17
15 Final installation and test.
OPERATION
FIRE ALARM- When the alarm sounds, the alarm
to the solenoid which releases the hold
ELECTRICAL SPECIFICATION
Voltage input- 24VDC +10% -15%
24VAC +10% -15%
Maximum input current- 24VDC 166mA
24VAC 166mA
NORMAL- The closer unit's solenoid will be energized
across a normally closed alarm contact
from 24VDC, 24VAC or 120VAC power
supply based on unit voltage.
contact will open and interrupt current
IMPORTANT: THE UNIT MUST BE TESTED AFTER THE
INSTALLATION, BY THE END USER, TO ASSURE
THAT THE DOOR CLOSER UNITS FUNCTION PROPERLY
WHEN THE ALARM SYSTEM IS ACTIVATED. THE ENTIRE
SYSTEM MUST ALSO BE TESTED PERIODICALLY AFTER
THE INITIAL INSTALLATION TEST, IN CONJUNCTION WITH
THE TESTING OF THE FIRE ALARM SYSTEM. THE END
USER IS ALSO RESPONSIBLE FOR THE ADJUSTMENTS
AND MAINTENANCE TO RETAIN THE SYSTEM IN
WORKING ORDER.
1. After installation is completed, recheck all
connections. Apply power to units.
2. Open door so slide block engages with hold
open assembly.
3. Advise fire officials prior to testing.
5. If the closer is used in conjunction with a
detectored unit, trip the test switch of the
main closer detector as explained in the test
procedure for that unit. After a short time
delay, the hold open electromagnet of both units
will release and the doors will close.
Resetting the test switch will allow
the units to return to standby.
4. Activate system into alarm so the electromagnet
releases and the doors closes.
open allowing the door to close and latch.
16
18
An auxiliary door stop (by others) must be installed to limit the
maximum degree of door swing. Failure to do so may result in
damage to the unit.
Slide wiring connection cover to allow access. Attach bracket and assemble bypass switch.
OPTIONAL:
BYPASS SWITCH
All wiring must comply with national,
Improper voltage to unit, will result in damage to unit and void warranty.
Determine power supply and unit voltage type: 24VAC/ 24VDC. CAUTION!!! DO NOT CONNECT 120VAC TO A 24 VOLT UNIT TYPE!!!
Connect power supply wires, one (1) to terminal block one (1) to bypass switch. connect other bypass switch wire to
terminal block . (Terminal Block can be removed for easier wiring). Slide wiring connection cover over wire connections.
WIRE CONNECTION COVER
NOTE:
state and local electrical codes.
CAUTION:
U.L. LISTED
INCOMING POWER
SMOKE DETECTOR
ALARM CONTROL UNIT OR
THIS CONNECTION IS NOT POLARITY DEPENDENT.
WIRE CONNECTION COVER
TERMINAL BLOCK 18awg MAX.
NOTE:
BYPASS SWITCH
TERMINAL
BLOCK
CONNECTION
INS NO.
PAGE
Rev.
08281000
5 of 5