dormakaba 8600 EMR Installation Instructions
08281010
03-2020
8600 EMR
17
Wiring: alarm initiation
4.14 SD-2 detector sensitivity test (ULC required only)
Fig.23
Voltage output terminals are provided to measure the sensitivity of the smoke detector. With power applied to
the detector, connect a volt meter to the two test terminals. The normal range is between 1.27 - 3.38 Vdc.
Sensitivity test
terminals
FINAL INSTALLATION
AND TEST
4.15 Hold open
Fig.24
Hold open position is preset at approximately 90°. Loosen set screws using 3/32” hex wrench. Slide hold open
device to desired position. Retighten set screws securely.
Hold open device
Hold open set screws - 3/32” hex
Hold open force adjustment - 5/32 hex.
Clockwise = stronger
Less Hold Open Angle
Greater Hold Open Angle
4.16 Check connections
Fig.25
After installation is completed, check all connections. The LED will blink every seven (7) to ten (10) seconds to
indicate the unit is operating properly.
LED
4.17 Engage hold open
Fig.26
Open door so slide shoe engages with hold open
assembly.
To test the detector, insert a small screwdriver into the
slot in the light pipe of the detector. Turn counter-
clockwise and hold for 10 seconds. The LED should
remain continually red and allow the door to close.