background image

dormakaba 8600 EMR Installation Instructions

08281010

03-2020

8600 EMR

17

Wiring: alarm initiation

4.14 SD-2 detector sensitivity test (ULC required only)

Fig.23 

Voltage output terminals are provided to measure the sensitivity of the smoke detector. With power applied to 
the detector, connect a volt meter to the two test terminals. The normal range is between 1.27 - 3.38 Vdc.

Sensitivity test 

terminals

FINAL INSTALLATION 

AND TEST

4.15 Hold open

Fig.24 

  

Hold open position is preset at approximately 90°. Loosen set screws using 3/32” hex wrench. Slide hold open 
device to desired position. Retighten set screws securely.

Hold open device

Hold open set screws - 3/32” hex

Hold open force adjustment - 5/32 hex.

Clockwise = stronger

Less Hold Open Angle

Greater Hold Open Angle

4.16 Check connections

Fig.25 

After installation is completed, check all connections. The LED will blink every seven (7) to ten (10) seconds to 
indicate the unit is operating properly.

LED

4.17 Engage hold open

Fig.26 

Open door so slide shoe engages with hold open 
assembly.

To test the detector, insert a small screwdriver into the 
slot in the light pipe of the detector. Turn counter-
clockwise and hold for 10 seconds. The LED should 
remain continually red and allow the door to close.

Summary of Contents for 8600DE EMR

Page 1: ...8600 EMR Surface Applied Closer with Detector Installation instructions 08281010 03 2020 EN ...

Page 2: ...0 4 5 Wire gauge 11 4 6 SD 2 detector to main electromagnet connection 12 4 7 SD 2 detector to auxiliary solenoid connection 12 4 8 Solenoid attachment to UL ULC listed alarm control panel 12 4 9 SD 2 detector interconnection 13 4 10 SD 2 detector to remote area detector 14 4 11 SD 2 detector to audible signal appliance 14 4 12 SD 2 detector to remote alarm indicator lamp 15 4 13 Alarm initiation ...

Page 3: ...unit or remote detector or both It can be a single installation or part of any of the multiple arrangements described above An auxiliary unit double door applications is a companion to the main unit and its electromagnet de energizes along with the main unit A remote open area detector sensing smoke alarms the 8600 EMR to which it is connected and any other 8600 EMR to which it is interconnected S...

Page 4: ... 2 2 Install detector Fig 2 Fig 1 2 1 1 8600T and 8600DE Install with detector cut out toward latch edge of door Use two 1 4 20x2 metal or two No 14x2 3 4 wood screws 8600T and 8600DE Standoff 8600PT Hinge Hinge C L C L 2 1 2 8600PT Install with detector cut out toward latch edge of door Use two 1 4 20x2 metal or two No 14x2 3 4 wood screws End cap End cap Slot 2 3 Installing the slide channel Fig...

Page 5: ...dormakaba 8600 EMR Installation Instructions 08281010 03 2020 8600 EMR 5 Closer 2 4 Install closer to door Fig 4 Left hand door 8600T and 8600DE Right hand door 8600PT Right hand door Left hand door ...

Page 6: ...Attach main arm to door closer 2 5 2 Place arm on top pinion as shown at 45 angle 2 5 3 Secure with pinion screw 6mm hex key Left hand door Right hand door 8600T and 8600DE 8600PT 2 5 1 With door in closed position rotate spindle 45 with wrench 2 5 2 Place arm on spindle 2 5 3 Open door and secure with pinion screw Left hand door Right hand door 6mm hex key 45 45 Rotate pinion Rotate pinion Hinge ...

Page 7: ...ing speeds sweep latch backcheck delayed action Fig 7 3 2 Adjust spring force Fig 8 S L DA BC Latch Sweep Delayed action Backcheck positioning Backcheck Closer size Max door weight lbs Door width Full turns Interior Exterior 8616 3 100 2 6 11 4 125 3 2 6 0 5 150 3 6 3 5 6 200 4 3 6 13 8656 5 150 3 6 3 7 6 200 4 3 6 0 Spring force ...

Page 8: ...ntact ratings Alarm and or accessory contacts 1 25 A at 24 VDC or 3 A at 120 VAC resistive maximum Trouble contacts 500 mA at 24 VDC resistive maximum SD 2 Detector connection list Function Terminal AC DC 24V INPUT 3 14 ALARM CONTACTS NORMALLY OPEN 1 2 ELECTROMAGNET 6 9 REMOTE ALARM INDICATOR LAMP 8 REMOTE ALARM INDICATOR LAMP 7 INTERCONNECT 15 INTERCONNECT 4 TROUBLE CONTACTS NORMALLY CLOSED 5 13 ...

Page 9: ...nsformer Optional Note For ULC installation transformer must install in 4 x 4 electrical box x 3 deep minimum 4 3 Power supply 24V AC DC Fig 11 24V AC DC The step down transformer is not used in this connection Connect 24V AC DC power to terminals 3 and 14 on the detectors These connections are not polarity dependent If the unit is connected to a second unit connect terminal 3 of the first unit to...

Page 10: ... Installations using a combination of SD 2 modules with and without remote area detectors can be wired accordingly by substituting the wiring diagram section from unit 1 2 or 3 in step 3 above instead of unit 1 2 or 3 below with remote detector The vertical dashed lines indicate where one diagram would be exchanged for another NOTE Input voltage must match detector voltage SD 2 1 SD 2 SD 2 13 12 1...

Page 11: ... the run To the determine the correct wire gauge multiply E1 times D1 Add that quantity to E2 times D2 Repeat the same procedure for each electromagnet to test the last unit in the run Compare the quantity calculated to the chart below The calculated value must be less than or equal to the value corresponding to the appropriate wire gauge 10 GAUGE 11 788 12 GAUGE 7 407 14 GAUGE 4 669 16 GAUGE 2 99...

Page 12: ...connection Strip approximately 1 4 of plastic insulation from the ends of the wires Connect auxiliary hold open solenoid wires to 9 6 of SD 2 detector 4 8 Solenoid attachment to UL ULC listed alarm control panel Fig 16 UL ULC listed alarm control panel Hold open electromagnet Some applications may require input power to the hold open electromagnet to be supplied through a UL ULC listed alarm contr...

Page 13: ...2 but no more than five 5 units can be interconnected SD 2 SD 2 SD 2 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 2 3 1 2b For units used in conjunction with remote are detectors complete wiring connections as illustrated below Heed caution note in SD 2 DETECTOR TO REMOTE AREA DETECTOR section of instruction sheet Additional units are ...

Page 14: ...trated below NOTE The SD 2 is wired as the E O L end of line device for the remote detector Therefore it must act as the last item in the loop SD 2 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 24V AC DC Power Supply Remote Detector UL ULC listed audible signal appliance or control unit 4 11 SD 2 detector to audible signal appliance Fig 19 1 Connect terminals 5 13 of a singular unit directly to a UL ULC lis...

Page 15: ... the job specifications 2 Make all signal initiating connections as illustrated in the appropriate figure below Note wiring differences for units with remote detectors vs units without remote detectors Dashed lines to return loop represent wires required for six 6 wire applications These wires are omitted in four 4 wire applications 3 Connections to only one 1 SD 2 are shown below SD 2 SD 2 13 12 ...

Page 16: ...10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 EOL EOL 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 13 12 1 8 2 9 10 3 4 5 6 7 15 14 11 3 2 1 Return loop UL ULC listed initiating circuit Return loop UL ULC listed initiating circuit Connections for six 6 ...

Page 17: ...sing 3 32 hex wrench Slide hold open device to desired position Retighten set screws securely Hold open device Hold open set screws 3 32 hex Hold open force adjustment 5 32 hex Clockwise stronger Less Hold Open Angle Greater Hold Open Angle 4 16 Check connections Fig 25 After installation is completed check all connections The LED will blink every seven 7 to ten 10 seconds to indicate the unit is ...

Page 18: ... go off Turn the light pipe to the normal position and the unit will resume blinking every second 7 to ten 10 seconds to indicate that it is reset and functioning properly 4 19 Install detector cover Fig 28 Install detector cover Slide tab of cover under end of detector and rotate into position Insert 1 4 40 screw and tighten Detector Tab Rotate Screw 4 20 Install cover Fig 29 COV FC FCSL FMC ...

Page 19: ...YSTEM THE END USER IS ALSO RESPONSIBLE FOR THE ADJUSTMENTS AND MAINTENANCE TO RETAIN THE SYSTEM IN WORKING ORDER 5 Maintenance 5 1 Maintaining the detector Fig 30 The SD 2 detector has been designed to be as maintenance free as possible Normal air borne dust however can accumulate in the detector sensing chamber and cause it to become more sensitive All detectors must be tested and cleaned at leas...

Page 20: ...be difficult to remove the first time Vacuum all areas illustrated below and then blow off same areas with compressed air Before reassembling the detector be sure all parts are free of debris 5 4 Final steps Replace cover and screen assembly Measure and record test voltage at test points RP1 RP2 If the product is operating normally and was cleaned effectively the test voltage will be less than the...

Page 21: ... Detector Tester Models 1H and 25S if and only if it is used 1 with the Model 1490 Accessory 2 with the new formula aerosol as identified by a date code located on the bottom of the can of 1990 or later This date code can be as first numeral last digit of year so that a B0xxx 1990 and B9xxx 1989 3 in accordance with the instruction stated above If the preceding requires are not met the use of Smok...

Page 22: ...www dormakaba com dormakaba DORMA USA Inc 1 Dorma Drive Drawer AC Reamstown PA 17567 USA T 717 336 3881 F 717 336 2106 ...

Reviews: