V E N T I L A T I O N

LAB1306R, Issue 1, March 2018 

Page 10

Page 23 

1.12   

Setting the humidity activated boost switching level (%RH) (for activation see 5.5) 

From the home screen, press “

HUM

” to move to the humidity (% RH) activated boost 

setting (Factory default 60% RH – recommended)  

Use the “

+

” or “

-

“ buttons to set the humidity switching level in steps of 1% RH (range 30- 

85%RH) 

Press “

SET

” to record or “

ESC

” to discard the settings and return to the home screen 

1.13    

Programming 

From the home screen, press “

PROG

” (The programme number will flash in the bottom 

left hand corner; P1 to P9 

Use the “

+

” and “

-

“ buttons to view the selected programme number (Factory default is P9) 

The pre-programmed Thermal bypass programmes are shown in the diagram on page 18 

Note: Each square has a time value of 30 minutes. Black squares indicate a time period 

where the unit is in automatic bypass mode i.e. the unit will monitor the temperatures and 

open or close the bypass accordingly.  White squares (blank spaces) indicate a time block 

where the heat exchanger bypass will be permanently set to operate and divert air around 

the heat exchanger regardless of the measured and set temperatures. 

Each of the programmes can be 

edited

 to create bespoke programmes as follows: 

From the home screen, press “

PROG

” 

Use the “

+

” and “

-

“ buttons to select the programme number (Factory default is P9) 

Press “

PROG

”. The programme number will stop flashing and the first block on the 

timeline at the bottom of the screen will begin to flash. 

Select the day to be edited by pressing “

DAY

” until the correct day is displayed along the 

top of the screen (1 – Monday, 2 – Tuesday etc.) 

To add a 30 minute temperature controlled bypass block (a black square) to the timeline, 

ensure that the word “

BYPASS

” is displayed on the screen by pressing “

BYPASS

”.  

Summary of Contents for Bluebrain

Page 1: ...1306R Issue 1 March 2018 Page 1 SPR418 Bluebrain Controller Installation and Operating Instructions It is important to follow the advice in this manual and correctly maintain the system to ensure a he...

Page 2: ...appliance Cleaning and user maintenance shall not be made by children without supervision 3 All wiring must be in accordance with the current IEE Wiring Regulations BS7671 The electrical installation...

Page 3: ...V E N T I L A T I O N LAB1306R Issue 1 March 2018 Page 3 Page 16 1 0 User control interface operation User control interface front view User control interface back view Day...

Page 4: ...DAY The hour text will flash Use the and buttons to set the hour Press DAY The minute text will flash Use the and buttons to set the minute Press DAY The day will flash Use the and buttons to set the...

Page 5: ...ic bypass operation Press COPY four times to move to Menu 7 IhuN Use the or button to set to off OF This action inhibits the automatic humidity controlled boost operation Press SET to return to the ho...

Page 6: ...ow speed cannot be set higher than Boost speed and Boost speed cannot be set higher than Max speed Press SET to record or ESC to discard the settings and return to the home screen 1 4 Automatic heat e...

Page 7: ...Press COPY as required to move to Menu 1 Filter Use the or buttons to change the time delay in steps of 50 hours as required or off Note The filter check reminder is factory set at the maximum of 3000...

Page 8: ...Use the or button to set to on or off Note The Delay on function will always be overridden by automatic humidity sensing Press SET to record or ESC to discard the settings and return to the home scree...

Page 9: ...and is adjustable between 15 C and 25 C Factory default 20 C Use the or buttons to set the operating temperature in steps of 1 C Press SET to record or ESC to discard the settings and return to the h...

Page 10: ...squares indicate a time period where the unit is in automatic bypass mode i e the unit will monitor the temperatures and open or close the bypass accordingly White squares blank spaces indicate a time...

Page 11: ...g PROG the day number will be displayed and then the day to copy to by pressing the and buttons the day number will flash When the two correct days have been selected press COPY and the timeline patte...

Page 12: ...actory settings P1 t3 20 C t4 10 C Humidity 60 Filter 3000 hours Fan 1 Low 20 Fan 1 Boost 50 Fan 1 Max 80 Fan 2 Low 20 Fan 2 Boost 50 Fan 2 Max 80 Bypass temp off T5 Delay on off Delay off off Hum on...

Page 13: ...LAB1199R Issue 4 Apr 2017 Page 25 V E N T I L A T I O N LAB1306R Issue 1 March 2018 Page 13...

Page 14: ...isolated before removing covers to electrical connections Fault Checks and possible solutions Nothing displayed on the controller LCD screen Check there is power connected to the unit Presence of an o...

Page 15: ...ct connection check there is nothing obstructing fan 2 Little or no air is extracting or supplying through the room valves Check that the filters have been removed from the pre commissioning protectiv...

Page 16: ...715523 Web www domusventilation co uk E OE V E N T I L A T I O N V E N T I L A T I O N Domus Ventilation Cambria House Caerphilly Business Park Van Road Caerphilly CF83 3ED Tel 44 0 3443 715523 Fax 44...

Reviews: