After washing, before connecting to the electric system, leave the device to dry completely.
When planning the location of the device there should be taken into account the space for free opening
of the doors. The devices should be moved away from the wall to ensure free air circulation through the
condenser. It is necessary to leave 40 cm of free space at least above the device and not less than 10 cm of
free space on the sides and at the back which ensures a proper air circulation for the correct operation of the
device.
Check if the floor is levelled where the device is to be located. Then, level the device, using adjusting
feet, checking whether the door is closed well at the same time.
In accordance with the EN378 standard it should be ensured that the room where the
device with R290 medium is to be located has the proper volume. 1 m
3
is required for 8
g of R290 refrigerant. The amount of R290 refrigerating medium is specified on the
rating place of the device.
CONNECTION TO ELECTRIC SYSTEM
The construction of the device is made according to the appropriate directives and harmonised
standards:
- low voltage directive 2014/35/UE,
- electromagnetic compatibility directive 2014/30/UE,
- PN-EN 60335-2-89:2012, PN-EN 60335-1:2012 standards,
- PN-EN 55014-1:2017-06, PN-EN-55014-2:2015-06 standards,
- PN-EN 61000-3-2:2019-04, PN-EN 61000-3-3:2013-10 standards.
The device is adapted to be supplied from the 230V 50Hz line and should be supplied from a separate
low voltage circuit. A grounded plug-in socket must be equipped with anti-shock protection selected,
according to the requirements of local standards and regulations, in compliance with the parameters
specified on the rating plate. The parameters of a residual current device should be selected according to the
current value, specified on the rating plate. The devices are provided with a flexible power supply cable of
HO5VV-F type (3x1,5mm², including protective conductor). The damaged power supply cable should be
replaced by a specialist from technical service or by a skilled person with appropriate qualifications.
The devices are equipped with a terminal to connect external equipotential bonding, marked by a
symbol
. Before connecting the device the installation correctness and effectiveness of equipotential
bonding operation should be checked in accordance with PN-IEC-60364-4-41.
The device can be started when effectiveness of anti-shock protection is confirmed by results
of measurements carried out according to the regulations in force.
The device can be connected to the electric system when it is stated that the electric system fulfils the
afore-mentioned requirements. The device is connected by inserting a plug of connecting cable into the plug-
in socket. A device, prepared in such a way, is ready to operate.
Because during transport the device could be inclined by more than 30
from the vertical,
wait about 1 hour before connecting the device to the power supply system. Otherwise, the
condensing unit can be damaged.
OPERATION
The temperature of chilled space and operating cycle of the refrigeration unit can vary. It depends on
the ambient temperature, amounts of inserted fresh products and heat inflow from outside. Therefore it is
necessary to avoid opening the door when unnecessary and inserting warm foodstuffs with temperatures
that significantly exceed the storage temperatures. Otherwise, it can considerably increase the chilling time
of products.
It is recommended to avoid a long contact of the skin with cold surfaces of the device or cold products.
The protective clothing should be used in case of longer contact. The failure to use the protective clothing
can cause torpidity or frostbite.