COMBUSTION PRODUCTS EXHAUSTION
The Evolution boilers are balanced flue oil boilers, so that the combustion products exhaustion is
carried out by means of an outlet duct and an air intake from outside. It can also work by taking the
air intake for the burner from the room, this is how the boilers come set from factory. To operate in
this mode, the room must be sufficiently ventilated and not obstruct or block any ventilation
openings.
4.1
External position of the gas evacuation pipes terminal
The installation of exhaustion of the products of combustion has to be carried out by qualified
personnel staff and it will fulfill the requirements demanded in the legislation and effective
regulatory schemes.
It is recommended that the position at the exhaustion duct exterior portion should be in accordance
with the data of the following figures and table:
Exhaustion duct position
Minimum distance
(mm)
A
under a cornice
300
B
between two horizontal ducts
1000
C
from an adjacent window
400
D
between two vertical ducts
1500
E
from an adjacent ventilation grille
600
F
under a balcony (*)
300
G
under a window
600
H
under a ventilation grille
600
I
from a recess in the building
300
J
from a corner of the building
300
K
from the floor
2500
L
from a vertical or horizontal duct or outlet (**)
300
M
from a frontal surface at a distance of 3 metres from the fume outlet
2000
N
as above, but with an opening
3000
(*)
Providing the width of the balcony is not over 2000 mm.
(**)
If the materials from which the pipe is made are sensitive to the action of the flue gases, this distance should be over 500 mm.
IMPORTANT: All accessories used for combustion product removal and air intake are to be those
supplied by DOMUSA TEKNIK.