V E N T I L A T I O N
LAB1306R, Issue 1, March 2018
Page 7
Page 20
1.5
Automatic humidity controlled boost activation/inactivation (for adjustment see 5.12)
From the home screen, press and hold “
SET
” and “
COPY
” simultaneously for 3 seconds
Press “
COPY
” as required to move to ‘Menu 7’ ‘IhuN’
Use the “
+
” or “
-
“ button to set to ‘on’ or ‘off’ (OF) as required
Press “
SET
” to record or “
ESC
” to discard the settings and return to the home screen
1.6
Filter reminder adjustment/inactivation
From the home screen, press and hold “
SET
” and “
COPY
” simultaneously for 3 seconds
Press “
COPY
” as required to move to ‘Menu 1’ ‘Filter’
Use the “
+
” or “
-
“ buttons to change the time delay in steps of 50 hours as required or ‘off’.
Note: The filter check reminder is factory set at the maximum of 3000 hours (approx.
4months - recommended). During adjustment, when this maximum has been reached, the
‘off’ option can be accessed.
Press “
SET
” to record or “
ESC
” to discard the settings and return to the home screen
1.7
Frost protection trigger temperature adjustment
From the home screen, press and hold “
SET
” and “
COPY
” simultaneously for 3 seconds
Press “
COPY
” as required to move to ‘Menu 4’ ‘T5’
Menu T5 sets the frost protection trigger temperature between -15°C and +5°C (Factory
d1°C)
Use the “
+
” or “
-
“ buttons to set the trigger temperature in steps of 1°C