background image

BT DUO HE 

 

1

 

SECURITY WARNINGS 

The hydraulic installation should be carried out by qualified personnel, in compliance with the current 
installation regulations. 

All interventions in the system must be carried out by a Technical Assistance Service authorized by 

DOMUSA TEKNIK

, since any modification to its configuration may cause operating errors and serious 

damage.  

This device can be used by children aged 8 years and above and people with reduced physical, sensory 
or mental abilities or lack of experience and knowledge, provided that they have been given 
appropriate supervision or training regarding the use of the device in a safe manner and the dangers 
involved. Children should not play with the appliance. The cleaning and maintenance to be performed 
by the user should not be carried out by children without supervision. 

1.1

 

Freeze Protection 

Precautions should be taken against possible frost, in order to avoid damage to the installation. It is 
advisable to add antifreeze to the water in the tank which should be compatible with public hygiene 
standards and must not be toxic. 

DOMUSA TEKNIK

 recommends the use of propylene glycol. Please 

contact the manufacturer of the product before use. 

For long periods of stoppage of the installation, all 

water in the tank should be emptied

1.2

 

Water Characteristics 

The domestic water should comply with the characteristics defined in the Technical Code of the 
Building . Otherwise, it should be treated. 

In addition, it should comply with Directive 98/83/EC on the quality of water intended for human 
consumption. Special attention should be paid to the following parameters: 

- Maximum chloride concentration: 250 mg/l. 

- Maximum sulphate concentration: 250 mg/l. 

- Sum of maximum chloride and sulphate concentration: 300 mg/l. 

- Maximum conductivity: 600 μS/cm. 

When the chloride concentration in the Domestic Water is higher than 250 mg/l, it is advisable to 
install an anti-corrosion protection in the interior of the tank, preventing the premature deterioration 
of it. 

DOMUSA TEKNIK

 provides as an option an electronic cathodic protection suitable for its line 

of 

BT TRIO

 buffer tanks. For installation, carefully read the installation instructions supplied with it. 

Summary of Contents for BT DUO HE HE 180/60

Page 1: ...INSTALLATION AND OPERATING INSTRUCTIONS BT DUO HE HE 180 60 ...

Page 2: ...vered to the end user It is advisable to carefully read the warnings and advice contained in this manual as they provide important information regarding the safety of the installation as well as use and maintenance The installation of these tanks should be carried out only by qualified personnel in accordance with the regulations in force and following the manufacturer s instructions Both the star...

Page 3: ...ION INSTRUCTIONS 4 3 1 HYDRAULIC INSTALLATION 4 3 2 LOCATION 4 3 3 EQUIPMENT OPTIONS 4 3 3 1 CATHODIC PROTECTION 5 3 3 2 SANIT S HIDRAULIC KIT 5 3 3 3 ELECTRICAL HEATER 5 4 TANK DRAINAGE 5 4 1 PRIMARY CIRCUIT DRAINAGE 5 4 2 DHW TANK DRAINAGE 5 5 MAINTENANCE 6 6 START UP 6 7 EQUIPMENT DELIVERY 6 8 TECHNICAL DATA 7 9 SPARE PARTS 8 ...

Page 4: ...n the tank which should be compatible with public hygiene standards and must not be toxic DOMUSA TEKNIK recommends the use of propylene glycol Please contact the manufacturer of the product before use For long periods of stoppage of the installation all water in the tank should be emptied 1 2 Water Characteristics The domestic water should comply with the characteristics defined in the Technical C...

Page 5: ... 260 395 1720 R E1 R E2 BT DUO HE 180 60 Domestic cold water inlet ES 3 4 M Domestic hot water outlet SS 3 4 M Primary inlet EP 1 H Primary outlet SP 1 H Optional DHW electrical heater R E1 1 1 4 H Optional Heating electrical heater R E2 1 1 4 H Buffer outlet A 1 H Buffer inlet B 1 H Air vent socket P 3 8 H ...

Page 6: ...with a safety valve calibrated to a maximum of 0 3 MPa 3 bar Place dielectric sleeves in the connections of the secondary circuit When the cold water pressure is higher than the design pressure of the appliance a calibrated pressure reducer must be installed at a value not higher than the design pressure To avoid heat losses through the hot water pipe in the tank installation an anti thermosiphon ...

Page 7: ...e two sockets E1 and E2 to connect the two electrical heaters one for DHW and one for the heating circuit DOMUSA TEKNIK supplies three 1 5 2 5 or 3 5 kW electrical heaters as an option For installation please read carefully the installation instructions supplied with them 4 TANK DRAINAGE 4 1 Primary circuit drainage For the correct drainage of the BT DUO HE tank it is advisable to install a cut of...

Page 8: ...perly It is recommended that the user periodically check the pressure level and temperature of the tank as well as the status of valves fittings and accessories 6 START UP In order to valid the guarantee the heat pump must be started up by personnel authorized by DOMUSA TEKNIK Before beginning the start up process check that The installation must be filled with water and well vented The air vent v...

Page 9: ...r standing DHW tank volume 180 Primary buffer volume L 60 Max DHW temperature ºC 70 Max DHW working pressure MPa bar 0 7 7 Max primary temperature ºC 85 Max primary working pressure MPa bar 0 3 3 Dry weight Kg 101 Wet weight Kg 341 Exchange surface m2 3 2 ...

Page 10: ...CACU000038 Cover 4 CTOR000080 M8 washer 5 6 SCHA000746 COTR000006 Elliptic covers holder O ring 7 CFOV000034 Manual air vent valve 8 CFER000083 Compression gland 9 SCON001569 Elliptic cover 10 SOPE000031 Sensor holder sheath 11 CFER000086 1 black trim 12 CFER000184 Compression gland 13 SCOB012550 Sensor holder sheath 14 CFER000087 1 black trim ...

Page 11: ...9 NOTES ...

Page 12: ...San Esteban s n 20730 AZPEITIA 20737 RÉGIL GUipuzcoa Tel 34 943 813 899 www domusateknik com DOMUSA TEKNIK reserves the right to make modifications of any kind to its product characteristics without prior notice CDOC001800 CDOC001800 14 11 22 ...

Reviews: