Delta P Plus Control Display

Delta P Plus Control 

For complete information, see the most current version of 

the Delta P Plus Installation, Operation, and Maintenance 

manual.

Description

The Delta P Plus Controller monitors the differential 

pressure between the clean-air and dirty-air plenums, 

providing a visual display of the filter condition. When 

combined with a pulse timer, it manages the pressure 

drop by turning the cleaning mechanism On and Off at 

the chosen limits. There are three (3) set points: High 

Pressure On, Low Pressure Off, and Alarm. The first two, 

High Pressure On and Low Pressure Off, control the 

filter cleaning system. The third, Alarm, provides a relay 

output to activate an external alarm supplied by others.
The user can program the Delta P Plus Controller to 

pulse while the collector is running, to maintain a 

relatively constant pressure drop across the filters, pulse 

only after the collector is shut down (after-shift cleaning), 

or a combination of both, cleaning while running as well 

as end of the shift.

Operation

Normal
The Delta P Plus Controller monitors the pressure on 

both sides of the tubesheet while the collector is running. 

As air flows through the filters, the resistance of the 

media and collected dust creates a pressure difference 

or “drop” between the dirty and clean air plenums. The 

Delta P Plus Controller measures the pressure drop and 

provides a visual display in inches water gauge or metric 

(SI) collectors of daPa.
Filter Cleaning
The Delta P Plus Controller offers three filter cleaning 

options.
1.  Differential Pressure Cleaning (DFF) - When the 

pressure drop across the filters reaches the 

Controller’s High Pressure On setpoint, the Controller 

closes an output relay allowing a sequential timer 

to trigger the cleaning valves. When the Controller 

senses that the pressure drop has decreased to 

the Low Pressure Off setpoint, the relay opens and 

the cleaning cycle stops. This sequence continues 

as long as the collector is in use, maintaining the 

pressure drop within a narrow range. 

2.  Downtime Cleaning (DTC) - The Delta P Plus 

Controller monitors the collection system.  When 

the pressure drop exceeds the Low Pressure Off set 

point and then approaches zero again, the Delta P 

Plus Controller runs a delay timer to allow the blower 

to come to a stop and then engages the cleaning 

mechanism for a preselected time.

3.  Combined Differential and Downtime Cleaning 

(ALL) - The Delta P Plus Controller combines the two 

functions described above; maintaining the pressure 

drop in a narrow band and downtime cleaning 

the filters when the collector is shut down. The 

downtime cleaning function can be toggled On or Off 

from the keyboard. 

Alarm
The Alarm setpoint is set to a higher setting than  the 

High Pressure On used to start the filter cleaning cycle. 

It indicates situations when the cleaning system cannot 

reduce the pressure drop due to cleaning system failure, 

lack of compressed air, or the end of the filter’s useful 

life. There is a time delay prior to setting the Alarm to 

prevent nuisance trips. The Delta P Plus Controller also 

provides an input connection for a remote Alarm reset. 

Summary of Contents for Torit AIRPLUS Trunk 2000 T-2000

Page 1: ...s property of the owner Leave with the unit when set up and start up are complete Donaldson Company reserves the right to change design and specifications without prior notice Illustrations are for re...

Page 2: ...on assumes no responsibility or liability for the suitability of any fire and or explosion mitigation strategy or any items incorporated into a collector as part of an owner operators hazard mitigatio...

Page 3: ...Inc Contents Description 1 Purpose and Intended Use 1 Rating and Specification Information 2 Operation 3 Inspection on Arrival 4 Installation Codes and Procedures 4 Installation 4 Foundations or Suppo...

Page 4: ...it Trunk 2000 is used to filter weld fume dust and particulate from plant sources and to recirculate clean air back to the workplace Ceiling hung or wall supported the compact size coupled with large...

Page 5: ...Trunk 2000 T 2000 2 All Collectors Compressed air maximum psig 90 psig 1 11 scf pulse Power and controls 115 VAC Rating and Specification Information Front View Typical Side View...

Page 6: ...gm valve to send a pulse of compressed air through the filter elements from the inside outward removing the dust from the outside of the filter elements The dust then falls into the hopper At the end...

Page 7: ...compromise collector performance Inspect collector to ensure all hardware is properly installed and tight prior to operating collector Installation Use proper equipment and adopt all safety precautio...

Page 8: ...e suspended or hung from overhead supports The supports must be adequate to carry the live load of the collector and installed to reduce sway or vibration to the collector Provide clearance from heat...

Page 9: ...and nuts typical Collector Suspension Both the 12V and 115V power to the collector are supplied from the Torit control box The control box can be mounted where it is convenient to the user When final...

Page 10: ...ting must be used See collector s rating plate for required voltage An electric disconnect switch having adequate amp capacity shall be installed in accordance with Part IX Article 430 of the National...

Page 11: ...nnect switch incoming power supply blower motor starter optional pulse control switch 1TGS solid state timer air regulator bleed type air filter safety exhaust valve automatic condensate valve air sup...

Page 12: ...ol board s preset OFF time At the end of the OFF time the control will energize a solenoid to provide the cleaning pulse for one segment of filter elements and then step to the next segment This cycle...

Page 13: ...ied and turned ON and OFF by the 200 watt maximum load per output solid state switch Pulse ON Time Factory set at 100 milliseconds Do not adjust pulse ON time unless the proper test equipment is avail...

Page 14: ...instructions on the motor s nameplate To reverse rotation three phase power supply Switch any two leads on the motor junction box Do not interchange a power lead with the ground wire Severe personal...

Page 15: ...ir manifold Filter Removal and Installation Use proper safety and protective equipment when removing contaminants and filters Dirty filters may be heavier than they appear Use care when removing filte...

Page 16: ...ure a positive filter gasket seal 7 Check for an accumulation of dust in the storage area and empty as necessary suspension yoke filter cartridge extraction arm filter access cover Filter Removal and...

Page 17: ...nstallation 2 Sweep or brush hopper walls 3 Replace filters and close filter access covers securely See Filter Removal and Installation 4 Remove the dustpans and dispose of dust properly Empty and cle...

Page 18: ...ushings B Bushing barrel and Product bore are tapered C Bushing cap screws D Bushing barrel is split except idler bushings E Removal holes are threaded installation holes are not Hub of blower wheel o...

Page 19: ...the extraction arms to the unit See Extraction Arm Installation and Operation Manual for instructions Do not over tighten thread forming screws 4 Remove lifting equipment 1 4 in diameter rope type sea...

Page 20: ...plenum and the low pressure tap is located in the clean air plenum 1 Choose a convenient accessible location on or near the collector for mounting that provides the best visual advantage 2 Plug the pr...

Page 21: ...Trunk 2000 T 2000 18 This Page Intentionally Left Blank...

Page 22: ...collector for mounting that provides the best visual advantage 2 Mount the gauge to the remote panel or door using the mounting ring retaining ring and four 6 32 x 1 1 4 in screws Do not tighten screw...

Page 23: ...L1 HI LO C NO NC NC NO C C NO NC NC NO C pressure switch L1 L2 1 2 3 sol com timer board transformer blower fan starter Photohelic gauge jumper jumper stop start 1M 115 V Photohelic Gauge Wiring Photo...

Page 24: ...ough the filters creating a pressure drop The Delta P Controller measures the pressure drop and provides a visual display in inches water gauge or metric SI collectors of daPa Filter Cleaning When the...

Page 25: ...f daPa Filter Cleaning The Delta P Plus Controller offers three filter cleaning options 1 Differential Pressure Cleaning DFF When the pressure drop across the filters reaches the Controller s High Pre...

Page 26: ...arge quantity of water in the dust collector when activated Provide adequate drainage to remove water Excess water weight can cause the leg structure to collapse Consult with local authorities when in...

Page 27: ...not installed on T 2000 Install the extraction arm to the T 2000 inlet panel See Extraction Arm Installation and Operation Manual Clean air outlet discharging dust Filters not installed correctly See...

Page 28: ...ment See Solid State Timer and Solid State Timer Wiring Diagram Damper control in extraction arm is closed Check that the damper control s are open The damper handle should be located in line with the...

Page 29: ...door to outdoor Recalibrate with the pressure tubing attached as described in the Delta P Maintenance Manual Delta P Controller ON but cleaning system does not start Pressure tubing disconnected ruptu...

Page 30: ...27 Donaldson Company Inc Date Service Performed Notes Service Notes...

Page 31: ......

Page 32: ...or product misapplication Donaldson also makes no warranty whatsoever as to any goods manufactured or supplied by others including electric motors fans and control components After Donaldson has been...

Reviews: