 8: ...uctions 95011817 1135 88 IDE 20 01 2020 Exit Device 8 Pair of door template 1 8 Pair of doors 9100 DE Delayed Egress Exit Devices x YR09LFSC Electric Trim Fair Secure x ES100 Power Supply x ES105 Power Transfer x 3914W Sounder x MC 4 DPS x Card Readers dormakaba ...

Page 9: ...tructions 95011817 1135 88 IDE 20 01 2020 Exit Device 9 Single door template 1 9 Single Door 9300 DE Delayed Egress Exit Device x YR09LFSC Electric Trim Fail Secure x ES100 Power Supply x ES105 Power Transfer x 3914W Sounder x MC 4 DPS x Card Readers dormakaba ...

Page 10: ...www dormakaba us dormakaba DORMA USA Inc T 800 523 8483 ...

Reviews: