15 Final installation and test.

OPERATION

FIRE ALARM- When the alarm sounds, the alarm 

to the solenoid which releases the hold

ELECTRICAL SPECIFICATION
Voltage input- 24VDC +10% -15%

            24VAC +10% -15%

Maximum input current- 24VDC 166mA

                    24VAC 166mA 

NORMAL- The closer unit's solenoid will be energized

        across a normally closed alarm contact

from 24VDC, 24VAC or 120VAC power

supply based on unit voltage.

contact will open and interrupt current

IMPORTANT: THE UNIT MUST BE TESTED AFTER THE

INSTALLATION, BY THE END USER, TO ASSURE

THAT THE DOOR CLOSER UNITS FUNCTION PROPERLY

WHEN THE ALARM SYSTEM IS ACTIVATED. THE ENTIRE 

SYSTEM MUST ALSO BE TESTED PERIODICALLY AFTER

THE INITIAL INSTALLATION TEST, IN CONJUNCTION WITH

THE TESTING OF THE FIRE ALARM SYSTEM. THE END 

USER IS ALSO RESPONSIBLE FOR THE ADJUSTMENTS

AND MAINTENANCE TO RETAIN THE SYSTEM IN 

WORKING ORDER.

1. After installation is completed, recheck all 

  connections. Apply power to units.

2. Open door so slide block engages with hold

   open assembly.

3. Advise fire officials prior to testing.

5. If the closer is used in conjunction with a

   detectored unit, trip the test switch of the

   main closer detector as explained in the test 

   procedure for that unit. After a short time 

   delay, the hold open electromagnet of both units

   will release and the doors will close.

   Resetting the test switch will allow

   the units to return to standby.

4. Activate system into alarm so the electromagnet

   releases and the doors closes.

open allowing the door to close and latch.

16

18

An auxiliary door stop (by others) must be installed to limit the 

maximum degree of door swing. Failure to do so may result in 

damage to the unit.

       Slide wiring connection cover to allow access. Attach bracket and assemble bypass switch.

OPTIONAL: 

BYPASS SWITCH

 All wiring must comply with national, 

  Improper voltage to unit, will result in damage to unit and void warranty.

       Determine power supply and unit voltage type: 24VAC/ 24VDC.  CAUTION!!! DO NOT CONNECT 120VAC TO A 24 VOLT UNIT TYPE!!! 

Connect power supply wires, one (1) to terminal block one (1) to bypass switch. connect other bypass switch wire to 

terminal block .  (Terminal Block can be removed for easier wiring).  Slide wiring connection cover over wire connections.    

WIRE CONNECTION COVER 

NOTE: 

 state and local electrical codes.

CAUTION: 

U.L. LISTED

INCOMING POWER

SMOKE DETECTOR

ALARM CONTROL UNIT OR

  THIS CONNECTION IS NOT POLARITY DEPENDENT.

WIRE CONNECTION COVER 

  TERMINAL BLOCK 18awg MAX.

NOTE: 

BYPASS SWITCH

TERMINAL

BLOCK

CONNECTION

INS NO.

PAGE

Rev.

08281000

5 of 5

08/13