dormakaba 9000 Delayed Egress Exit Device Installation
Instructions
95011817 (1135-88) IDE-20
01-2020
Exit Device
5
Basic wire connection
1.5 Basic wire connection
1
2
3
4
5
6
7
8
9
10
11
12
DORMA ES100
Minimum 18 AWG
wire recommended for
24VDC inputs (red &
black) leads.
DORMA ES105
(Power transfer)
"required"
* For 24VDC inputs only (red & black wires).
Note: Wire run is from supply to device
and back to the supply.
WIRE 18AWG 16AWG 14AWG 12AWG
FEET 25 50 75 100
Maximum Wire Length From Power Supply To
Device & Back To Supply In Feet x Wire Gage/Size
Monitoring
Outputs
Control Inputs
CAUTION:
TURN OFF 120VAC POWER PRIOR TO MAKING ANY CONNECTIONS TO TERMINALS
WHITE
BLACK
GREEN
(NEUTRAL)
(HOT)
(GROUND)
120 VAC
POWER LINE
(1.0 AMP MAX.)
From UPS
Power Source
Green Ground
Screw Located
On Chassis
dormakaba MODEL ES100
24 VOLT DC POWER SUPPLY
FUSE
PUSH
TO RESET
CIRCUIT
BREAKER
3.0 AMP
24VDC
3/4 AMP
120VAC
REPLACE WITH 3AG 3/4 AMP
SLO-BLOW TYPE FUSE ONLY
NO
CONNECTION
ZONE 2
ZONE 1
CONTROL
SWITCH
CONTROL
SWITCH
OUTPUT
TERMINALS
24VDC
OUTPUT
TERMINALS
24VDC
(+)
(+)
(+)
(+)
(-)
(-)
(IN)
(IN)
(AD100 220V Version Optional)
Note: "The fire alarm contact is to be
used as a supplementary feature and
not intended to replace required fire
alarm appliances".
Specific project or custom wiring diagrams available on re-
quest, consult the
dormakaba
techinical service department.
“Product intended for indoor use.”
NOTE: Always disconnect power prior to making any
connections or service.
It is recommended that the 120VAC power be supplied
from an Uninterrupted Power Supply (UPS) to ensure
proper operation during a power failure.
Always observe proper static discharge grounding pro-
cedure's when installing or servicing the DE device.
Wires that interconnect (+) 24Vdc, (-) 24Vdc, authorized
egress/auto reset, and all other secondary connections must
be located within the same room as the panic hardware per
UL294
.
For ULC installations:
Some
"Authorities Having Juris-
diction"
also require an illumination level of 100' feet at
the door, to be provided by the emergency power supply
system.
(12) Wire primary connection
bundle 22" in length.
DPS
(See Page 6 for typical
wiring of control inputs
and monitoring outputs.)
BLACK: (-) 24VDC IN
RED: (+) 24VDC IN
WHITE: AUTHORIZED EGRESS/AUTO RESET
ORANGE: BYPASS/RE-ARM
GREY: DPS N/C
VIOLET: ALARM RELAY COMMON
GREEN: RED OUTPUT EMITTER
BROWN: RED OUTPUT COLLECTOR
BLUE: GREEN OUTPUT EMITTER
YELLOW: GREEN OUTPUT COLLECTOR
PINK: ALARM RELAY N/C
TAN: ALARM RELAY N/O
Grey
Black
(6) Wire secondary connection
bundle 22" in length.
BLACK: NOT USED
RED: TIED TOGETHER WITH
BLUE: 24VDC for acc.
GREEN: FIRE ALARM CONTACT
BROWN: 24VDC for acc.
VIOLET: CHECK EXIT
OTHER DOOR ON PAIRS