background image

Donaldson Company, Inc.© 1998

17

4.0

4.0

4.0

4.0

4.0 OPERATION

OPERATION

OPERATION

OPERATION

OPERATION

   Turn the unit on/off as required for your
operation. When the airflow becomes low, turn
the unit off, wait until the fan runs down and the
shake cycle is complete and then restart the unit.
The RVS fan must operate for at least 30 seconds
to reset the shake cycle control logic.

5.0

5.0

5.0

5.0

5.0 ROUTINE MAINTENANCE

ROUTINE MAINTENANCE

ROUTINE MAINTENANCE

ROUTINE MAINTENANCE

ROUTINE MAINTENANCE

5.1

5.1

5.1

5.1

5.1 Dust Drawer Models

Dust Drawer Models

Dust Drawer Models

Dust Drawer Models

Dust Drawer Models

   Empty the collector dust drawer periodically or
whenever it becomes two-thirds full. Also remove
any dust that has settled to the bottom of the dust
compartment. Shut off the collector fan before
emptying the dust drawer.

5.2

5.2

5.2

5.2

5.2 Hopper Models

Hopper Models

Hopper Models

Hopper Models

Hopper Models

1.  The hopper is not for dust storage. Empty it

periodically as necessary to keep the dust in
the hopper at a minimum. If a drum or pail is
used, empty it when two-thirds full. Shut off
the collector before emptying the drum or pail.

2.  If the unit has a pail with a gate, close the gate

and empty the pail. Reinstall the pail and open
the gate. The collector fan does not need to be
shut off if this procedure is followed.

3.0

3.0

3.0

3.0

3.0 ELECTRICAL

ELECTRICAL

ELECTRICAL

ELECTRICAL

ELECTRICAL

1.  Make electrical connections to the disconnect

switch*, fan starter*, fan motor and control
box. See Figure 16—Electrical Wiring Diagram
and reference 2SG-40533-00 Single Filter
Cleaning Mechanism Print. Fan access is
through the top door of the cabinet.

* Customer supplied

2.  

Start the fan motor and check fan for proper

rotation

 as indicated by the arrow on the fan

housing. Proper rotation is extremely
important. Even if the fan is running in the
wrong direction, it will deliver approximately
40% of its rated air volume on the Single RVS-
5/10/15. If the rotation is incorrect, reverse any
two leads (3 phase only) on the output side of
the fan motor starter.

Disconnect and lockout all electrical
power to the collector before
performing any service work.

All electrical work must be done
by a qualified electrician according
to local codes.

•  Check the air exhaust outlet at

the top of the collector to be
sure that it is not blocked or
that material is not stored over
the exhaust opening.

•  Stand clear of the fan exhaust

during the rotation check.

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

All electrical controls should be
remote mounted on collectors with
explosion vents.

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

Summary of Contents for Torit RVS-10

Page 1: ...or Without Hopper With or Without Hopper Includes Installation Operation and Service Instructions Includes Installation Operation and Service Instructions Includes Installation Operation and Service I...

Page 2: ...burning objects or lit cigarettes into the hood or ducting of any dust control system Avoid mixing combustible materials with dust generated from grinding of ferrous metals due to the potential fire h...

Page 3: ...tion 5 1 1 1 NormalOperation 5 1 1 2 Filter Cleaning 5 6 2 0 Installation 6 2 1 Inspection 6 2 2 Pre Installation 6 2 3 Location 6 2 4 Assembly of Hopper and Separator 8 2 5 Assembly of Hopper and Sep...

Page 4: ...T iew of T iew of T iew of T iew of Typical RVS Dust Collector ypical RVS Dust Collector ypical RVS Dust Collector ypical RVS Dust Collector ypical RVS Dust Collector Clean Air Outlet Filter Element...

Page 5: ...inet inlet and is deflected downward by the inlet deflector It then passes through a tight mesh screen on the outside of the filter The screen spaced 1 inch away from the filter media catches fibrous...

Page 6: ...f the filter cartridge opens after the fan is shut off allowing fine dust particles collected on the filter media to escape The dust falls down into the dust pan or optional hopper for disposal as sho...

Page 7: ...pper Separator Installation Legs to Hopper Separator Installation Legs to Hopper Separator Installation Legs to Hopper Separator Installation Sealant Crossbraces Sealant Hopper Crossbraces Hopper or S...

Page 8: ...ments Attachments 2 5 1 Square to Round Inlet Adapter Install the square to round inlet adapter to the separator inlet as shown in Figure 5 2 5 2 55 Gallon Drum Cover Pack Install the 55 Gallon drum c...

Page 9: ...tion 55 Gallon Drum Cover Pack Installation 55 Gallon Drum Cover Pack Installation O Ring Gasket Round VS Collar Clamp Drum Cover Drum Ref Supplied by Others Figure 7 Figure 7 Figure 7 Figure 7 Figure...

Page 10: ...igure 9 Figure 9 40 Liter Pail Pack Installation 40 Liter Pail Pack Installation 40 Liter Pail Pack Installation 40 Liter Pail Pack Installation 40 Liter Pail Pack Installation Cabinet Clamp Sight Gla...

Page 11: ...top cover and retain 8 M8 15mm bolts 2 Set silencer pack on top of cabinet as shown 3 Use rubber seal between silencer and top of cabinet as needed 4 Fasten silencer to cabinet using 8 M8 15mm bolts 2...

Page 12: ...t hopper cabinet only 2 Install 4 rivnuts in the enlarged cabinet holes per drilling detail 3 Apply sealant to the outside of the cabinet bolt circle 4 Secure the base plate to the cabinet with two bo...

Page 13: ...els RVS 5 10 15 Casters M8 x 70mm Lg Bolts Nuts Washers 4 M8 x 20mm Lg Bolts Nuts Washers 16 Outrigger Weldment Front View 2 6 6 Outrigger Package If the RVS collector has an Outrigger package install...

Page 14: ...l box 2 6 8 Magnehelic Gage Pack The Magnehelic gage should be installed as shown in Figure 14 2 6 9 5 Gallon Pail Insert 55 Gallon Drum Insert The 5 gallon pail insert assembly is shown in Figure 15...

Page 15: ...n Pail Insert 55 Gallon Drum Insert 5 Gallon Pail Insert 55 Gallon Drum Insert 5 Gallon Pail Insert 55 Gallon Drum Insert 5 Gallon Pail Insert 55 Gallon Drum Insert 5 Gallon Pail Insert 55 Gallon Drum...

Page 16: ...ed by Torit 115 VAC P2 Pressure Switch white wired by Torit In grounded systems the L2 wire must be connected to the ground terminal to the transformer 110VACneutral NOTES 1 All electrical work must b...

Page 17: ...the gate The collector fan does not need to be shut off if this procedure is followed 3 0 3 0 3 0 3 0 3 0 ELECTRICAL ELECTRICAL ELECTRICAL ELECTRICAL ELECTRICAL 1 Make electrical connections to the d...

Page 18: ...ter Element Filter Element Filter Element If the fine mesh screen on the filter becomes plugged with fibrous material it can be removed and cleaned Clean with cold water only To remove the screen simp...

Page 19: ...ilter Replacement A slight bleed through on any new filter is normal and will quickly disappear as the filter seasons CAUTION CAUTION CAUTION CAUTION CAUTION 7 Inspect the door gasket on the cabinet a...

Page 20: ...ce fuse with MDX 3 amp fuse only Other types of fuses may cause shaker motor damage 2b Using a volt ohm meter check the output voltage at terminals X1 and X2 on the transformer must be 115 volts AC If...

Page 21: ...seconds minimum for the timing sequence to start The Delta control starts the shake cycle only after the filter element obtains a 3 pressure drop reference Figure 13 Ambient and Delta Pressure Switch...

Page 22: ...er instructions 2b Check the motor internal wiring connections and motor cable connections Correct if needed reference Motor Manufacturer s Wiring Diagram 3a Remove the upper door and check for proper...

Page 23: ...ker arm or replace the shaker assembly completely 1a Rewire per local and national codes for proper wire size 1b Check and correct internal motor wiring for proper connections for your voltage referen...

Page 24: ...d 3 Remove and replace if the ducting is collapsed Remove and clean out debris that is blocking the ducting 4 Check with your local Torit representative for information 5 Check the fan exhaust area fo...

Page 25: ...velcro seam for easy installation and removal The screen must be stretched tightly around the filter and located all the way to the top of the filer end cap covering the perforated liner completely r...

Page 26: ...ormer Voltage Table Transformer Voltage Table Transformer Voltage Table Transformer Voltage Table Transformer Voltage Table TRANSFORMER H1 H2 H3 H4 H5 H6 X2 X1 INPUT VOLTAGE H1 H2 H1 H3 H1 H4 H1 H5 H1...

Page 27: ...sembly Control Box Assembly Control Box Assembly Control Box Assembly O N CTS 60 30 Clean 180 Wait Time 60 Time 90 Sec Detail C 01 Single RVS 5 10 15 All switches preset to OFF position Default set to...

Page 28: ...rol Box Assembly Control Box Assembly Control Box Assembly Control Box Assembly 1 2 3 4 Timer Control 60 30 Clean 180 Wait Time 60 Time 90 Sec Detail C 01 Single RVS 5 10 15 All switches preset to OFF...

Page 29: ...osure 1T3 1T2 1T1 230V WHT BLK 115V ControlEnclosure Fan Mtr MDX 3 3AMP Slo Blo 125 VAC P2 AC IN WHT WHT GRN GRN BLK WHT Timer PC Board M1 VIB Mtr 1 8 HP 115 60 1 Wiring by Torit Wiring by Others Figu...

Page 30: ...re not manufactured by seller and is expressly in lieu of all other warranties expressed or implied including any warranty or merchantability or fitness for a particular purpose or use There are no wa...

Reviews: