Pr Mode (Pump Control Mode)
Drive
Pr-51 :
Communication ID Setup
It is CAN Communication ID on Multi-Drive control mode.
Be sure to not duplicate ID for setup.
Pr-53 :
Alternation method
It determines the order of Q-Driver’s run, stop, alternation on Multi-Drive operation mode.
Setting is available for Ver 1.3x
When Pr-50 CAN comm. mode is 0, alternation is set 0.
Pr-54 :
Lead Pump Alternation Time
Alternative operation refers to an operation that when it reaches time specified by the user,
the drive with a lot of power consumed is to be stopped and the one with less power
consumption is to be started alternatively at the same time in order to prevent a specific
drive(pump) being operated constantly. If times is set, drives are forcedly shifted.
Functional Description
Single Mode
Setup Data
0 (Factory Setting)
1 ~ 6
Multi-Drive
control
Comm. ID No.
Related Functions
dr-02
Pr-52
Pr-53
Pr-54
Pr-55
Pr-61
Target Frequency Input Method
CAN Communication Speed
Lead Pump Alternation method
Lead Pump Alternation Time
Stand-by Pump Waiting Time
PID Type on Multi-Drive control
Functional Description
Setup Data
0 (Factory Setting)
In order if ID
1
In order of low watt-hour
Functional Description
Setup Data
0
Release of alternation
1 ~ 24 (hour)
Alternation time setup. (Factory Setting 12[hour])